Table Name
PIC Table Type
FACTORY
Menu Name
Status
vfd_fdv
0 to 1
22
23
24
dmp_auto
0 to 1
25
mrn_opt
0 to 1
26
pr_opt
0 to 1
27
cpr_opt
0 to 1
28
Comp_pre
0 to 1
29
pg_opt
0 to 1
lqby_opt
0 to 2
30
31
Table Name
PIC Table Type
CFGGEVFD
Menu Name
Status
1
vfd_gain
0.10 to 1.50
2
vfd_max
90.0 to 110.0
3
vfd_min
50.0 to 89.0
4
vfd_str
65.0 to 100.0
5
vfdculm
0.0 to 99999.0
6
vfdc20ma
10.0 to 5000.0
comp_100
45.0 to 62.0
7
8
vfd_ldap
0 to 1
Table Name
PIC Table Type
SERVICE1
Menu Name
Status
1
ser_pass
0 to 65535
2
3
atom_pre
8.000 to 15.000
4
gv1_lim
30 to 100
gv1stpos
0 to 40
5
6
ctrl_db
0.5 to 2
7
ewtdgain
1 to 3
8
gv1decdb
2 to 10
9
gv1incdb
2 to 10
10
max_gv
1.0 to 4.0
11
dem_20ma
10 to 100
12
dem_pdb
3 to 15
13
ldramprt
5 to 20
tmramprt
1 to 10
14
15
rcysh_dt
0.5 to 4
16
rcyst_dt
2 to 10
17
dmp_dly
1 to 5
18
dmp_cldb
2 to 10
19
dmp_opdb
10 to 20
20
dmp_dt
4 to 10
21
oilpvr_t
15 to 300
22
sf_st_th
40 to 100
wflow_t
0.5 to 5
23
24
mbb_pfcl
0.5 to 2
25
ex_start
0 to 1
26
oilstiro
0 to 3
27
28
0 to 3
29
pgt_set
0 to 1
Instance
HMI Menu Path
13H
1
//MAINMENU/CONFIG/
Default
Unit
Note Menu text description
0
-
-
0
-
0
-
0
-
0
-
0
-
-
0
-
0
-
-
Instance
HMI Menu Path
13H
2
//MAINMENU/CONFIG/
Default
Unit
Note Menu text description
0.75
-
100
%
70
%
100
%
250
AMPS
200
AMPS
50
Hz
1
-
Instance
HMI Menu Path
13H
3
//MAINMENU/CONFIG/
Default
Unit
Note Menu text description
2222
-
-
14.5
PSI
80.7
%
4
%
1
^F
2
-
6
-
6.5
-
2
%
40
%
10
%
5
%
3
^F
1
^F
5
^F
2
min
5
PSI
13
PSI
7
^F
40
sec
70
%
5
min
1
-
0
-
1
-
-
-
65
-
VFD Feedback Voltage Sel
0-5V=0, 0-10V=1
Electrical Damper Valve
Marine Option
Power Request Option
Cont. Power Request
19DV Comp Design Press
44PSI=0, 72PSI=1
Purge System Option
Liquid Bypass Option
No=0, Full=1, Partial=2
VFD Gain
VFD Max Speed Per
VFD Min Speed Per
VFD Start Speed Per
VFD Current Limit
VFD Load Current 20mA
Comp Frequency 100%
VFD Load Current Input
Service Password
Atmospheric Pressure
GV1 Travel Limit
GV1 Closure at Startup
Controlled Fluid DB
Derivatived EWT Gain
Proportional Dec Band
Proportional Inc Band
Maximum GV Movement
Demand Limit At 20 mA
Demand Limit Prop Band
Amps or KW Ramp per Min
Temp Ramp per Min
Recycle Shutdown Delta T
Recycle Restart Delta T
Damper Valve Act Delay
Damper Valve Close DB
Damper Valve Open DB
Damper Action Delta T
Oil Press Verify Time
Soft Stop Amps Threshold
Water Flow Verify Time
Power Calibration Factor
Enable Excessive Starts
Oil Stir Cycle(19XR6/7)
No Stir=0, 30s/30m=1,
1m/4h=2, Comb. 0&1=3
Purge Active Temp SP
Low Limit
High Limit
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
2
Low Limit
High Limit
0.1
1.5
90
110
50
89
65
100
0
99999
10
5000
45
62
0
1
Low Limit
High Limit
0
65535
8
15
30
100
0
40
0.5
2
1
3
2
10
2
10
1
4
10
100
3
15
5
20
1
10
0.5
4
2
10
1
5
2
10
10
20
4
10
15
300
40
100
0.5
5
0.5
2
0
1
0
3
30
90
71