Raypak 910500 Owner's Manual And Installation Instructions page 78

Table of Contents

Advertisement

Cascade Master/Follower Pump and Sensor Wiring
Follow sensor and pump connections for DHW or any of the 3 Modes in Hydronic applications as per
the instructions shown in
MASTER and FOLLOWERS.
The System and DHW pump outputs and any sensor inputs are not used in the Cascade Follower
configuration.
NOTE: where pump control is common across all heaters, eg IDHW, operation of the pump MUST be
provided via a relay box (not supplied). Refer to diagrams in
If used, connect the Enable/Disable wiring to terminals 11 and 12 marked 'Enable/Disable' on the
Master water heater (Refer to
contacts closure, which can come from a room thermostat or a remote relay. No power of any kind
should be applied to either of these terminals.
ALARM CONNECTION
An alarm annunciator or light may be connected to the alarm contacts on the water heater at terminals
23 and 24 marked 'Alarm Dry Contacts'. The Alarm Contacts are 3A rated dry contacts on a normally-
open relay that close during fault or lockout conditions, and the maximum voltage across the contacts
is 30 VAC or 30 VDC. Refer to
In a cascade system, the alarm output of the Master water heater will be active if either the Master
water heater or any of the Follower(s) have a lockout condition. The alarm output of the Follower water
heaters will only energize if a lockout condition occurs on that specific water heater.
BMS COMMUNICATION
The MVB is equipped as standard with a communications port for connectivity to building automation
via Modbus protocol. Refer to the VERSA IC manual for further information.
Other protocols such as Lonworks, Metasys and Bacnet may be used with the addition of interface
cards. Refer to Rheem for further information.
TM
Fig 45: PIM
FT_BUS Wire Connection
Fig. 37 to 42
beginning on page 70 for the water heater designated as the
Fig. 35
on page 68). This connection must be provided through dry
Fig. 35
on page 68.
Fig 27, 29 and 31
78
starting on page 57.

Advertisement

Table of Contents
loading

This manual is also suitable for:

910750911000911250911500911750912000

Table of Contents