Fig 11: Typical Installation – Mechanical Heating Primary Flow and Return
Closed Loop Water Source Heat Pump Applications
The bypass pipe diameter MUST be the same as the inlet and outlet pipes.
Select the pipe size between the heater and the system loop main, equal to the inlet/outlet
header connections of the water heater (as a minimum).
Install the correct pump. The temperature rise must be between 10°C and 15°C. Refer to
10
on page 30 for pump selection for 15°C temperature rise or
and friction loss data for 10°C temperature rise.
Fig 12: Typical Installation – Closed Loop Water Source Heat Pump
"X" – MAXIMUM 4 x SYSTEM
PIPE DIAMETERS OR 300mm
WHICHEVER IS SMALLER
37
Table 11
on page 30 for flow rate
Table