Table Name
PIC Table Type
CONF_ISM
Menu Name
Status
com_tout
0 to 255
1
2
star_typ
0 to 3
3
4
5
scycd_en
0 to 1
6
rla
10 to 5000
7
rkw
50 to 9999
8
mot_lra
100 to 65535
9
lrs_del
1 to 10
str_lra
100 to 65535
10
11
rlv
200 to 13800
12
cu_th
5 to 100
13
vu_th
1 to 10
14
ct_ratio
3 to 1000
15
vt_rat
1 to 115
16
cu_per
1 to 10
17
vu_per
1 to 10
18
lfref_en
0 to 1
linefreq
0 to 1
19
20
gfp_en
0 to 1
21
gf_amps
1 to 25
22
gfp_pers
1 to 10
23
gfs_del
1 to 20
24
gfct_rat
150 to 150
25
ovvol_th
105 to 115
26
udvol_th
85 to 95
27
ovud_per
1 to 10
28
uvs_del
1 to 4
Table Name
PIC Table Type
CFGUMVFD
Menu Name
Status
1
comp_hz
47 to 110
2
rlv_i
200 to 13800
3
rla
10 to 2000
4
rla_load
10 to 2000
5
rlv
200 to 13800
6
rpm
1500 to 3600
7
rlkw
0 to 5600
8
skipfrq1
0.0 to 102.0
9
skipfrq2
0.0 to 102.0
10
skipfrq3
0.0 to 102.0
11
skipband
0.0 to 102.0
12
ramp_inc
5 to 60
13
ramp_dec
5 to 60
14
lvim_th
1 to 10
15
lvim_per
1 to 10
16
lcim_th
5 to 40
lcim_per
1 to 10
17
18
mcim_th
5 to 40
19
mcim_per
1 to 10
20
scycd_en
0 to 1
21
pwm_freq
0 to 1
22
23
res_def
0 to 1
24
com_tout
0 to 255
25
mod_tout
0 to 255
gw_baud
1 to 4
26
27
28
72
Instance
HMI Menu Path
13H
4
//MAINMENU/CONFIG/
Default
Unit
Note Menu text description
10
sec
0
-
-
-
0
-
200
AMPS
1500
KW
1000
AMPS
5
cycles
2000
AMPS
460
Volts
15
%
5
%
100
-
1
-
5
sec
5
sec
0
-
0
-
1
-
15
AMPS
5
cycles
10
cycles
150
-
115
%
85
%
5
sec
1
sec
Instance
HMI Menu Path
13H
18
//MAINMENU/CONFIG/
Default
Unit
Note Menu text description
50
Hz
460
Volts
200
AMPS
200
AMPS
460
Volts
3000
rpm
1500
KW
102
Hz
102
Hz
102
Hz
0
Hz
30
sec
30
sec
10
%
10
sec
40
%
10
sec
40
%
10
sec
0
-
0
-
-
0
-
10
sec
2
sec
2
-
-
-
Communication Timeout
Starter Type
Full Volt=0, Redu Volt=1
Solid State=2, FS VFD=3
Single Cycle Dropout
Motor Rated Load Amps
Motor Rated Kilowatts
Motor Locked Rotor Trip
Locked Rotor Start Delay
Starter LRA Rating
Motor Rated Line Voltage
Current Imbal Threshold
Voltage Imbal Threshold
Motor Current CT Ratio:1
Volt Transformer Ratio:1
Current Imbal Persist
Voltage Imbal Persist
Line Frequency Faulting
Frequency(N=50Hz Y=60Hz)
Ground Fault Protection
Ground Fault Current
Ground Fault Persistence
Ground Fault Start Delay
Ground Fault CT Ratio:1
Overvoltage Threshold
Undervoltage Threshold
Over Under Volt Persist
Under Volt Start Delay
Compressor Speed 100%
Rated Line Voltage
Motor Nameplate Current
Motor Rated Load Current
Motor Nameplate Voltage
Motor Nameplate RPM
Motor Nameplate KW
Skip Frequency 1
Skip Frequency 2
Skip Frequency 3
Skip Frequency Band
Increase Ramp Time
Decrease Ramp Time
Line Voltage Imbalance%
Line Volt Imbalance Time
Line Current Imbalance%
Line Current Imbal Time
Motor Current Imbalance%
Motor Current Imbal Time
Single Cycle Dropout
PWM Switch Frequency
2KHz=0, 4KHz=1
Restore Defaults
LEN Comm Timeout
Modbus Comm Timeout
Gateway Modbus Baud Rate
4800=1, 9600=2
19200=3, 38400=4
Low Limit
High Limit
0
255
0
3
0
1
10
5000
50
9999
100
65535
1
10
100
65535
200
13800
5
100
1
10
3
1000
1
115
1
10
1
10
0
1
0
1
0
1
1
25
1
10
1
20
150
150
105
115
85
95
1
10
1
4
Low Limit
High Limit
47
110
200
13800
10
2000
10
2000
200
13800
1500
3600
0
5600
0
102
0
102
0
102
0
102
5
60
5
60
1
10
1
10
5
40
1
10
5
40
1
10
0
1
0
1
0
1
0
255
0
255
1
4