Carrier PIC 5+ User Manual page 69

Control for 19 series centrifugal chiller
Table of Contents

Advertisement

Table Name
PIC Table Type
SYS_STAT
Menu Name
Status
sys_ctlm
1
2
sys_stat
3
mas_stat
4
sla_stat
5
sys_perl
6
sys_kw
7
sys_ctlp
8
sys_dem
9
sys_supt
sys_rent
10
Table Name
PIC Table Type
ISM_CAL1
Menu Name
Status
1
2
cal_en
0 to 1
3
ism_ma
4 to 20
4
ismo_per
0 to 100
5
vfd_ma
4 to 20
6
vfdi_per
0 to 100
7
cal_fact
0 to 2000
cal_done
0 to 1
8
Table Name
PIC Table Type
ISM_CAL2
Menu Name
Status
1
2
cal_en
0 to 1
3
vfd_v
0 to 10
4
vfdo_per
0 to 100
5
ism_v
0 to 10
ismi_per
0 to 100
6
7
cal_fact
800 to 1200
8
cal_done
0 to 1
Table Name
PIC Table Type
VFD_STAT
Menu Name
Status
1
cycle_1
no/yes
2
lineim_i
no/yes
3
hi_volt
no/yes
4
low_volt
no/yes
5
lo_dcbus
no/yes
hi_dcbus
no/yes
6
7
vfd_por
no/yes
8
grnd_flt
9
ph_rev
no/yes
10
motor_ov
no/yes
11
start_ok
no/yes
12
rect_pu
no/yes
13
inv_pu
no/yes
14
rect_oi
no/yes
inv_oi
no/yes
15
16
prs_trip
no/yes
17
no_amps
no/yes
18
accelflt
no/yes
19
stop_ok
no/yes
20
ampstop
no/yes
21
rect_ot
no/yes
22
inv_ot
no/yes
23
motim_i
no/yes
lineim_v
no/yes
24
Instance
HMI Menu Path
12H
29
//MAINMENU/MAINTAIN/
Default
Unit
Note Menu text description
0
-
0
-
0
-
0
-
0
%
0
KW
0
°F
0
%
0
0
Instance
HMI Menu Path
12H
31
//MAINMENU/MAINTAIN/
Default
Unit
Note Menu text description
0
-
0
-
4
mA
0
%
4
mA
0
%
0
-
0
-
Instance
HMI Menu Path
12H
32
//MAINMENU/MAINTAIN/
Default
Unit
Note Menu text description
0
-
0
-
0
Volts
0
%
0
Volts
0
%
1000
-
0
-
Instance
HMI Menu Path
12H
34
//MAINMENU/
Default
Unit
Note Menu text description
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
System Control Mode
System Status
Master Run Status
Slave Run Status
System Percent Load
System KW
System Control Point
System Demand Limit
Supply Liquid Temp
Return Liquid Temp
J8B 4-20mA Output
Calibration Enable
ISM Output mA
ISM Output Percent
VFD Reading mA
VFD Reading Percent
Calibration Factor
Calibration Completed
J6 0-10V Input
Calibration Enable
VFD Output Voltage
VFD Output Percent
ISM Reading Voltage
ISM Reading Percent
Calibration Factor
Calibration Completed
Single Cycle Dropout
Line Current Imbalance
High Line Voltage
Low Line Voltage
Low DC Bus Voltage
High DC Bus Voltage
VFD Power On Reset
Ground Fault
Line Phase Reversal
Motor Overload Trip
Start Complete
Rectifier Power Fault
Inverter Power Fault
Rectifier Overcurrent
Inverter Overcurrent
Condenser High Pressure
Motor Amps Not Sensed
Motor Acceleration Fault
Stop Complete
Stop Fault
Rectifier Overtemp
Inverter Overtemp
Motor Current Imbalance
Line Voltage Imbalance
Low
High
CCN
LEN
Limit
Limit
Force
Force
Low
High
CCN
LEN
Limit
Limit
Force
Force
0
1
x
4
20
x
0
100
4
20
x
0
100
0
2000
0
1
Low
High
CCN
LEN
Limit
Limit
Force
Force
0
1
x
0
10
x
0
100
0
10
x
0
100
800
1200
0
1
Low
High
CCN
LEN
Limit
Limit
Force
Force
69