FusionModule5000 Smart Modular Data Center
Product Description (ECC800)
Category
System
Others
ATS (Optional)
Table 3-9 lists the specifications of an ATS.
Table 3-9 ATS specifications
Item
Input voltage range
Input frequency
range
Item
Battery string sharing
Charge voltage
Display
System efficiency
Current equalization
Number of combined
cabinets
Cable connection
Rated power
Noise
Maintenance mode
Surge protection
Specifications
187–264 V AC (phase voltage)
40–70 Hz
Specifications
Battery strings are shared in the cabinet by
default. There are no combined cabinets in the
Smart Module.
Equalized charging voltage: 2.35 V/cell; float
charging voltage: 2.25 V/cell
The maximum battery capacity is 3,000 Ah.
The charging current is limited based on the
battery capacity.
LCD+LED
≥ 96%
< 5% (in parallel mode)
In a Smart Module, cabinets do not need to be
combined.
Routed in and out from the top
The integrated UPS supports the 3+1 working
mode (three power modules and one redundant
module) and supports up to 112 kW IT cabinet
power. IT cabinet power can be 32 kW (1+1),
72 kW (2+1), or 112 kW (3+1).
At atmospheric pressure (25ºC)
25% load: 54 dB
50% load: 58 dB
75% load: 61 dB
100% load: 65 dB
Maintained from the front or rear
Level C SPD
29