Chiller Shutdown Sequence; Oil Lubrication Control - Carrier PIC 5+ User Manual

Control for 19 series centrifugal chiller
Table of Contents

Advertisement

5.3 - Chiller Start-up Sequence
5.3.1 - Prestart Check
Once start-up begins, the controller performs a series of
pre-start tests to verify that all pre-start alerts and safeties
are within the limits.
PRESTART ALERTCONDITION
STARTS IN 12 HOURS >= 8
OIL SUMP TEMP <= 140F AND OIL SUMP TEMP
<= EVAP_SAT + 50F
CONDENSER PRESSURE >= COND PRESS OVERRIDE
- 20 PSI
Number of recycle restart in the last 4 hours is greater than 5
COMP BEARING TEMP >= COMP BEARING ALERT- 10F
COMP MOTOR WINDING TEMP >= MOTOR TEMP
OVERRIDE - 10F
COMP DISCHARGE TEMP >= COMP DISCHARGE
ALERT- 10F
EVAP_SAT < Evap trip point + EVAP OVERRIDE DELTA T
OR
EVAP REFRIG LIQUID TEMP < Evap trip point + EVAP
OVERRIDE DELTA T
NOTE: Evap trip point = 33F(water) or EVAP REFRIG
TRIPPOINT(brine)
ACTUAL LINE VOLTAGE <= UNDERVOLTAGE
THRESHOLD
(N/A for Eaton/Rockwell UM VFDs)
ACTUAL LINE VOLTAGE >= OVERVOLTAGE THRESHOLD
(N/A for Eaton/Rockwell UM VFDs)
Guide vane 1 has not been calibrated successfully
The compressor RUN STATUS parameter on the default
screen line now reads PRESTART. If one test is not
successful, the start-up is delayed or aborted. If all the tests
are successful, the chilled water pump relay energizes, and
the main screen line now reads STARTUP.
5.3.2 - Startup
One second later, the chilled and condenser water pump
relays are energized.
Five seconds later the control monitors the chilled water and
condenser water flow devices and waits until the WATER
FLOW VERIFY TIME (service-configured, default 5 minutes)
expires to confirm water flow.
After water flow is verified, the water temperature will be
compared to CONTROL POINT plus 1/2 CHILLED
WATER DEADBAND. If the temperature is less than or
equal to this value, the control turns off the condenser pump
relay and goes into a RECYCLE mode.
If the RECYCLE condition is not satisfied, the start-up
sequence continues and checks the guide vane position. For
single-stage compressor ( Comp(Single=0,Dual=1)=0 in
FACTORY configuration ), if the guide vanes are more than
GUIDE VANE CLOSURE AT STARTUP, the start-up waits
until the controller closes the vanes. For dual-stage compressor
(Comp(Single=0,Dual=1)=1 in FACTORY configuration ),
guide vane is to be opened to the initial position "GV1 Closure
at Startup" at "Option Configuration" menu.
If EC valve or Economizer damper valve is equipped and
enabled, control checks the status of these valves position to
be fully closed.
If the vanes and valves position are verified.
When chiller type is 19XR, the oil pump pressure difference
is less than 6 psi (41.4 kPa), the oil pump relay will be
energized.The control then waits until the oil pressure
difference (OIL PRESS VERIFY TIME, operator-
configured, default of 40 seconds) reaches a maximum of 18
psi (124 kPa). After oil pressure is verified, the control waits
40 seconds for oil prelube.
State
Alarm
When chiller type is 19XR6/7, and oil pump kept OFF for
Number
or Alert
over 50 hours. The oil prelube time will be 6 minutes instead
100
Alert
of 40 seconds.
101
Alert
When chiller type is 19DV, The control will check the
102
Alert
refrigerant pump pressure difference, refrigerant pump will
103
Alert
be turned ON if it passed. Then controller waits until the
230
Alarm
refrigerant pump pressure difference reaches 12 psi (82.7
231
Alarm
kPa). After ref pressure is verified, if high side float chamber
with liquid level, refrigerant pump will be kept ON for 20
232
Alarm
seconds; if not, refrigerant pump will be kept ON until there
is liquid level, and then kept on 10 seconds after that.
The compressor start relay energizes to start the compressor.

5.4 - Chiller Shutdown Sequence

233
Alarm
Chiller shutdown begins if any of the following occurs:
234
Alarm
-
Local OFF button is pressed
-
A recycle condition is present (see Recycle Mode section)
235
Alarm
-
The time schedule has gone into unoccupied mode when
236
Alarm
in Network or Local Schedule control mode
-
The chiller protective limit has been reached and chiller
is in alarm
-
The start/stop status (CHIL_S_S) is overridden to stop
from the network when in Network mode
If the chiller is normally shutdown from running, soft stop
shutdown will be performed. The soft stop feature closes the
guide vanes of the compressor automatically if a non-alarm
stop signal occurs before the compressor motor is deenergized.
Any time the compressor is directed to STOP (except in the
cases of a fault shutdown), the guide vanes are directed to
close and VFD will be command to minimum speed for
variable speed compressor, and the compressor shuts off
when any of the following is true:
-
PERCENT LOAD CURRENT (%) drops below the
SOFT STOP AMPS THRESHOLD
-
ACTUAL GUIDE VANE POSITION drops below 4%
-
4 minutes have elapsed after initinize the stop
When any one of the above condition is true, the shutdown
sequence stops the compressor by deactivating the
compressor start relay.
Then the guide vane shall be closed and stay at the fully
closed position.
When chiller type is 19XR2~E, the oil pump relay will be
Turned OFF after 60 seconds post lube.
When chiller type is 19XR6/7, the oil pump relay will be
Turned OFF after 120 seconds post lube.
When chiller type is 19DV, the refrigerant pump relay will
be Turne OFF after 120 seconds post lube.
And then the chilled water/brine pump and condenser water
pump will be shutdown.