FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
Power distribution circuit
breakers for IT equipment
Dimensions (H x W x D)
An integrated UPS cabinet works in 380 V, 400 V, or 415 V power mode, and features
redundancy, high reliability, high efficiency, energy saving, environmental protection, and
intelligent and easy operation.
Table 3-8 lists the technical specifications for the integrated UPS.
Table 3-8 Technical specifications for the integrated UPS
Category
Input
Output
Battery
40 A/1P x 18 x 2; 63 A/1P x 6 x 2
2000 mm x 600 mm x 1100 mm
2000 mm x 600 mm x 1200 mm (with a tail frame)
2200 mm x 600 mm x 1200 mm (with a top frame and tail
frame)
Item
Power system
Rated input voltage
Input voltage range
Input frequency range
Input power factor
Rated input current
Rated voltage
Total harmonic
distortion (THD)
(linear load)
Total harmonic
distortion (THD)
(non-linear load)
Power factor
Maximum peak factor
for loads
Overload capability
Number of batteries
Specifications
Three phases
380 V, 400 V, or 415 V AC, three-phase,
four-wire, and PE
80–280 V AC (phase voltage) (When the input
voltage ranges from 80 V AC to 176 V AC,
loads are linearly derated.)
40–70 Hz
> 0.99 (full load); > 0.98 (50% load)
250A
380 V, 400 V, or 415 V AC, three-phase,
four-wire, and PE
THD ≤ 1%
THD ≤ 4%
1
3:1 (in compliance with IEC 62040-3 standard)
60 min (105%–110% load)
10 min (111%–125% load)
1 min (125%–150% load)
30 to 40 12 V batteries (32 batteries by default)
Derated by 6% when 30 batteries are used
28