Code 1
(cont.)
Parameter
With heating circuit pump logic function: Heating circuit
address A5:...
pump "OFF"
1
AT > RT
2
AT > RT
3
AT > RT
4
AT > RT
5
AT > RT
6
AT > RT
7
AT > RT
to
to
15
AT > RT
Coding in the delivered condition
Adjusted OT OFF
A6:36
Extended economy mode
disabled
+ 5 K
set
+ 4 K
set
+ 3 K
set
+ 2 K
set
+ 1 K
set
set
−1 K
set
−9 K
set
Possible change
A6:5
to
A6:35
Extended economy mode
enabled, i.e. the burner and
heating circuit pump will be
switched OFF at a variable
value, adjustable between
5 and 35 °C plus 1 °C. The
mixer is closed. This value
is based on the adjusted
outside temperature, com-
prising the actual outside
temperature and a time
constant. The time con-
stant takes the cooling
down of an average build-
ing into account.
Recommended setting:
"A6:16" to "A6:18"
Codes
47