Recommended Shutdown Procedure Using OFFLINE/RESET Switch

Caution: Do not remove a DFE module from an operating chassis system before reading the
following information and instructions.
Precaución: Antes de retirar los módulos DFE del chasis en funcionamiento, lea las siguientes
instrucciones y la información suministrada.
Before pulling a DFE module out of a chassis, 
press or tap on its 
Its CPU LED changes from solid green to blinking between green and amber, indicating that the 
module is shutting down. At the end of the shutdown routine, the CPU LED changes to a 67%/
33% sequence of amber/off, respectively, indicating the module is in a halt state. In this time it is 
safe to restart or remove the module from the chassis.
When a controlled shutdown is initiated from the 
from the time the CPU starts alternately flashing amber/off until the device automatically restarts.
Note: The only safe time to pull a
alternately flashing amber/off. Otherwise, system operation will be interrupted.

Last Resort Shutdown Procedure Using OFFLINE/RESET Switch

Caution: This method of shutting down a DFE module is not recommended except as a last resort,
because all processes currently running on the module will be interrupted resulting in loss of
frames.
Precaución: No se recomienda utilizar este método para apagar los módulos DFE. Recurra a él
sólo como último recurso, puesto que interrumpe todos los procesos del módulo en
funcionamiento, lo que podría resultar pérdidas de frames.
To reset a DFE module without it performing an orderly shutdown routine, 
press and hold the
Pulling any DFE module out of the chassis before it has been shut down is not recommended. The 
only safe time to pull a module out of the chassis is after the completion of a shutdown and the 
management LED is alternately flashing amber/off.
 switch for less than 1 second. 
OFFLINE/RESET
DFE module
OFFLINE/RESET
 switch for approximately 6 seconds. 
Overview of DFE-Platinum Module Shutdown Procedure
, you have 60 seconds 
OFFLINE/RESET switch
out of the chassis is when the CPU LED is
DFE-Platinum Series Hardware Installation Guide 4-7