Sensors - Carrier PIC 5+ User Manual

Control for 19 series centrifugal chiller
Table of Contents

Advertisement

3.2 - Sensors

Pressure transducers:
Pressure transducers are used to measure and control the pressures in the unit. These electronic sensors deliver 0 to 5 VDC.
The transducers can be calibrated through the controller. The pressure transducers are connected to the IOBs.
Sensor
Evaporator pressure transducer
Condenser pressure transducer
Economizer pressure transducer
Oil supply pressure transducer
Oil sump pressure transducer
Pump Output Pressure
Bearing Outlet Pressure
Bearing Inlet Pressure
Pump Input Pressure
Evaporator water pressure difference
transducer (Option)
Condenser water pressure difference
transducer (Option)
Evaporator entering water pressure
transducer (Option)
Evaporator leaving water pressure
transducer (Option)
Condenser entering water pressure
transducer (Option)
Condenser leaving water pressure
transducer (Option)
Temperature sensors:
The system uses electronic sensors to measure and control the temperatures in the unit.
There are three types of temperature sensors, 5K thermistor, 10K thermistor and RTD (three wirings, MINCO S100308)
based on the IOB channel configurations.
Sensor
Entering chilled water temperature sensor
Leaving chilled water temperature sensor
Entering condenser water temperature
sensor
Leaving condenser water temperature
sensor
Evap refrig liquid temperature sensor
Comp discharge temperature sensor
Low speed motor end bearing temperature
sensor
Low speed comp end bearing temperature
sensor
High speed motor end bearing temperature
sensor
High speed comp end bearing temperature
sensor
Comp thrust bearing oil temperature sensor Measure the compressor thrust bearing oil temperature
1st Stage Bearing Temp
2nd Stage Bearing Temp
Bearing Ref Supply Temp
Motor winding temperature sensors
Oil sump temperature sensor
Oil supply temperature sensor
The temperature sensor range is -40 ~ +245°F.
Detailed Description
This transducer measures the pressure of the evaporator.
This transducer measures the pressure of the condenser
This transducer measures the pressure of the economizer
This transducer measures the oil pressure in the oil discharge piping
This transducer measures the Oil pressure in the oil sump
This transducer measures the pressure of pump output
This transducer measures the pressure of bearing outlet
This transducer measures the pressure of bearing inlet
This transducer measures the pressure of pump input
This optional transducer measures the evaporator pressure difference
between entering and leaving water.
This optional transducer measures the condenser pressure difference
between entering and leaving water.
This is an option transducer, and it measures the pressure of evaporator
entering water
This is an optional transducer, and it measures the pressure of
evaporator leaving water
This is an optional transducer, and it measures the pressure of
condenser entering water
This is an optional transducer, and it measures the pressure of
condenser leaving water
Detailed Description
measures the temperature of entering evaporator water.
measures the temperature of leaving evaporator water.
measures the temperature of entering condenser water.
measures the temperature of leaving condenser water.
measures the temperature of evaporator refrigerant liquid.
measures the Compressor discharge temperature.
measure the low speed motor end bearing temperature
measure the low speed compressor end bearing temperature
measure the high speed motor end bearing temperature
measure the high speed compressor end bearing temperature
Measure the 1st stage bearing temperature
Measure the 2nd stage bearing temperature
Measure the bearing ref supply temperature
The 3 sensors measure the temperature of compressor motor windings
measures the compressor sump temperature of oil
measures the oil temperature in the oil discharge piping
Chiller Configuration
Standard for 19XR2~E/V/D, 19XR6/7 and 19DV
Standard for 19XR2~E/V/D, 19XR6/7 and 19DV
Standard for 19XR6/7
Standard for 19XR2~E/V/D and 19XR6/7
Standard for 19XR2~E/V/D and 19XR6/7
Standard for 19DV
Standard for 19DV
Standard for 19DV
Standard for 19DV
Optional for 19XR2~E/V/D, 19XR6/7 and 19DV
Optional for 19XR2~E/V/D, 19XR6/7 and 19DV
Optional for 19XR2~E/V/D, 19XR6/7 and 19DV
Optional for 19XR2~E/V/D, 19XR6/7 and 19DV
Optional for 19XR2~E/V/D, 19XR6/7 and 19DV
Optional for 19XR2~E/V/D, 19XR6/7 and 19DV
Chiller Configuration
Standard for 19XR2~E/V/D, 19XR6/7 and 19DV
Standard for 19XR2~E/V/D, 19XR6/7 and 19DV
Standard for 19XR2~E/V/D, 19XR6/7 and 19DV
Standard for 19XR2~E/V/D, 19XR6/7 and 19DV
Standard for 19XR2~E/V/D, 19XR6/7 and 19DV
Standard for 19XR2~E/V/D, 19XR6/7 and 19DV
Standard for 19XR6/7
Standard for 19XR6/7
Standard for 19XR6/7
Standard for 19XR6/7
Standard for 19XR2~E/V/D
Standard for 19DV
Standard for 19DV
Standard for 1-9DV
Standard for 19XR2~E/V/D, 19XR6/7 and 19DV
19XR2~E/V/D and 19DV only has 1 sensor.
Standard for 19XR2~E/V/D and 19XR6/7
Standard for 19XR2~E/V/D and 19XR6/7
7

Advertisement

Table of Contents
loading