Carrier PIC 5+ User Manual page 10

Control for 19 series centrifugal chiller
Table of Contents

Advertisement

Description
Channel #
Auto Water Temp
AI6
Reset
Common CHWS
AI7
Temp
Auto Demand Limit
AI8
Input
Common CHWR
AI9
Temp
Refrigerant Leak
AI10
Sensor
Chiller Status Output
AO1
mA
Fire Security Interlock DI1
Customer Alert
DI2
Free Cooling Start
DI3
Switch
Power Request
DI4
Feedback
Chiller Alert Relay
DO2
Free Cooling Mode
DO3
Power Request
DO4
Output
Entering Evap Water
AI3
Pressure
Leaving Evap Water
AI4
Pressure
Entering Cond Water
AI5
Pressure
Leaving Cond Water
AI6
Pressure
Evap Water Flow
AI8
Measurement
Cond Water Flow
AI9
Measurement
Chilled Water Pump
AO1
(Variable)
Condenser Water
AO2
Pump (Variable)
Tower Fan (Variable)
AO3
Chilled Water Pump
DO1
Condenser Water
DO2
Pump
Tower Fan High
DO3
Tower Fan Low
DO4
10
Board # Option
IOB3
User option, 4~20mA
IOB3
Used for lead lag option
IOB3
User option, 4~20mA
IOB3
Used for lead lag option
IOB3
User option, 4~20mA
IOB3
User option, 4~20mA
4mA=OFF 8mA=Tripout
12mA=Shutdown
20mA=Running
IOB3
User option, dry contact,
normal open
IOB3
Marine option, dry contact
IOB3
Marine option, dry contact
IOB3
Marine option
IOB3
User option, 24VAC output,
recommend with external
power supply
IOB3
Marine option
IOB3
Marine option
IOB4
User option, if IOB4
installed, same as follows
IOB4
User option
IOB4
User option
IOB4
User option
IOB4
User option, 4~20mA
IOB4
User option, 4~20mA
IOB4
User option, 4~20mA/0~5V
IOB4
User option, 4~20mA/0~5V
IOB4
User option, 4~20mA/0~5V
IOB4
User option, 24VAC output,
recommend with external
power supply
IOB4
User option, 24VAC output,
recommend with external
power supply
IOB4
User option, 24VAC output,
recommend with external
power supply
IOB4
User option, 24VAC output,
recommend with external
power supply
19DV mapping:
Description
Channel #
Entering Chilled
AI1
Water Temperature
Leaving Chilled Water
AI2
Temperature
Entering Condenser
AI3
Water Temperature
Leaving Condenser
AI4
Water Temperature
Evap. Refrigerant
AI5
Liquid Temperature
Comp Discharge
AI6
Temperature
Condenser Pressure
AI7
Evaporator Pressure
AI8
FS VFD Load Current AI10
Chiller Status Output
AO1
mA
Evap Water Flow
DI1
Switch
Cond Water Flow
DI2
Switch
Remote Contact Input DI3
Remote Emergency
DI4
Stop Input
Economizer Bypass
DO1
Valve
Refrigerant Pump
DO2
Chiller Alarm Relay
DO3
Vapor Venting Line SV DO4
Motor Winding
AI1
Temperature 1
EC Valve Feedback
AI3
Pump Outlet Pressure AI5
Bearing Outlet
AI6
Pressure
Bearing Inlet Pressure AI7
Auto Demand Limit
AI8
Input
Refrigerant Leak
AI9
Sensor
Pump Inlet Pressure
AI10
Guide Vane1 Output
AO1
EC Valve Output mA
AO3
Liquid Level Switch
DI2
High Pressure Switch DI3
Ice Build Contact
DI4
Condenser Control
DO1
Valve
Evaporator Control
DO2
Valve
Condenser Filling
DO3
Valve
Economizer Isolation
DO4
Valve
1st Stage Bearing
AI1
Temp
2nd Stage Bearing
AI2
Temp
Bearing Ref Supply
AI3
Temp
Guide Vane 2 Actual
AI4
Pos
Remote Reset Sensor AI5
Guide Vane 1 Actual
AI6
Pos
Board # Option
IOB1
IOB1
IOB1
IOB1
IOB1
IOB1
IOB1
IOB1
IOB1
For free standing VFD
IOB1
User option, 4~20mA
4mA=OFF 8mA=Tripout
12mA=Shutdown
20mA=Running
IOB1
User option, dry contact,
"Closed" indicates "FLOW"
IOB1
User option, dry contact,
"Closed" indicates "FLOW"
IOB1
User option, dry contact,
"Closed" indicates Turn ON
the chiller
IOB1
User option, dry contact,
"Closed" indicates chiller
emergency stop
IOB1
x
IOB1
IOB1
User option, 24VAC output,
recommend with external
power supply
IOB1
x
IOB2
IOB2
Factory option
IOB2
IOB2
IOB2
IOB2
User option, 4~20mA
IOB2
User option, 4~20mA
IOB2
IOB2
IOB2
Factory option
IOB2
IOB2
IOB2
User option, dry contact
IOB2
x
IOB2
x
IOB2
x
IOB2
x
IOB3
IOB3
IOB3
IOB3
IOB3
User option, 5K thermistor
IOB3