FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
Cooling Capacity Derating Coefficient Curve in Proportion to the Altitude
Figure 3-43 Cooling capacity derating coefficient curve in proportion to the altitude
Cooling Capacity Curve in Proportion to the Glycol Solution Density
The cooling capacity is obtained by multiplying the glycol solution density by the rated
cooling capacity.
Figure 3-44 Cooling capacity curve in proportion to the glycol solution density
When the altitude is within 1000 m, the cooling capacity deviation is in the tolerance range and can be
ignored.