Carrier PIC 5+ User Manual page 78

Control for 19 series centrifugal chiller
Table of Contents

Advertisement

Table Name
PIC Table Type
CONNECT
Menu Name
Status
17
18
bacena
0 to 1
19
bacunit
0 to 1
20
network
1 to 9999
21
bac_id
0 to 9999999
22
auid
0 to 1
23
balmena
0 to 1
24
bacschen
0 to 1
25
mstpaddr
1 to 127
mstpbaud
0 to 5
26
27
28
29
30
maxmastr
1 to 127
31
maxinfof
1 to 255
32
33
ch_opt
0 to 1
34
ch_ip_P1
0 to 255
ch_ip_P2
0 to 255
35
36
ch_ip_P3
0 to 255
37
ch_ip_P4
0 to 255
Table Name
PIC Table Type
SETPOINT
Menu Name
Status
1
ecw_sp
15.0 to 120.0
2
lcw_sp
10.0 to 120.0
3
ecdw_sp
63.0 to 150.0
4
lcdw_sp
68.0 to 150.0
5
ice_sp
15.0 to 60.0
6
dem_base
10.0 to 100.0
7
EWT_OPT
0 to 1
Table Name
PIC Table Type
MAINMENU
Menu Name
Type_Instance
1
GENUNIT
0x0011_i1
2
TEMP
0x0011_i2
3
PRESSURE
0x0011_i3
4
INPUTS
0x0011_i4
5
OUTPUTS
0x0011_i5
6
HYDRLIC
0x0011_i6
7
RUNTIME
0x0011_i7
8
MODES
0x0011_i8
9
SETPOINT
0x0017_i1
10
CONFIG
0xA001_i4
78
Instance
HMI Menu Path
13H
16
//MAINMENU/CONFIG/
Default
Unit
Note Menu text description
-
0
-
0
-
1600
-
1600001
-
0
-
0
-
0
-
1
-
2
-
-
-
-
3
-
5
-
-
0
-
140
-
206
-
129
-
10
-
Instance
HMI Menu Path
17H
1
//MAINMENU/SETPOINT
Default
Unit
Note Menu text description
60
°F
45
°F
104
°F
113
°F
40
°F
100
%
0
-
A001H
Access
PreProc
ALL
NONE
ALL
NONE
ALL
NONE
ALL
NONE
ALL
NONE
ALL
NONE
ALL
NONE
ALL
NONE
USER
NONE
USER
NONE
BACnet Configuration
BACnet/IP Enable
BACnet Metric Unit
BACnet Network
BACnet Identifier
ALC Auto Id Scheme
BACnet Alarms Enable
BACnet Schedule Enable
MS/TP Mac address
MS/TP Baud rate
9600 = 0, 19200 = 1
38400 = 2, 57600 = 3
76800 = 4, 115200 = 5
MS/TP Max Master
MS/TP Max Info Frames
Call Home Configuration
Call Home Option
Call Home IP Addr Part 1
Call Home IP Addr Part 2
Call Home IP Addr Part 3
Call Home IP Addr Part 4
Cooling ECW Setpoint
Cooling LCW Setpoint
Heating ECDW Setpoint
Heating LCDW Setpoint
Ice Build Setpoint
Base Demand Limit
EWT Control Option
PostProc
Menu text description
NONE
General Parameters
NONE
Temperatures
NONE
Pressures
NONE
Inputs Status
NONE
Outputs Status
NONE
Hydraulic Status
NONE
Run Times
NONE
Modes
NONE
Setpoint
NONE
Configuration Menu
Low Limit
0
0
1
0
0
0
0
1
0
1
1
0
0
0
0
0
Low Limit
15
10
63
68
15
10
0
Instance
2
High Limit
1
1
9999
9999999
1
1
1
127
5
127
255
1
255
255
255
255
High Limit
120
120
150
150
60
100
1
Menu icons

Advertisement

Table of Contents
loading