Maintenance - Altronix MAXIMAL FIT MaxFit11FE Installation Manual

Expandable power systems
Table of Contents

Advertisement

5. Connect devices or Altronix sub-assembly modules to be powered to the terminals marked [– DC +]
(Fig. 1h, pg. 5). For auxiliary device connection, this output will not be affected by
Low Power Disconnect or Fire Alarm Interface. Connect device to the terminals
marked [+ AUX –] (Fig. 1f, pg. 5). Refer to page 2 for non power-limited applications.
6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result
in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel
type. Connect battery to the terminals marked [– BAT + ] (Fig. 1g, pg. 5). Use two (2) 12VDC batteries
connected in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH),
CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2
batteries of an appropriate rating.
7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 5) supervisory
relay outputs.
8. To delay AC reporting for 2 hrs., set DIP switch [AC Delay] to OFF position (Fig. 1c, pg. 5).
To delay AC reporting for 1 min., set DIP switch [AC Delay] to ON position (Fig. 1c, pg. 5).
Note: Must be set to ON position for Burglar Alarm Applications.
9. To enable Fire Alarm Disconnect set DIP switch [Shutdown] to ON position. (Fig. 1c, pg. 5).
To disable Fire Alarm Disconnect set DIP switch [Shutdown] to OFF position. (Fig. 1c, pg. 5).
10. Trigger terminals are end of a line resistor supervised (10k Ohms). Opening or shorting trigger terminals
will cause [DC] output to shutdown (Fig. 1d, pg. 5).
11. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching
[Trigger EOL Shutdown] (Fig. 1d, pg. 5).
12. For Access Control Applications: mount UL Listed tamper switch (Altronix Model TS112 or equivalent) at
the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2" from the
right side (Fig. 3a, pg. 7). Connect tamper switch wiring to the Access Control Panel input or the appropriate
UL Listed reporting device.
13. Please ensure that the cover is secured with the provided key lock.
Use 18 AWG or larger for all low voltage power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery).
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test:
Battery Test:
Note:
Expected battery life is 5 years; however, it is recommended to change batteries within 4 years or less if necessary.
- 4 -

Maintenance:

Under normal load conditions the DC output voltage should be checked for proper
voltage level (MaxFitFE Configuration Chart, pg. 2).
Under normal load conditions check that the battery is fully charged, check specified
voltage at the battery terminals and at the board terminals marked [– BAT +] to
ensure that there is no break in the battery connection wires.
Maximum charge current 1.54A.
MaxiFit11FE/13FE/33FE/35FE/37FE/55FE/75FE/77FE Expandable Power Systems Installation Guide
Wiring: