Viessmann Vitoligno 300-P Service Instructions For Contractors page 56

Pellet boiler
Table of Contents

Advertisement

Codes
Code 2
(cont.)
Coding in the delivered condition
52:5
Only in systems with a
heating water buffer cyl-
inder:
The return temperature
raising pump stops when
the boiler water tempera-
ture has fallen below the
buffer cylinder tempera-
ture minus 5 K (top sen-
sor).
54:0
Without solar control unit 54:1
55:0
Without DHW cylinder
56:0
Set DHW temperature
adjustable from 10 to
60 °C
58:0
Without auxiliary function
for DHW heating
59:0
Cylinder heating
Start point: Set value
−2.5 K
Shutdown point: Set
value +2.5 K
5A:0
No function
60:15
During DHW heating, the
boiler water temperature
is max. 15 K higher than
the set DHW tempera-
ture
56
Possible change
52:0
Value adjustable from 0 to
to
10 K
52:10
With Vitosolic 100;
will be recognised auto-
matically
54:2
With Vitosolic 200;
will be recognised auto-
matically
55:1
Cylinder heating,
hysteresis ± 2.5 K
55:2
Adaptive cylinder heating
active
56:1
Set DHW temperature
adjustable from 10 to 75
°C
58:1
Input of a second set DHW
to
value, adjustable from 10
58:75
to 75 °C (observe coding
address "56")
59:1
Starting point adjustable
to
from 1 to 10 K below the set
59:10
value
5A:1
Flow temperature demand
from the DHW cylinder is
the maximum system
value
60:10
The difference between the
to
boiler water temperature
60:50
and the set DHW tempera-
ture is adjustable from 10 to
50 K