14: Charger Boost voltage setting
Interface
15: Charger Float voltage setting
Interface
00: Exit setting
Interface

3-6. Operating Mode Description

Operating mode
Online mode
ECO mode
Frequency
Converter mode
Battery mode
Bypass mode
Setting
Parameter 3: Set up the charger boost voltage.
2.25-2.40: setting the charger boost voltage from 2.25
V/cell to 2.40V/cell. (Default: 2.36V/cell)
Setting
Parameter 3: Set up the charger float voltage.
2.20-2.33: setting the charger float voltage from 2.20
V/cell to 2.33V/cell. (Default: 2.28V/cell)
Setting
Exit the setting mode.
Description
When the input voltage is within acceptable
range, UPS will provide pure and stable AC power
to output. The UPS will also charge the battery at
online mode.
Energy saving mode:
When the input voltage is within voltage
regulation range, UPS will bypass voltage to
output for energy saving. The UPS will also
charge the battery at ECO mode.
When input frequency is within 40 Hz to 70 Hz,
the UPS can be set at a constant output
frequency, 50 Hz or 60 Hz. The UPS will still
charge battery under this mode.
When the input voltage is beyond the acceptable
range or power failure, the UPS will backup
power from battery and alarm is sounding every
5 seconds.
When input voltage is within acceptable range
but UPS is overload, UPS will enter bypass mode
or bypass mode can be set by front panel. Alarm
is sounding every 10 seconds.