Huawei FusionModule5000 Product Description page 88

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
Item
DO output
DI input
RS485 serial
port
expansion
Wiegand
interface
BLINK
button
Address DIP
switch
E-label
Indicators
Table 3-50 describes the access actuator indicators.
Table 3-50 Access actuator indicator description
Indicat
or
PWR
RUN
Specifications
One 12 V DC power output that controls magnetic locks, phoenix terminal
One DI input port for connecting to the door status switch
Two RS485 ports (one route) with the default communications rate of
9600 bit/s, physical port cascading supported (reserved function)
Two Wiegand interfaces, 12 V DC card reader operating power output;
two routes of card readers can operate at the same time.
Press the button for less than 1 second to start blinking.
Hold down the button for 1–5 seconds to search for a network and start
networking.
Hold down the button for more than 6 seconds to clear network
parameters.
4-pin address DIP switch
Supported
Col
Name
or
Gree
Power input
n
status indicator
Gree
Communication
n
status indicator
Status
Description
Steady on
The power input is normal.
Off
There is no power input.
Off
The power is abnormal or the board
program is loading.
Blinking at
The access actuator successfully
long intervals
registers with the ECC800 and the
software runs properly (the
indicator blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at
The communication is disconnected
short intervals
or the access actuator fails to
register with the ECC800 (the
indicator blinks at 4 Hz, on for
0.125s and then off for 0.125s).
81