ABB RED670 Commissioning Manual page 123

Line differential protection
Hide thumbs Also See for RED670:
Table of Contents

Advertisement

1MRK 505 378-UUS Rev. J
Table 29:
Test point
1
2
3
4
5
6
The table showing test points for phase-to-ground loops is used together with figure 31.
Table 30:
Test point
1
2
3
4
5
6
The table showing test points for phase-to-phase loops is used together with figure 32.
11.4.6.1
Measuring the operating limit of set values
Procedure:
Line differential protection RED670
Commissioning manual
Test points for phase-to-ground loop CG (Ohm/loop)
Value
X
[X1+XN]
R
0
X
0
R
RLdFwd
X
0.85·[X1+XN]
R
0.85·[X1+XN]·1/tan(60°)+RFFwPE
X
0.85·[X1+XN]
R
-0.85·[X1+XN]·
tan (AngNegRes-90°)
X
RFltFwdPG·tan (LdAngle)
R
RFltFwdPG
X
-0,5·RLdFwd·tan (ArgDir)
R
0,5·RLdFwd
Test points for phase-to-phase loops A-B
Value
X
X1
R
0
X
0
R
RLdFwd
X
0.85·X1
R
0.85·X1·1/tan(60°)+0.5
RFLdFwdPP
X
0.85·X1
R
-0.85·X1·tan (AngNegRes-90°)
X
0.5·RFLdFwdPP·tan (ArgLd)
R
0.5·RFLdFwdPP
X
-0.5·RLdFwd·tan (ArgDir)
R
0.5·RLdFwd
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Testing functionality by secondary injection
Comments
XN=(X
-X
)/3
0
1
R≈0.491·(X1+XN)+RFFwPE
Comments
R=0.491·X1+0.5 RFLdFwdPP
GUID-B1B7DEB6-7BC3-4A90-8D8F-E4E69B434AFA v3
Section 11
117