Huawei FusionModule5000 Product Description page 9

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
flexible deployment, and excellent monitoring. It is a new-generation smart modular data
center solution.
Integration
Security and Reliability
Space Saving and Energy Efficiency
Quick Installation
Optimal Compatibility
Modular power distribution allows for flexible expansion.
The smart module integrates a cabinet system, power supply and distribution system,
cooling system, facility management system, surge protection and grounding system, fire
extinguishing system, and integrated cabling system. It provides an overall solution.
The integrated power supply and distribution system has an automatic transfer switch
(ATS), and distributes power to uninterruptible power systems (UPSs), air conditioners,
and IT equipment.
You are advised to deploy batteries independently when the input power is 380 V and more than four
battery cabinets are configured or when the input power is 480 V.
The smart module supports optional aisle and cabinet access control, which prevents
unauthorized personnel from entering the smart module and improves security.
The auxiliary fire extinguishing system improves the equipment room security. It
consists of the rotating skylight which starts automatically when fire occurs, and the
emergency button which helps open the door in emergencies.
The smart module supports two power inputs.
Each UPS is equipped with a manual maintenance bypass switch. When the smart
module is working properly, the switch is locked to prevent misoperations.
Modular UPSs work in N+1 redundancy mode to improve the reliability of the smart
module.
Strong current and weak current cables, optical fibers, and network cables are routed
separately to minimize electromagnetic interference.
The positive temperature coefficient (PTC) electric heater of the air conditioner provides
dual protection functions: automatic reset and auto-recovery disabling.
The smart module can be placed in a room of an office building.
The smart module can be directly installed on a concrete floor in a building, which
simplifies engineering.
Equipment room area ≥ 300 m
Aisle lighting is available, saving electric energy.
The smart module is delivered within a few days and can be quickly installed onsite,
which reduces cost.
The design minimizes the workload of engineering.
The standardized installation procedures reduce the installation time and workload.
2
.