Carrier PIC 5+ User Manual page 74

Control for 19 series centrifugal chiller
Table of Contents

Advertisement

Table Name
PIC Table Type
CONF_OPT
Menu Name
Status
astart
0 to 1
1
2
commsens
0 to 1
3
hgbp_opt
0 to 3
4
5
6
hgbp_sel
0 to 3
7
8
9
hpop_gv1
0.5 to 10.0
hgcl_gv1
1.5 to 20.0
10
11
hgb_toff
0.5 to 10
12
hgb_ton
0.5 to 10
13
hgbp_ldb
0.5 to 2.0
14
hdpv_opt
0 to 1
15
hdp_0
20 to 85
16
hdp_100
20 to 85
17
hdpv_min
0 to 100
18
ice_opt
0 to 1
ice_recy
0 to 1
19
20
ice_term
0 to 2
21
22
tfh_sp
55 to 105
23
leak_en
0 to 1
24
leak_ma
4 to 20
25
exv_opt
0 to 1
26
oil_high
100 to 140
27
oil_low
90 to 130
28
gt_fact
0.25 to 3.00
29
gv_srd_f
0.70 to 1.20
30
pd_tcfg
0 to 60
31
evap_t_o
0 to 1
32
evap_ref
0 to 1
33
34
cfa_opt
0 to 1
35
cusa_opt
0 to 1
36
wp_opt
0 to 2
37
38
wfm_opt
39
40
41
fs_opt
0 to 1
42
43
flow4ma
0 to 200
44
flow20ma
0 to 200
45
chwf_bas
0 to 150
46
evpd_bas
0 to 20
47
cdwf_bas
0 to 150
48
cdpd_bas
0 to 20
49
wpd_20ma
10 to 40
50
vssv_dly
0 to 10
51
opvfdmax
35 to 60
52
opvfdstp
0 to 10
53
0 to 1
54
pgon_opt
Table Name
PIC Table Type
CONF_IOB
Menu Name
Status
1
lv_enth
17.0 to 19.0
2
lv_exth
19.0 to 21.0
3
typ_ai11
0 to 6
4
typ_ai12
0 to 6
5
typ_ai13
0 to 6
6
typ_ai14
0 to 6
7
typ_ai19
0 to 5
74
Instance
HMI Menu Path
13H
10
//MAINMENU/CONFIG
Default
Unit
Note Menu text description
0
-
0
-
0
-
-
-
0
-
-
-
5
%
10
%
4
^F
2
^F
1
^F
0
-
25
PSI
50
PSI
0
%
0
-
0
-
0
-
-
75
°F
0
-
20
mA
0
-
122
°F
113
°F
1
-
0.95
-
15
min
1
-
1
-
-
0
-
0
-
0
-
-
0
-
-
0
-
-
0
GPS
0
GPS
0
GPS
0
PSI
0
GPS
0
PSI
10
PSI
5
min
50
PSI
7
%
0
-
0
-
Instance
HMI Menu Path
13H
11
//MAINMENU/CONFIG
Default
Unit
Note Menu text description
17
Volts
19
Volts
4
-
1
4
-
4
-
4
-
2
-
Auto Restart Option
Common Sensor Option
EC Valve Option
No=0, Cont.=1,
ON/OFF=2, mA=3
EC Valve Selection
Disable=0, Surge=1
Low Load=2, Comb=3
ECV Open IGV1 Position
ECV Close IGV1 Position
ECV Off DT for Low Load
ECV On DT for Low Load
ECV Low Load DB
Head Pres Valve Option
Head Pres Delta P 0%
Head Pres Delta P 100%
Head Pressure Min Output
Ice Build Option
Ice Build Recycle
Ice Build Termin Source
Temp=0,Contact=1,Both=2
Tower Fan High Setpoint
Refrig Leakage Option
Refrig Leakage Alarm mA
Oil EXV Option
Oil Temp High Threshold
Oil Temp Low Threshold
Gas Torque Factor
Guide Vane/SRD Factor
Power Recovery Timeout
Evap Liquid Temp Opt
Evap App Calc Selection
Sat Temp=0, Ref Temp=1
Condenser Flush Alert
Customer Alert Option
Water Pressure Option
No=0, Pres.=1, Pres.D=2
Water Flow Measurement
No=0, Flow Meter=1,
Water Pres. D=2
Water Flow Determination
Sat Temp=0,Flow Switch=1
Water Flow at 4mA
Water Flow at 20mA
Evap Flow Rate Baseline
Evap Pres Drop Baseline
Cond Flow Rate Baseline
Cond Pres Drop Baseline
Water Pres Drop @20mA
Vapor Source SV Delay
Max Oil Pressure Diff
Oil Pump VFD Max Step
Vapor Source SV Option
Purge On Idle Option
Low Entered Volt V1 IOB
Low Exited Volt V2 IOB
IOB1 AI#1 Type
IOB1 AI#2 Type
IOB1 AI#3 Type
IOB1 AI#4 Type
IOB1 AI#9 Type
Low Limit
High Limit
0
1
0
1
0
3
0
3
0.5
10
1.5
20
0.5
10
0.5
10
0.5
2
0
1
20
85
20
85
0
100
0
1
0
1
0
2
55
105
0
1
4
20
0
1
100
140
90
130
0.25
3
0.7
1.2
0
60
0
1
0
1
0
1
0
1
0
2
0
3
0
1
0
200
0
200
0
150
0
20
0
150
0
20
10
40
0
10
35
60
0
10
0
1
0
1
Low Limit
High Limit
17
19
19
21
0
6
0
6
0
6
0
6
0
5