Viessmann Vitoligno 300-P Service Instructions For Contractors page 48

Pellet boiler
Table of Contents

Advertisement

Codes
Code 1
(cont.)
Coding in the delivered condition
Mixer economy function
A7:0
Without mixer economy
function
Set changeover
A9:7
With pump idle time:
Heating circuit pump
"OFF" in case of set value
modification by changing
the operating mode or
changing the set room
temperature
Room shutdown
B5:5
With remote control:
With room temperature-
dependent heating circuit
pump logic function
Parameter
With heating circuit pump logic function:
address B5:...
Heating circuit pump "OFF"
1
RT
2
RT
3
RT
4
RT
48
> RT
+ 5 K
actual
set
> RT
+ 4 K
actual
set
> RT
+ 3 K
actual
set
> RT
+ 2 K
actual
set
Possible change
A7:1
With mixer economy func-
tion (extended heating cir-
cuit pump logic):
Heating circuit pump also
"OFF":
The mixer has been closed
for longer than 20 min.
Heating circuit pump
"ON":
■ Mixer changes to control
function
or
■ After cylinder heating (for
20 min)
or
■ If there is a risk of frost
A9:0
Without pump idle time
A9:1
Pump idle time adjustable
to
from 1 to 15
A9:15
B5:0
Without room temperature-
dependent heating circuit
pump logic function
B5:1
With room temperature-
to
dependent heating circuit
B5:8
pump logic function (see
the following table)
Heating circuit pump "ON"
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
+ 4 K
set
+ 3 K
set
+ 2 K
set
+ 1 K
set