Raypak 910500 Owner's Manual And Installation Instructions page 29

Table of Contents

Advertisement

PIPE SIZING AND PUMP SELECTION
The pipe sizing for water heating and mechanical heating systems should be carried out by persons
competent to do so, choosing the most suitable pipe size for each individual application. Reference to
the technical specifications of the water heater and local regulatory authority requirements must be
made.
PUMP SELECTION APPLICATIONS UP TO 65
Table 9
on page 29 provides minimum pipe and pump sizes for typical water heating installations up to
o
65
C at the optimum temperature rise for these applications (20
PUMP SELECTION APPLICATIONS ABOVE 65
In mechanical heating applications, the MVB is designed to operate on a primary flow and return
circuit serving the main system flow and return circuit.
and pump sizes for primary circuit in mechanical heating and domestic hot water applications over
o
65
C at the optimum temperature rise for these applications (15
MVB
Pump
Model
Model
910500
UPS32-80N
910750
UPS32-80N
911000
Magna 1 40-120
911250
Magna 1 40-120
911500
Magna 1 40-120
911750
Magna 1 65-150
912000
Magna 1 65-150
Note: Manifold header sizes are minimum requirements for water heater performance.
Pipe and pump sizing is for primary circuits in DHW and hydronic applications up to 71
degree rise.
Header sizing is based on a total length of 20m of primary flow and return piping and 20 bends,
excluding equa-flow manifolds on storage tanks and MVBs, at 1.2m/sec velocity in copper pipe.
Magna 1 pumps have 3 speed control modes. PP = Proportional Pressure, CP = Constant Pressure, CC =
Constant Curve. UPS pumps have 3 fixed speed control settings. The appropriate speed setting must be
used to ensure correct operation
Table 9: Pump and Pipe Sizing for Water Heating Applications up to 65
o
MVB Pipe Size and Pump and Pipe Selection Chart –
DHW and Hydronic Applications up to 65
(20 degree rise)
Minimum Manifold Header Size (mm) / Pump Speed Setting
Branch
1 Unit
Size
pipe
speed
mm
dia
mm
50
50
65
65
65
65
PP1
80
80
CC2
80
80
CC3
100
100
CC2
100
100
PP2
C
o
K).
C
o
Table 10
on page 39 provides minimum pipe
o
K).
2 Units
pipe
speed
dia
mm
3
65
3
3
80
3
100
PP1
100
CC2
100
CC3
125
CC2
125
PP2
29
o
C
3 Units
4 Units
pipe
pipe
speed
dia
dia
mm
mm
80
3
100
100
3
100
100
CP1
125
125
CC2
125
125
CC3
150
150
CC2
200
150
PP2
200
o
C for a 20
o
C
speed
3
3
PP1
CC3
CC3
CC2
PP2

Advertisement

Table of Contents
loading

This manual is also suitable for:

910750911000911250911500911750912000

Table of Contents