Raypak Hydronic Heating Boiler 992BE-2342BE Specifications

Raypak Hydronic Heating Boiler 992BE-2342BE Specifications

Hydronic heating boiler type h

Advertisement

Quick Links

Job:
Engineer:
Contractor:
Prepared By:
Model:
100% Factory Fire Tested
Efficiency: 87%
Maximum Outlet Temperature: 230°F
Minimum Non-Condensing Inlet Temperature: 120°F
Thermal Shock Proof Heat Exchanger
Limited Twenty-Year Thermal Shock Warranty
Limited Ten-Year Closed-System Heat Exchanger
Warranty
Diagnostic Center with Fault History
PolyTuf Powder Coated Cabinet
No Combustible Floor Shield Required
Fan-Assisted
Patented Burner Security Blanket
Heat Exchanger
H Stamp
Headers
Glass-Lined Cast Iron – Standard
Bronze – Option A-1
ASME Inspected and Stamped
160 PSIG Working Pressure
National Board Approved
Fin Tubing
Copper – Standard
Cupro Nickel – Option A-3
ASME Steel Tube Sheet
Silicone High Temp. O-Rings
ASME Pressure Relief Valve
60 PSIG – Standard
PSIG – Optional
Temperature and Pressure Gauge
Water Connections
Left – Standard
Right – Option A-6
Controls
120V, 60Hz, 1∅ Power Supply
120/24V 60Hz Transformer
100% Shut-Off/Lockout
Hot Surface Ignition
Remote Flame Sensor
High Limit Control, Manual Reset
On/Off Power Switch
Manual Shut-Off, Front-Mounted
Flow Switch
Blocked Vent Pressure Switch
Combustion Air Proving Switches
Economaster Pump Time Delay
Enable/Disable
Catalog No.: 2000.451E
Date:
Indoor/Outdoor:
Gas Train
Manual Gas Shut-Off Valve(s)
Gas Pressure Regulator
Safety Shut-Off Valve
Firing Control Valve
Low Gas Pressure Switch, Manual
Firing Mode
3-Stage (H8): Model 992BE
4-Stage (H9): Models 1262BE -
2342BE
Fuel
Natural Gas
Propane Gas
4" WC Gas Supply Pressure
G-20
Design Certified ANSI Z21.13/
CSA 4.9
Construction
Indoor/Outdoor Construction
Enclosed Front Controls
Venting
Vent Location
Top – Standard
Rear – Option D-14
Vent Termination Cap
Outdoor D-11
Indoor, Horizontal D-15
Indoor, Vertical (by others)
Combustion Air
In-Line Filter Kit (TruSeal only)
D-17
Air Intake Elbow D-16
Extractor – Optional
By others
Not required
Effective: 11-15-07
Replaces: 1-1-07
®
Hi Delta
- Type H
Hydronic Heating Boiler
Models 992BE-2342BE
87% Efficiency
MBTUH Input:
Burner
Ultra-Low NOx: Less than 30 PPM
Temperature Controls
B-
TempTracker Digital Controller,
4-Stage
Y-241 Electronic Sequencer, 4-Stage
Y-281 Electronic Sequencer, 8-Stage
Options
C-6
Ignition Module, Manual Reset
®
D-21 TruSeal
Direct Vent
F-10 Low Water Cut-Off, Remote
Probe
I-1
High Limit Control, Auto Reset
P-
Pump:
60Hz
Water Hardness:
Cast Iron
Mounted
Front
P-26 Cold Water Start (See 2000.49)
S-2
High Gas Pressure Switch,
Manual
X-1
SureRack™ Kit
X-2
SureRack Add-on
Regulatory Agency Requirements
HP, 120V, 1∅,
GPG
Bronze
Loose
Rear

Advertisement

loading

Summary of Contents for Raypak Hydronic Heating Boiler 992BE-2342BE

  • Page 1 Job: Engineer: Contractor: Prepared By: Model: 100% Factory Fire Tested Efficiency: 87% Maximum Outlet Temperature: 230°F Minimum Non-Condensing Inlet Temperature: 120°F Thermal Shock Proof Heat Exchanger Limited Twenty-Year Thermal Shock Warranty Limited Ten-Year Closed-System Heat Exchanger Warranty Diagnostic Center with Fault History PolyTuf Powder Coated Cabinet No Combustible Floor Shield Required Fan-Assisted...
  • Page 2 1. Rates shown are for natural or propane gas, and elevations up to 5,000 feet. For installation above 5,000 feet, please contact manufacturer. 2. Required natural gas pressure is 7 – 10.5” WC. Required propane gas pressure is 11 – 13” WC. Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 Catalog No.: 2000.451E...

This manual is also suitable for:

Hi delta 992beHi delta 1262beHi delta 1532beHi delta 1802beHi delta 2002beHi delta 2072be ... Show all