Huawei FusionModule5000 Product Description page 99

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
Item
PoE port
RS485 port
DI input
BLINK button
Smoke sensor
test button
E-label
Indicators
Table 3-60 describes the indicators on the multi-functional sensor.
Table 3-60 Description of the indicators on the multi-functional sensor
Indicat
or
RUN
ALM
Specifications
One PoE port that complies with IEEE802.3AT
Reserved
One DI input port, 12 V DC power input
Wireless communication:
Press the button for less than 1s to start blinking.
Hold down the button for 1–5 seconds to search for a network and
start networking.
Hold down the button for more than 6 seconds to clear network
parameters.
Supported
Supported
Col
Name
or
Gree
Module
n
running status
indicator
Red
Alarm indicator
Status
Description
Steady on
The power supply is normal.
Off
The power supply is abnormal.
Blinking at
The multi-functional sensor
long intervals
successfully registers with the
ECC800 and the software runs
properly (the indicator blinks at 0.5
Hz, on for 1s and then off for 1s).
Blinking at
The multi-functional sensor fails to
short intervals
register with the ECC800 or the
communication fails (the indicator
blinks at 4 Hz, on for 0.125s and
then off for 0.125s).
Blinking
The indicator blinks at super short
intervals for 0.5s (blinking at 10
Hz, on for 0.05s and then off for
0.05s) and then turns off for 0.5s.
The cycle lasts for 10s.
Steady on
A system failure alarm or smoke
alarm is generated.
92

Advertisement

Table of Contents
loading

This manual is also suitable for:

V100r001

Table of Contents