Code 1
(cont.)
Overview
Coding
Coding in the delivered condition
Output 52 M1
02:0
Output 52 M1 not used
Output 52 M2
03:0
Output 52 M2 not used
Sensor 2 M1
04:0
Do not adjust
Output 20 M1
05:0
Do not adjust
Maximum temperature
06:...
Maximum boiler water
temperature limit.
Delivered condition
defaulted by the boiler
coding card
Buffer HC ON
34:5
Only for systems with a
heating water buffer cyl-
inder and code "BB:1" the
following must be selec-
ted:
Enable heating circuit
pumps (see following
example)
Possible change
02:1
Output 52 M1 controls the
mixer of heating circuit
HC1
03:1
Output 52 M2 controls the
mixer of heating circuit
HC2
03:2
Output 52 M2 used for the
solar control unit
06:...
Subject to boiler output
(defaulted by the boiler
coding card)
34:0
Value adjustable from 0 to
to
20 K.
34:20
Codes
45