Indicators
Table 3-39 describes the indicators on the ECC800 monitoring module.
Table 3-39 Indicators on the ECC800 monitoring module
Indicat
or
RUN
ALM
3G
RF_Z
Color
Name
Green
Running status
indicator
Red
Alarm indicator
Green
3G status
indicator
Green
Communication
status indicator
Status
Description
Steady on
The power supply is normal, the
program is being loaded, or
WiFi WPS is pairing.
Off
The power supply is abnormal.
Blinking at
The software runs properly (the
long
indicator blinks at 0.5 Hz, on for
intervals
1s and then off for 1s) or the
ECC800 registers with the
NetEco successfully.
Blinking at
The ECC800 does not register
short
with the NetEco (the indicator
intervals
blinks at 4 Hz, on for 0.125s and
then off for 0.125s).
Steady on
A system failure alarm is
generated.
Off
The system is normal.
Steady on
The 3G module is powered on.
Off
The 3G module stops running,
or no 3G module is configured.
Blinking at
The 3G module succeeds in
long
dial-up (the indicator blinks at
intervals
0.5 Hz, on for 1s and then off
for 1s).
Blinking at
The 3G module registers with
short
the operator network
intervals
successfully (the indicator
blinks at 4 Hz, on for 0.125s and
then off for 0.125s).
Steady on
No network parameters exist, or
a network is to be created.
Blinking at
A network is set up, and no
long
node access is allowed (the
intervals
indicator blinks at 0.5 Hz, on for
1s and then off for 1s).