Raypak 910500 Owner's Manual And Installation Instructions page 56

Table of Contents

Advertisement

Manual Diff
1.0 ~ 23.0°C
System
OFF,
Purge Time
0:20 ~ 20:00 min
Glycol %
0 ~ 50%
Ind DHW
OFF, ON
Sensor S5
Ind Supply
300.0,
Setpoint
0.5 ~ 93.0°C
Priority Ovr
AUTO,
Timer
0:10 ~ 2:00 hr
Modbus
Off, Monitor, Temp,
Mode
Rate
Address
1 ~ 170
Data Type
RTU, ASCH
Parity
None, Odd, Even
2400, 9600, 19200,
Baud Rate
57600, 115000
H Models – Hydronic Heating and Combination Hydronic/Indirect DHW
Mode 1 (Type H Units Only) - Hydronic Heating Only
Refer to
Fig 26 and
This mode selection is for hydronic heating systems with single or multiple water heaters (Maximum 4
water heaters) in primary/secondary piping configuration with or without Outdoor Air Reset (S4).
The system temperature is controlled by the System sensor (S3).
The Water Heater Pump (P1) runs during any call for heat.
The System Pump (P2) (if connected to the MVB) runs whenever the system is enabled for heating and
the outdoor air temperature is lower than the warm weather shut down (WWSD) temperature setting (if
utilized).
The Water Heater Pump (mandatory) and System Pump (optional) are delayed "off" as user defined in
the ADJUST menu.
Fig 26: MODE 1 – Single Water Heater with Primary/Secondary Piping
Only available to be viewed/changed if PIM DIP switch 1 is ON
N/A for Mode 3 high temp DHW i.e. PIM DIP switch 1 must be
set to OFF.
Sets the length of system pump (P2) post purge i.e. pump run
on (only when Modbus Mode para = Temp or Rate and if PIM
DIP switch 3 is ON - Default DIP 3 setting is ON)
Not used for MVB
Select ON if an indirect DHW tank sensor S5 is used in lieu of
an indirect DHW tankstat (only avail if Mode para = 2 or 3).
Indirect DHW tank target setpoint temp when a tankstat is used
in lieu of tank sensor S5 (only avail if MODE para = 2 or 3 and
Ind DHW Sensor S5 para = OFF)
Sets length of priority override time (only avail if Mode para = 3
or if Mode para = 2 and Ind Priority Enable para is set to ON
BMS Modbus operating mode (Temp = Temp control, Rate =
Rate control)
Modbus slave address (not avail if Modbus Mode para = OFF)
Modbus data type (not avail if Modbus Mode para = OFF)
Modbus parity (not avail if Modbus Mode para = OFF)
Modbus baud rate (not avail if Modbus Mode para = OFF)
27 on page 56.
56
N/A
0:20 min
0%
OFF
82.0°C
(90ºC)
2:00 hr
Monitor
1
RTU
Even
19200