Carrier PIC 5+ User Manual page 9

Control for 19 series centrifugal chiller
Table of Contents

Advertisement

Description
Channel #
Damper Valve
DI2
Feedback Fully Close
High Pressure Switch DI3
Ice Build Contact
DI4
Oil Heater Relay
DO1
Oil Pump Relay
DO2
Economizer Damper
DO3
Valve Open
Economizer Damper
DO4
Valve Close
Low Speed ME Brg
AI1
Temp
Low Speed CE Brg
AI2
Temp
High Speed ME Brg
AI3
Temp
High Speed CE Brg
AI4
Temp
Remote Reset Sensor AI5
Guide Vane 1 Actual
AI6
Pos
Common CHWS
AI7
Temp
Auto Water Temp
AI8
Reset
Common CHWR
AI9
Temp
Head Pressure
AO1
Output
EC Valve Feedback
DI1
Fully Open
EC Valve Feedback
DI2
Fully Close
Spare Safety
DI3
Power Request
DI4
Feedback
EC Valve Solenoid /
DO1
Open
EC Valve Close
DO2
Free Cooling Mode
DO3
Power Request
DO4
Output
Entering Evap Water
AI3
Pressure
Leaving Evap Water
AI4
Pressure
Entering Cond Water
AI5
Pressure
Leaving Cond Water
AI6
Pressure
Evap Water Flow
AI8
Measurement
Cond Water Flow
AI9
Measurement
Chilled Water Pump
AO1
(Variable)
Condenser Water
AO2
Pump (Variable)
Tower Fan (Variable)
AO3
Customer Alert
DI3
Free Cooling Start
DI4
Switch
Chilled Water Pump
DO1
Condenser Water
DO2
Pump
Tower Fan High
DO3
Tower Fan Low
DO4
Board # Option
IOB2
IOB2
IOB2
User option, dry contact
IOB2
IOB2
IOB2
IOB2
IOB3
IOB3
IOB3
IOB3
IOB3
User option, 5K thermistor
IOB3
IOB3
Used for lead lag option
IOB3
User option, 4~20mA
IOB3
Used for lead lag option
IOB3
Factory option
IOB3
Factory option
IOB3
Factory option
IOB3
User option, dry contact,
normal open
IOB3
Marine option
IOB3
Factory option
IOB3
Factory option
IOB3
Factory option
IOB3
Marine option
IOB4
User option, if IOB4
installed, same as follows
IOB4
User option
IOB4
User option
IOB4
User option
IOB4
User option, 4~20mA
IOB4
User option, 4~20mA
IOB4
User option, 4~20mA/0~5V
IOB4
User option, 4~20mA/0~5V
IOB4
User option, 4~20mA/0~5V
IOB4
Marine option, dry contact
IOB4
Marine option, dry contact
IOB4
User option
IOB4
User option
IOB4
User option
IOB4
User option
19XR2~E/V/D I/O, 19XRC mapping:
Description
Channel #
Entering Chilled
AI1
Water Temperature
Leaving Chilled Water
AI2
Temperature
Entering Condenser
AI3
Water Temperature
Leaving Condenser
AI4
Water Temperature
Evap. Refrigerant
AI5
Liquid Temperature
Comp Discharge
AI6
Temperature
Condenser Pressure
AI7
Evaporator Pressure
AI8
FS VFD Load Current AI10
Variable Speed Oil
AO1
Pump
Oil EXV Output
AO2
EC Valve Output mA
AO3
Chiller Lockout Input
DI1
Spare Safety
DI2
Remote Contact Input DI3
Remote Emergency
DI4
Stop Input
Stage 1 IGV Increase DO1
Stage 1 IGV
DO2
Decrease
Chiller Alarm Relay
DO3
Motor Winding
AI1
Temperature 1
Thrust Bearing Oil
AI2
Temperature
Oil Sump
AI3
Temperature
Oil Supply
AI4
Temperature
Guide Vane 1 Actual
AI5
Pos
Oil Supply Pressure
AI6
Oil Sump Pressure
AI7
EC Valve Feedback
AI8
Motor Winding
AI9
Temperature 2
Motor Winding
AI10
Temperature 3
Diffuser Pressure
AI11
Guide Vane1 Output
AO1
Diffuser Output
AO2
Evap Water Flow
DI1
Switch
Cond Water Flow
DI2
Switch
Ice Build Contact
DI4
Oil Heater Relay
DO1
Oil Pump Relay
DO2
EC Valve Soleniod /
DO3
Open
Vapor Source SV
DO4
Heat Reclaim
AI3
Entering Temp
Heat Reclaim Leaving
AI4
Temp
Remote Reset Sensor AI5
Board # Option
IOB1
IOB1
IOB1
IOB1
IOB1
IOB1
IOB1
IOB1
IOB1
For free standing VFD
IOB1
Factory option
IOB1
Factory option, 4~20mA
IOB1
Factory option, 4~20mA
IOB1
User option, dry contact,
normal open
IOB1
User option, dry contact,
normal open
IOB1
User option, dry contact,
"Closed" indicates Turn ON
the chiller
IOB1
User option, dry contact,
"Closed" indicates chiller
emergency stop
IOB1
IOB1
IOB1
User option, 24VAC output,
recommend with external
power supply
IOB2
IOB2
IOB2
IOB2
Factory option
IOB2
IOB2
IOB2
IOB2
Factory option, 4~20mA
IOB2
For high voltage motor
IOB2
For high voltage motor
IOB2
Factory option
IOB2
Factory option, for 4~20mA
type guide vane
IOB2
Factory option
IOB2
User option, dry contact,
"Closed" indicates "FLOW"
IOB2
User option, dry contact,
"Closed" indicates "FLOW"
IOB2
User option, dry contact
IOB2
IOB2
IOB2
Factory option
IOB2
Factory option, for 19XRC
IOB3
Heat reclaim option
IOB3
Heat reclaim option
IOB3
User option, 5K thermistor