Viessmann Vitoligno 300-P Service Instructions For Contractors page 59

Pellet boiler
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
6C:60
In conjunction with an
integral solar control
unit:
Maximum cylinder tem-
perature 60 °C
6D:10
In conjunction with an
integral solar control
unit:
Frost protection disabled
6E:130
In conjunction with an
integral solar control
unit:
Max. collector start-up
temperature; the solar cir-
cuit pump is not started
when the collector tem-
perature exceeds 130 °C
6F:20
In conjunction with an
integral solar control unit
and coding address
"6E":
The solar circuit pump
only starts when the col-
lector temperature has
fallen 20 K below the col-
lector start-up tempera-
ture
70:0
DHW circulation pump
"On" according to time
program when DHW
heating is enabled
71:0
DHW circulation pump
"On" according to time
program
Possible change
6C:10
Maximum cylinder temper-
to
ature adjustable from 10 to
6C:90
90 °C
The solar circuit pump
6D:−10
starts when the collector
to
temperature reaches or
6D:+9
falls below the frost protec-
tion temperature selected
here; it stops when the
selected frost protection
temperature is exceeded
by 2 K
6E:110
Value adjustable from 110
to
to 199°C
6E:199
6E:200
Without collector start-up
limit
6F:10
Value adjustable from 10 to
to
50 K
6F:50
70:1
DHW circulation pump
"On" according to time pro-
gram
71:1
"OFF" during DHW heating
to the first set value
71:2
"ON" during DHW heating
to the first set value
Codes
59