Huawei FusionModule5000 Product Description page 67

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
Item
Configuration of a
condensate pump
Configuration of an
air deflector
Heating function
Humidification
function
External
dimensions (H x W
x D)
Package
dimensions (H x W
x D)
Net weight
Installation mode
Certification
a refers to the test condition (return air dry/wet bulb temperature: 37.8°C/20.8°C; chilled
water inlet temperature: 10°C; water flow rate: 5.5 m
Table 3-35 NetCol5000-C technical specifications (3)
Item
Cooling capacity
Maximum power
Maximum current
Air supply mode
NetCol5000-C030H7B201E12
0E0
No
For a 1000 mm deep model:
no
For a 1100 mm deep model:
yes
For a 1200 mm deep model:
yes
Yes
Yes
2000 mm x 300 mm x 1000
mm
2000 mm x 300 mm x 1100
mm
2000 mm x 300 mm x 1200
mm
2200 mm x 760 mm x 1350 mm
≤ 174 kg
On a concrete or ESD floor
RoHS and REACH
NetCol5000-C030H7A201E12
0E0
a
30 kW
Active route: 7050 W
Standby route: 1200 W
Active route: 26 A
Standby route: 6.5 A
Horizontal flow
NetCol5000-C030H7B2010020
E1
Yes
Yes
No
No
2000 mm x 300 mm x 1100
mm
2000 mm x 300 mm x 1200
mm
2200 mm x 760 mm x 1350 mm
≤ 170 kg
On a concrete or ESD floor
RoHS and REACH
3
/h).
NetCol5000-C030H7A201002
0E1
a
30 kW
1200 W
6.5 A
Horizontal flow
60