ABB RELION RED670 Series Product Manual

Line differential protection
Hide thumbs Also See for RELION RED670 Series:

Advertisement

Quick Links

R E L I O N ® 670 SERIES
Line differential protection RED670
Version 2.2
Product guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB RELION RED670 Series

  • Page 1 — R E L I O N ® 670 SERIES Line differential protection RED670 Version 2.2 Product guide...
  • Page 2: Table Of Contents

    Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
  • Page 3: Application

    1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Issued: March 2018 Revision: C 1. Application Out of Step function is available to separate power system M13635-3 v7 The Intelligent Electronic Device (IED) is used for the sections close to electrical centre at occurring out of step.
  • Page 4 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Add binary I/O boards as required for the application when ordering.
  • Page 5 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Description of configuration A42 GUID-A3E1E81D-9278-4AC1-8AAA-AD0D56DABE23 v1 RED670 A42 – Single breaker with single or three phase tripping 12AI (6I+6U) WA2_VT VN MMXU WA1_VT Control Control Control S SCBR S SCBR S XCBR VN MMXU...
  • Page 6 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Description of configuration B33 GUID-1231CFD6-8CEF-464E-8124-E9F7EFD0FF62 v1 RED670 B33 – Multi breaker with single or three phase tripping 12AI (6I+6U) WA1_VT WA1_CT Control Control 50BF 3I>BF 52PD Control S SCBR S SCBR S SCBR CC RBRF...
  • Page 7 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Description of configuration B42 GUID-D1058782-6EAD-4E94-8513-1D3647E67250 v1 RED670 B42 – Multi breaker with single or three phase tripping 12AI (6I+6U) WA1_VT WA1_CT Control Control 52PD 50BF 3I>BF Control S SCBR S SCBR VN MMXU S SCBR...
  • Page 8 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Description of configuration C42 GUID-C82DE474-FDC4-49CF-AF12-445716D9C6B6 v1 RED670 C42 – Single breaker with single or three phase tripping and back-up distance protection 12AI (6I+6U) DFR/SER DR 21FL DRP RDRE LMB RFLO WA2_VT VN MMXU...
  • Page 9 The basic IED configuration is provided with the signal matrix, been connected in the special way. On request, ABB is single line diagram and the application configuration prepared available to support the re-configuration work, either directly for the functions included in the product by default.
  • Page 10: Available Functions

    1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 are not exposed to the user or do not need 2. Available functions GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1 to be configured are not described in this manual. The following tables list all the functions available in the IED.
  • Page 11: Differential Protection

    1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) Differential protection HZPDIF High impedance differential protection, single phase 3-A02 3-A02 3-A02 3-A02 REFPDIF Restricted earth fault protection, low impedance 0–2 L3CPDIF Line differential protection for 3 CT sets, 2-3 line...
  • Page 12 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) ZMFPDIS High speed distance protection, quad and mho 1–B15 1–B15 1–B15 characteristic ZMFCPDIS High speed distance protection for series comp. lines, quad and mho characteristic PPLPHIZ Phase preference logic...
  • Page 13: Current Protection

    1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Back-up protection functions GUID-A8D0852F-807F-4442-8730-E44808E194F0 v13 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) Current protection PHPIOC Instantaneous phase overcurrent protection OC4PTOC Directional phase overcurrent protection, 51_67 four steps EFPIOC...
  • Page 14: Multipurpose Protection

    1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) SAPTUF Underfrequency protection 3-E04 3-E04 3-E04 3-E04 SAPTOF Overfrequency protection 3-E04 3-E04 3-E04 3-E04 SAPFRC Rate-of-change of frequency protection 3-E04 3-E04 3-E04...
  • Page 15: Control

    1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v16 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) Control SESRSYN Synchrocheck, energizing check and synchronizing SMBRREC Autorecloser 2-H05 1-H04 2-H05 1-H04...
  • Page 16: Logic

    1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) I103POSCMDV IED direct commands with position for IEC 60870-5-103 I103IEDCMD IED commands for IEC 60870-5-103 I103USRCMD Function commands user defined for IEC 60870-5-103...
  • Page 17 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) AND, GATE, INV, Extension logic package LLD, OR, (see Table 6) PULSETIMER, RSMEMORY, SLGAPC, SRMEMORY, TIMERSET, VSGAPC, XOR FXDSIGN Fixed signal function...
  • Page 18 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 3. Number of function instances in APC10 Function name Function description Total number of instances SCILO Interlocking BB_ES A1A2_BS A1A2_DC ABC_BC BH_CONN BH_LINE_A BH_LINE_B DB_BUS_A DB_BUS_B DB_LINE ABC_LINE AB_TRAFO SCSWI...
  • Page 19 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 4. Number of function instances in APC15 Function name Function description Total number of instances SCILO Interlocking BB_ES A1A2_BS A1A2_DC ABC_BC BH_CONN BH_LINE_A BH_LINE_B DB_BUS_A DB_BUS_B DB_LINE ABC_LINE AB_TRAFO SCSWI...
  • Page 20 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 6. Total number of instances for extended logic package Extended configurable logic block Total number of instances GATE PULSETIMER RSMEMORY SLGAPC SRMEMORY TIMERSET VSGAPC...
  • Page 21: Monitoring

    1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) Monitoring CVMMXN Power system measurement CMMXU Current measurement VMMXU Voltage measurement phase-phase CMSQI Current sequence measurement VMSQI Voltage sequence measurement...
  • Page 22: Metering

    1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) I103EF Function status earth-fault for IEC 60870-5-103 I103FLTPROT Function status fault protection for IEC 60870-5-103 I103IED IED status for IEC 60870-5-103 I103SUPERV...
  • Page 23 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v16 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) Station communication LONSPA, SPA SPA communication protocol LON communication protocol HORZCOMM Network variables via LON DNPGEN DNP3.0 communication general protocol MST1TCP,...
  • Page 24 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) IEC 62439-3 Parallel redundancy protocol 1-P23 1-P23 1-P23 1-P23 IEC 62439-3 High-availability seamless 1-P24 1-P24 1-P24 1-P24 redundancy PMUCONF,...
  • Page 25 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 7. Number of function instances in Synchrophasor report, 8 phasors Function name Function description Number of instances PMUCONF Configuration parameters for C37.118 2011 and IEEE1344 protocol PMUREPORT Protocol reporting via IEEE 1344 and C37.118 PHASORREPORT1 Protocol reporting of phasor data via IEEE 1344 and C37.118, phasors 1-8...
  • Page 26: Basic Ied Functions

    1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v13 Table 8. Basic IED functions IEC 61850 or function Description name INTERRSIG Self supervision with internal event list TIMESYNCHGEN Time synchronization module BININPUT, SYNCHCAN, Time synchronization SYNCHGPS, SYNCHCMPPS,...
  • Page 27 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 9. Local HMI functions IEC 61850 or function ANSI Description name LHMICTRL Local HMI signals LANGUAGE Local human machine language SCREEN Local HMI Local human machine screen behavior FNKEYTY1–FNKEYTY5 Parameter setting function for HMI in PCM600 FNKEYMD1–...
  • Page 28 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 The L4CPDIF function applies the Kirchhoff's law, and principle supplemented by an additional advanced internal compares currents entering and leaving the protected multi- fault detector. This results in fast protection with very high end circuit consisting of overhead power lines and cables.
  • Page 29 RED670. Older versions than 670 1.2.3 needed. In this system, a 64 kbits/s or 2 Mbit/s must be verified with ABB. communication channel is only needed between the master and each one of the slave IEDs. The Master-Slave condition...
  • Page 30 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Protected zone Comm. Channels IEC0500043_2_en.vsd IEC05000043 V2 EN-US Figure 9. Five terminal lines with master-master system Protected zone Comm. Channels en05000044.vsd IEC05000044 V1 EN-US Figure 10. Five terminal line with master-slave system Current samples from IEDs located geographically apart from The communication link is continuously monitored, and an each other, must be time coordinated so that the current...
  • Page 31 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 • Startup element is sensitive enough to detect the • It is possible to block the each sub function of startup abnormal status of the protected system element •...
  • Page 32 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 selection makes the function suitable in applications with The independent measurement of impedance for each fault single phase auto-reclosing. loop together with a sensitive and reliable phase selection makes the function suitable in applications with single phase Built-in adaptive load compensation algorithm for the autoreclosing.
  • Page 33 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 which increases the possibility to detect high resistive faults SEMOD153825-5 v7 The ability to accurately and reliably classify different types of on heavily loaded lines , see Figure 14. fault so that single phase tripping and autoreclosing can be used plays an important roll in today's power systems.
  • Page 34 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 The extensive output signals from the phase selection gives also important information about faulty phase(s) which can be used for fault analysis. Forward A current-based phase selection is also included. The operation measuring elements continuously measure three phase currents and the residual current and, compare them with the...
  • Page 35 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 zone) through the phase selector or the first starting zone. GUID-BF2F7D4C-F579-4EBD-9AFC-7C03296BD5D4 v8 The out-of-step protection (OOSPPAM ) function in the IED This can provide fast operate times for evolving faults. can be used for both generator protection and as well for line protection applications.
  • Page 36 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 result will be the same for all bays on a bus since the voltage There are settings for Phasor type (positive sequence, is the same, which is an important condition for operating negative sequence or zero sequence in case of 3-phase with phase preference.
  • Page 37 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 for example, in the case of the primary protection being out of the fault current is almost independent on the fault location in service due to communication or voltage transformer circuit the network.
  • Page 38 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 One undervoltage step with definite time characteristic is also Stub protection STBPTOC available within the function in order to provide functionality M12902-3 v10 When a power line is taken out of service for maintenance for overcurrent protection with undervoltage seal-in.
  • Page 39 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 relatively short time. The function has settable inverse 8. Frequency protection operating curves and independent alarm stages. Underfrequency protection SAPTUF M13349-3 v13 Underfrequency occurs as a result of a lack of generation in Voltage differential protection VDCPTOV SEMOD153862-5 v7 the network.
  • Page 40 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 unsymmetrical conditions such as open phase or The zero sequence detection is recommended for IEDs used unsymmetrical faults. in directly or low impedance earthed networks. It is based on the zero sequence measuring quantities.
  • Page 41 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 can be connected. The synchronizing feature evaluates Normal security means that only the command is evaluated voltage difference, phase angle difference, slip frequency and and the resulting position is not supervised. Enhanced frequency rate of change before issuing a controlled closing security means that the command is evaluated with an of the circuit breaker.
  • Page 42 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Reservation function QCRSV Selector mini switch VSGAPC M13506-3 v5 SEMOD158756-5 v10 The purpose of the reservation (QCRSV) function is primarily The Selector mini switch (VSGAPC) function block is a to transfer interlocking information between IEDs in a safe multipurpose function used for a variety of applications, as a way and to prevent double operation in a bay, switchyard...
  • Page 43 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Phase segregated scheme communication logic for distance Current reversal and weak-end infeed logic for phase protection ZC1PPSCH segregated communication ZC1WPSCH SEMOD141686-4 v3 SEMOD156473-5 v3 Communication between line ends is used to achieve fault Current reversal and weak-end infeed logic for phase clearance for all faults on a power line.
  • Page 44 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 To achieve fast fault clearing for all earth faults on the line, the direct transfer trip logic to ensure tripping of the line only directional earth fault protection function can be supported under abnormal conditions.
  • Page 45 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Three phase undercurrent LCP3PTUC GUID-D8D1A4EE-A87F-46C6-8529-277FC1ADA9B0 v4 The group indication logic function (INDCALH) is used to GUID-E8EA5CE8-ED7A-4FA3-9DAC-83227D53387F v3 Three phase undercurrent function (LCP3PTUC) is designed route several indication signals to a common indication, LED for detecting loss of load conditions.
  • Page 46 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 One of the outputs is inverted. The output signal OUT is 1 if • SRMEMORYQT function block is a flip-flop that can set the input signals are different and 0 if they are the same. or reset an output from two inputs respectively.
  • Page 47 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 16 boolean (logical) signals into an integer. The block input M12153-3 v14 Complete and reliable information about disturbances in the will freeze the output at the last value. primary and/or in the secondary system together with continuous event-logging is accomplished by the disturbance Integer to Boolean 16 conversion IB16...
  • Page 48 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 There are three LEDs on the local HMI (green, yellow and to ten seconds of data before the trigger instant can be saved red), which will display status information about the IED and in the disturbance file.
  • Page 49 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 based on the oil level in the oil insulated devices are used as • Applicable to very long time accumulation (≤ 99999.9 input signals to the function. In addition, the function hours) generates alarms based on the received information.
  • Page 50: Ethernet

    1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M11345-3 v11 17. Human machine interface Precision time protocol PTP Local HMI PTP according to IEEE 1588-2008 and specifically its profile AMU0600442 v15 IEC/IEEE 61850-9-3 for power utility automation is a synchronization method that can be used to maintain a common time within a station.
  • Page 51: Station Communication

    SPA communication protocol Each IED is provided with several communication interfaces SEMOD120134-5 v1 A single glass or plastic port is provided for the ABB SPA enabling it to connect to one or many substation level protocol. This allows extensions of simple substation...
  • Page 52: Remote Communication

    1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Information number parameter for each output range, and the Function status auto-recloser for IEC 60870-5-103 I103AR signal. I103AR is a function block with defined functions for autorecloser indications in monitor direction. This block Function commands generic for IEC 60870-5-103 FunctionType parameter, and the information includes the...
  • Page 53: Hardware Description

    1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Binary input module BIM Binary signal transfer M1769-3 v4 The binary input module has 16 optically isolated inputs and SEMOD52522-4 v8 The remote end data communication is used for the is available in two versions, one standard and one with transmission of analog values for line differential protection or enhanced pulse counting capabilities on the inputs to be...
  • Page 54 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M15243-4 v7 module has one RS485 communication port. The RS485 is a balanced serial communication that can be used either in 2- wire or 4-wire connections. A 2-wire connection uses the same signal for RX and TX and is a multidrop communication with no dedicated Master or slave.
  • Page 55 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M15243-12 v9 IEC06000182-2-en.vsd IEC06000182 V2 EN-US Figure 21. A 1/2 x 19” size IED side-by-side with RHGS6. Case size (mm)/(inches) 6U, 1/2 x 19” 265.9/ 223.7/ 242.1/ 255.8/ 205.7/ 190.5/ 203.7/...
  • Page 56: Connection Diagrams

    Connection diagram, RED670 2.2, B42X00 1MRK002807-DH The latest versions of the connection diagrams can be downloaded from http://www.abb.com/protection-control. Connection diagram, RED670 2.2, C42X00 1MRK002807-DK Connection diagrams for IEC Customized products Connection diagrams for ANSI Customized products Connection diagram, 670 series 2.2...
  • Page 57: Technical Data

    1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 24. Technical data General M10993-1 v3 IP11376-1 v2 Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified requirements Operative range...
  • Page 58 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Energizing quantities, rated values and limits Analog inputs M16988-1 v11 IP15842-1 v1 Table 10. TRM - Energizing quantities, rated values and limits for protection transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range...
  • Page 59 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 11. TRM - Energizing quantities, rated values and limits for measuring transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ± 10% Current inputs Rated current I Operating range (0-1.8) ×...
  • Page 60 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Binary inputs and outputs M12576-1 v11 IP15844-1 v1 Table 14. BIM - Binary input module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V...
  • Page 61 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Maximum 176 binary input channels may The stated operate time for functions be activated simultaneously with influencing include the operating time for the binary factors within nominal range. inputs and outputs.
  • Page 62 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Maximum 176 binary input channels may The stated operate time for functions be activated simultaneously with influencing include the operating time for the binary factors within nominal range. inputs and outputs.
  • Page 63 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M12584-1 v9 The stated operate time for functions include the operating time for the binary inputs and outputs. Table 18. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
  • Page 64 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 SEMOD175395-2 v8 The stated operate time for functions include the operating time for the binary inputs and outputs. Table 19. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs Function of quantity Static binary output trip Rated voltage...
  • Page 65 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M12441-1 v9 The stated operate time for functions include the operating time for the binary inputs and outputs. Table 21. BOM - Binary output module contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Binary outputs...
  • Page 66 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 23. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01%/% Operative range Full wave rectified...
  • Page 67 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 25. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III Ring wave immunity test, 100 kHz 2-4 kV...
  • Page 68 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 27. Environmental tests Test Type test value Reference standard Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1 Cold storage test Test Ab for 16 h at -40°C IEC 60068-2-1 Dry heat operation test Test Bd for 16 h at +70°C...
  • Page 69 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Differential protection M13062-1 v20 Table 30. Restricted earth-fault protection, low impedance REFPDIF Function Range or value Accuracy Operating characteristic Adaptable ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 70 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M16023-1 v9 Table 32. Line differential protection L3CPDIF, L6CPDIF, LT3CPDIF, LT6CPDIF Function Range or value Accuracy Minimum operate current (20-200)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 71 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 32. Line differential protection L3CPDIF, L6CPDIF, LT3CPDIF, LT6CPDIF, continued Function Range or value Accuracy **Operate time, unrestrained negative Min. = 10 ms sequence function Max. = 20 ms **Reset time, unrestrained negative Min.
  • Page 72 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-0BD8D3C9-620A-426C-BDB5-DAA0E4F8247F v4 Table 34. Additional security logic for differential protection LDRGFC Function Range or value Accuracy Operate current, zero sequence current (1-100)% of lBase ±1.0% of I Operate current, low current operation (1-100)% of lBase ±1.0% of I Operate voltage, phase to neutral...
  • Page 73 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Impedance protection M13842-1 v15 Table 35. Distance measuring zone, Quad ZMQPDIS Function Range or value Accuracy Number of zones Max 5 with selectable direction Minimum operate residual (5-1000)% of IBase current, zone 1 Minimum operate current, (10-1000)% of IBase...
  • Page 74 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 SEMOD173239-2 v10 Table 36. Distance measuring zone, quadrilateral characteristic for series compensated lines ZMCPDIS, ZMCAPDIS Function Range or value Accuracy Number of zones Max 5 with selectable direction IBase Minimum operate residual (5-1000)% of...
  • Page 75 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 SEMOD173242-2 v14 Table 38. Full-scheme distance protection, Mho characteristic ZMHPDIS Function Range or value Accuracy Number of zones, Ph-E Max 5 with selectable direction Minimum operate current (10–30)% of IBase Positive sequence impedance, ±2.0% static accuracy (0.005–3000.000) W/phase...
  • Page 76 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 SEMOD153649-2 v8 Table 40. Faulty phase identification with load encroachment FMPSPDIS Function Range or value Accuracy Load encroachment criteria: ±2.0% static accuracy (1.00–3000.00) W/phase Load resistance, forward and (5–70) degrees Conditions: reverse...
  • Page 77 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-9E13C38A-3B6D-402B-98A6-6CDA20632CE7 v5 Table 42. Phase selection, quadrilateral characteristic with settable angle FRPSPDIS Function Range or value Accuracy Minimum operate current (5-500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 78 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-6C2EF52A-8166-4A23-9861-38931682AA7D v7 Table 43. High speed distance protection ZMFPDIS, ZMFCPDIS Function Range or value Accuracy Number of zones 3 selectable directions, 3 fixed directions Minimum operate current, Ph-Ph (5-6000)% of IBase ±1.0% of I and Ph-E...
  • Page 79 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M16036-1 v10 Table 44. Power swing detection ZMRPSB Function Range or value Accuracy Reactive reach ±2.0% static accuracy (0.10-3000.00) W/phase Conditions: Voltage range: (0.1-1.1) x U Current range: (0.5-30) x I Angle: at 0 degrees and 85 degrees Resistive reach (0.10–1000.00) W/loop...
  • Page 80 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-BACA37F7-E945-40BC-BF9D-A65BFC96CA91 v8 Table 48. Phase preference logic PPLPHIZ Function Range or value Accuracy Operate value, phase-to-phase (1 - 100)% of UBase ±0.5% of U and phase-to-neutral undervoltage Reset ratio, undervoltage <...
  • Page 81 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-42119BFF-1756-431C-A5A1-0AB637213E96 v1 Table 49. Phase preference logic PPL2PHIZ Function Range or value Accuracy Operate value, phase-to-phase (1 - 100)% of UBase ±0.5% of U and phase-to-neutral undervoltage Reset ratio, undervoltage <...
  • Page 82 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Wide area measurement system GUID-F0BAEBD8-E361-4D50-9737-7DF8B043D66A v4 Table 51. Protocol reporting via IEEE 1344 and C37.118 PMUREPORT Influencing quantity Range Accuracy Signal frequency ± 0.1 x f ≤ 1.0% TVE Signal magnitude: Voltage phasor (0.1–1.2) x U...
  • Page 83 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Current protection M12336-1 v13 Table 52. Instantaneous phase overcurrent protection PHPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 84 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M12342-1 v21 Table 53. Directional phase overcurrent protection, four steps OC4PTOC Function Range or value Accuracy Operate current, step 1-4 (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 85 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M12340-2 v9 Table 54. Instantaneous residual overcurrent protection EFPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 86 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M15223-1 v17 Table 55. Directional residual overcurrent protection, four steps EF4PTOC Function Range or value Accuracy Operate current, step 1-4 (1-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 87 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v6 Table 56. Four step directional negative phase sequence overcurrent protection NS4PTOC Function Range or value Accuracy Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of I at I £...
  • Page 88 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 SEMOD173350-2 v16 Table 57. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy (0.25-200.00)% of IBase Operate level for 3I ·cosj directional residual ±1.0% of I at I £...
  • Page 89 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M12352-1 v15 Table 58. Thermal overload protection, one time constant LCPTTR/LFPTTR Function Range or value Accuracy Reference current (2-400)% of IBase ±1.0% of I Reference temperature (0-300)°C, (0 - 600)°F ±1.0°C, ±2.0°F Operate time: Time constant t = (1–1000)
  • Page 90 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M12350-1 v12 Table 60. Stub protection STBPTOC Function Range or value Accuracy Operating current (5-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I IBase Reset ratio >...
  • Page 91 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 SEMOD175159-2 v9 Table 63. Directional overpower protection GOPPDOP Function Range or value Accuracy Power level (0.0–500.0)% of SBase ±1.0% of S at S ≤ S for Step 1 and Step 2 ±1.0% of S at S >...
  • Page 92 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v8 Table 65. Voltage-restrained time overcurrent protection VRPVOC Function Range or value Accuracy Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 93 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Voltage protection M13290-1 v15 Table 66. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1.0–100.0)% of ±0.5% of U Absolute hysteresis (0.0–50.0)% of UBase...
  • Page 94 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M13304-1 v14 Table 67. Two step overvoltage protection OV2PTOV Function Range or value Accuracy Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of U at U ≤ U ±0.5% of U at U >...
  • Page 95 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M13317-2 v14 Table 68. Two step residual overvoltage protection ROV2PTOV Function Range or value Accuracy Operate voltage, step 1 - step 2 (1.0-200.0)% of UBase ± 0.5% of U at U ≤...
  • Page 96 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 SEMOD166919-2 v7 Table 70. Voltage differential protection VDCPTOV Function Range or value Accuracy Voltage difference for alarm and trip (2.0–100.0) % of UBase ±0.5% of U UBase Under voltage level (1.0–100.0) % of ±0.5% of U Independent time delay for voltage...
  • Page 97 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Frequency protection M13360-1 v15 Table 73. Underfrequency protection SAPTUF Function Range or value Accuracy Operate value, start function, at symmetrical three (35.00-75.00) Hz ±2.0 mHz phase voltage Operate time, start at f + 0.02 Hz to f - 0.02 Hz Min.
  • Page 98 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M14976-1 v10 Table 75. Rate-of-change of frequency protection SAPFRC Function Range or value Accuracy Operate value, start function (-10.00-10.00) Hz/s ±10.0 mHz/s Operate value, restore enable frequency (45.00-65.00) Hz ±2.0 mHz Definite restore time delay (0.000-60.000) s...
  • Page 99 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Multipurpose protection M13095-2 v10...
  • Page 100 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 76. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, - NegSeq, -3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1-phase2, phase2-phase3, phase3-phase1, MaxPh-Ph, MinPh-Ph, UnbalancePh- Measuring voltage input phase1, phase2, phase3, PosSeq, -...
  • Page 101 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 76. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Independent time delay, overvoltage at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater 0.8 x U to 1.2 x U , step 1 - 2...
  • Page 102 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 76. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Undervoltage: Critical impulse time 10 ms typically at 1.2 x U to 0.8 x Impulse margin time 15 ms typically...
  • Page 103 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Secondary system supervision M12358-1 v10 Table 77. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤ I ±10.0% of I at I >...
  • Page 104 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v5 Table 79. Fuse failure supervision VDSPVC Function Range or value Accuracy Operate value, block of main fuse failure (10.0-80.0)% of UBase ±0.5% of Ur Reset ratio <110% Operate time, block of main fuse failure at 1 x U to 0...
  • Page 105 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Control M12359-1 v15 Table 80. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ±0.5% of U at U ≤...
  • Page 106 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M12379-1 v13 Table 81. Autorecloser SMBRREC Function Range or value Accuracy Dead time: shot 1 “t1 1Ph” (0.000-120.000) s ±0.2% or ±35 ms shot 1 “t1 2Ph” whichever is greater shot 1 “t1 3Ph “...
  • Page 107 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Scheme communication M16038-1 v14 Table 82. Scheme communication logic with delta based blocking scheme signal transmit ZCPSCH Function Range or value Accuracy Scheme type Intertrip Permissive UR Permissive OR Blocking DeltaBlocking Operate voltage, Delta U...
  • Page 108 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 SEMOD166938-2 v6 Table 85. Current reversal and weak-end infeed logic for phase segregated communication ZC1WPSCH Function Range or value Accuracy Detection level phase to neutral (10-90)% of UBase ±0.5% of U voltage Detection level phase to phase...
  • Page 109 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Direct transfer trip GUID-B5714FAE-A87D-4C2D-A167-6CB3522CE1D5 v5 Table 89. Low active power and power factor protection LAPPGAPC Function Range or value Accuracy Operate value, low active power (2.0-100.0)% of SBase ±1.0% of S Reset ratio, low active power <105%...
  • Page 110 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-C99E063D-B377-40D5-8481-9F46D4166AED v3 Table 92. Carrier receive logic LCCRPTRC Function Range or value Accuracy Operation mode 1 Out Of 2 2 Out Of 2 Independent time delay (0.000-60.000) s ±0.2% or ±35 ms whichever is greater GUID-122A206E-27D2-4D15-AD5A-86B68F1ED559 v5...
  • Page 111 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-0E964441-43DE-43B6-B454-485FBBF66B5C v5 Table 95. Negative sequence overcurrent protection LCNSPTOC Function Range or value Accuracy Operate value, negative sequence (3 - 2500)% of IBase ±1.0% of Ir at I ≤ I overcurrent ±1.0% of I at I >...
  • Page 112 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-C4ACE306-2A54-483D-B247-A479D48CBF5F v5 Table 97. Three phase overcurrent LCP3PTOC Function Range or value Accuracy Operate value, overcurrent (5-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio, overcurrent >...
  • Page 113 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Logic M12380-1 v13 Table 99. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater...
  • Page 114 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v3 Table 106. Number of AND instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v3 Table 107. Number of GATE instances Logic block Quantity with cycle time 3 ms...
  • Page 115 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-C6C98FE0-F559-45EE-B853-464516775417 v3 Table 114. Number of TIMERSET instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms TIMERSET (0.000–90000.000) s ±0.5% ±10 ms GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v2 Table 115.
  • Page 116 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-61263951-53A8-4113-82B5-3DB3BF0D9449 v1 Table 122. Number of PULSETIMERQT instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms (0.000–90000.000) s ±0.5% ±10 ms PULSETIMERQT GUID-94C803B4-6C5A-4072-AB5C-20DDE98C9A70 v1 Table 123.
  • Page 117 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-19810098-1820-4765-8F0B-7D585FFC0C78 v7 Table 127. Number of instances in the extension logic package Logic block Quantity with cycle time 3 ms 8 ms 100 ms SLGAPC VSGAPC PULSETIMER GATE —...
  • Page 118 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-B258726E-1129-47C9-94F9-BE634A2085FA v4 Table 132. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC Function Cycle time (ms) Range or value Accuracy Elapsed time integration 0 ~ 999999.9 s ±0.2% or ±20 ms whichever is greater 0 ~ 999999.9 s...
  • Page 119 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Monitoring M12386-1 v16 Table 136. Power system measurement CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) x f ±2.0 mHz Voltage (10 to 300) V ±0.3% of U at U≤ 50 V ±0.2% of U at U>...
  • Page 120 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6 Table 139. Voltage measurement phase-earth VNMMXU Function Range or value Accuracy Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V ±0.2% of U at U > 50 V Phase angle (5 to 175) V ±0.5 degrees at U ≤...
  • Page 121 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M12760-1 v11 Table 143. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in - first out Time tagging resolution 1 ms...
  • Page 122 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v8 Table 145. Insulation supervision for liquid medium function SSIML Function Range or value Accuracy Oil alarm level 1.00-100.00 ±10.0% of set value Oil lockout level 1.00-100.00 ±10.0% of set value Temperature alarm level -40.00-200.00...
  • Page 123 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M13765-1 v5 Table 149. Indications Function Value Buffer capacity Maximum number of indications presented for single disturbance Maximum number of recorded disturbances M12702-1 v4 Table 150. Event recorder Function Value Buffer capacity...
  • Page 124 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Metering M13404-2 v5 Table 155. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value SEMOD153707-2 v5 Table 156.
  • Page 125 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Station communication M15031-1 v9 Table 157. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0 Communication speed for the IEDs...
  • Page 126 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M12589-1 v4 Table 162. SLM – LON port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (1000m/3000 ft typically *) Plastic fiber: 7 dB (10m/35ft typically *) Fiber diameter Glass fiber: 62.5/125 mm...
  • Page 127 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 166. SFP - Galvanic RJ45 Quantity Rated value Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for communication using any protocol Standard IEEE 802.3u 100BASE-TX...
  • Page 128 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 M12756-1 v11 Remote communication Table 168. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber Multi-mode fiber Single-mode fiber Single-mode fiber...
  • Page 129 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Hardware M11778-1 v7 SEMOD53385-1 v1 Table 169. Case Material Steel sheet Front plate Stainless steel with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) M12327-1 v5 Table 170.
  • Page 130 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v3 connections, one blank slot is necessary between two adjacent IO modules. Please refer to the ordering particulars for details. Table 175. NUM: Communication ports 4 Ethernet ports 1 Basic, 3 Optional Ethernet connection type SFP Optical LC or Galvanic RJ45...
  • Page 131 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Basic IED functions M11963-1 v5 Table 177. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out M12331-1 v9 Table 178.
  • Page 132 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 SEMOD141136-2 v9 Table 182. IRIG-B Quantity Rated value Number of channels IRIG-B Number of optical channels Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
  • Page 133 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Inverse characteristic M12388-1 v23 Table 183. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 , 1.5 x I ≤...
  • Page 134 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 185. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is greater æ...
  • Page 135 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 186. IEC Inverse time characteristics for Line differential protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 1.10 IEC 60255-151, ±5.0% or ±40 ms whichever is greater æ...
  • Page 136 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 188. RI and RD type inverse time characteristics for Line differential protection Function Range or value Accuracy RI type inverse characteristic 0.05 ≤ k ≤ 1.10 IEC 60255-151, ±5.0% or ±40 ms whichever is greater ×...
  • Page 137 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 190. IEC Inverse time characteristics for Line Differential protection Function Range or value Accuracy Operating characteristic: k = (0.05-2.00) in steps of 0.01 IEC 60255-151, ± 5.0% or ±...
  • Page 138 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 191. RI and RD type inverse time characteristics for Line Differential protection Function Range or value Accuracy RI type inverse characteristic k = (0.05-2.00) in steps of 0.01 IEC 60255-151, ±...
  • Page 139 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 193. IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 2.00 IEC 60255-151, ±5.0% 1.5 x I ≤...
  • Page 140 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 GUID-2AE8C92E-5DA8-487F-927D-8E553EE29240 v2 Table 195. ANSI Inverse time characteristics for Voltage restrained time overcurrent protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 , ±...
  • Page 141 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 SEMOD116978-2 v10 Table 197. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 142 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 198. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 143 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 199. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of ±5.0% or ±45 ms whichever is greater 0.01 æ...
  • Page 144: Ordering For Customized Ied

    1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 25. Ordering for customized IED GUID-79B6B8D2-5EE1-4456-A767-5820B9FA61D7 v9 Table 200. General guidelines Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
  • Page 145 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 205. Differential functions Function Function Ordering no Position Available Selected Notes and rules identification High impedance differential protection, single phase HZPDIF 1MRK005904-HB Restricted earth fault protection, low impedance REFPDIF 1MRK005904-LC Line differential protection for 3 CT sets, 2-3 line ends...
  • Page 146 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 207. Impedance functions, alternatives Function Function Ordering no Position Available Selected Notes and rules identification Note: One and only one alternative can be selected. Selected qty is 0 for other functions in an unselected alternative. Alternative 1 Distance protection, quadrilateral Distance protection zone, quadrilateral characteristic ZMQPDIS,...
  • Page 147 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 209. Current functions Function Function Ordering no Position Available Selected Notes and rules identification Instantaneous phase overcurrent protection PHPIOC 1MRK005910-AD Directional phase overcurrent protection, four steps OC4PTOC 1MRK005910-BC Instantaneous residual overcurrent protection EFPIOC...
  • Page 148 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 216. General calculation Position Table 217. General calculation functions Function Function Ordering no Position Available Selected Notes and rules identification Multipurpose filter SMAIHPAC 1MRK005915-KB Table 218. Secondary system supervision Position Table 219.
  • Page 149 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 225. Logic functions Function Function Ordering no Position Available Selected Notes and rules identification Configurable logic blocks Q/T 1MRK005922-MX Extension logic package 1MRK005922-AZ Table 226. Monitoring Position Table 227.
  • Page 150 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 232. Mounting selection Mounting details with IP40 of protection from the front Ordering no Selection Notes and rules No mounting kit included 19" rack mounting kit for 1/2 x 19" case or 2xRHGS6 or RHGS12 1MRK002420-BB 19"...
  • Page 151 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 235. Analog system selection Analog system Ordering no Selection Notes and rules When more than one TRM is selected, the connector type on both TRMs must be the same (A compression or B ring lug). Slot position (front view/rear view) No Transformer input module included Only valid if IEC 61850-9-2...
  • Page 152 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 236. Maximum quantity of I/O modules, with compression terminals When ordering I/O modules, observe the maximum quantities according to the tables below. Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but can also be freely placed.
  • Page 153 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 238. Binary input/output module selection Binary input/ Ordering no Selection Notes and rules output modules Slot position (front view/rear view) 1/2 case with 1 █ █ █ These black marks indicate the maximum number of modules per...
  • Page 154 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 238. Binary input/output module selection, continued Binary input/ Ordering no Selection Notes and rules output modules IOM 8 inputs, 1MRK000173-BE 10+2 outputs, RL110, 110-125VDC, 50mA IOM 8 inputs, 1MRK000173-CE 10+2 outputs, RL220,...
  • Page 155 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Table 239. Station communication, remote end serial communication and time synchronization selection Station communication, remote end Ordering no Selection Notes and rules serial communication and time synchronization Slot position (front view/rear view) The maximum number and type of LDCM modules supported...
  • Page 156: Ordering For Pre-Configured Ied

    Multi breaker, 1/3 phase tripping, 2-5 line ends 1MRK004002-FG Single breaker, 1/3 phase tripping, 2-3 line ends 1MRK004002-GG Multi breaker, 1/3 phase tripping, 2-3 line ends 1MRK004002-HG Single breaker, 1/3 phase tripping, with distance protection 1MRK004002-KG ACT configuration ABB standard configuration Selection for position #2...
  • Page 157 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Software options Ordering no Notes and rules No option All fields in the ordering form do not need to be filled in. High impedance differential protection - 3 blocks 1MRK004001-AB Line differential protection 6 CT sets 1MRK004001-AD...
  • Page 158 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Mounting details with IP40 of protection from the front Ordering no Notes and rules No mounting kit included 19" rack mounting kit for 1/2 x 19" case or 2xRHGS6 or RHGS12 1MRK002420-BB 19"...
  • Page 159 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Analog system Ordering no Notes and rules When more than one TRM is selected, the connector type on both TRMs must be the same (A compression or B ring lug). Slot position (front view/rear view) No Transformer input module included Only valid if IEC 61850-9-2...
  • Page 160 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Binary input/ Ordering no Notes and rules output modules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Note: 1 BIM required in position P3 and 1 BOM required in position P4. Slot position (front view/rear view)
  • Page 161 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Binary input/ Ordering no Notes and rules output modules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Note: 1 BIM required in position P3 and 1 BOM required in position P4. IOM 8 inputs, 1MRK000173-CE 10+2 outputs,...
  • Page 162 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 Station communication, remote end serial Ordering no Notes and rules communication and time synchronization Slot position (front view/rear view) The maximum number and type of LDCM modules supported depend on the total amount of I/O and communication modules...
  • Page 163: Ordering For Accessories

    1MRK 512 001-BEN and 1MRK 001024-CA. Multi-breaker/Single or Three Phase trip with external neutral Please refer to the website: www.abb.com/protection-control on current circuit (ordering number RK926 315-BV). for detailed information. The normally open "In test mode" contact 29-30 on the RTXP...
  • Page 164 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 External resistor unit SEMOD120228-4 v8 High impedance resistor unit with resistor and voltage dependent resistor 20-100V, 1ph Quantity: RK 795 101-MA High impedance resistor unit with resistor and voltage dependent resistor 20-100V, 3ph Quantity: RK 795 101-MB High impedance resistor unit with resistor and voltage dependent resistor 100-400V, 1ph...
  • Page 165 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 User documentation Rule: Specify the number of printed manuals requested Application manual Quantity: 1MRK 505 376-UEN ANSI Quantity: 1MRK 505 376-UUS Technical manual Quantity: 1MRK 505 377-UEN ANSI Quantity: 1MRK 505 377-UUS Commissioning manual...
  • Page 166 1MRK 505 379-BEN C Line differential protection RED670 2.2 Product version: 2.2 ANSI Quantity: 1MRK 511 398-UUS Cyber security deployment guideline Quantity: 1MRK 511 399-UEN Application guide, Communication set-up Quantity: 1MRK 505 382-UEN Reference information M2175-3 v4 For our reference and statistics we would be pleased to be provided with the following application data: Country: End user: Station name:...
  • Page 168 — ABB AB Grid Automation Products 721 59 Västerås, Sweden Phone: +46 (0) 21 32 50 00 abb.com/protection-control © Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice.

Table of Contents