Current Safe Stop; Current Cut - Mitsubishi Electric DXK09ZJ-S Technical Manual

Inverter wall mounted type residential air-conditioner
Table of Contents

Advertisement

Current cut

Current safe stop

Compressor lock, Compressor wiring short circuit, Compressor output is open phase,
Outdoor PCB is faulty, Service valve is closed, EEV is faulty, Compressor faulty.
DXC09, 12 : 1.703Ω (U-V, V-W, U-W) or more at 20ºC
DXC18 : 1.417Ω (U-V), 1.392Ω (V-W), 1.435Ω (U-W) or more at 20ºC

-
-
*  
70
Overload operation, compressor
lock, overcharge
'09•SRK-DB-087D
'11 • SRK-T-118
73

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dxk12zj-sDxk18zj-s

Table of Contents