System
OFF,
Purge
0:20 ~ 20:00 min
Time
Glycol %
0 ~ 50%
Ind DHW
OFF, ON
Sensor S5
Ind Supply
300.0,
Setpoint
0.5 ~ 93.0°C
Ind DHW
OFF,
Setpoint
10.0 ~ 82.0°C
Ind
1.0 ~ 5.0°C
Differential
Ind Priority
OFF, ON
Enable
Priority
AUTO,
Ovr Timer
0:10 ~ 2:00 hr
4.0 ~ 37.5°C
WWSD
OFF
Outdoor
1.6 ~ 29.4°C
Start
Outdoor
-51.1 ~ 7.2°C
Design
Boiler
1.6 ~ 65.5°C
Start
Boiler
21.1 ~ 93.3°C
Design
Modbus
Off, Monitor,
Mode
Temp, Rate
Address
1 ~ 170
Data Type
RTU, ASCH
Parity
None, Odd, Even
2400, 9600,
Baud Rate
19200, 57600,
115000
(1
) Split differential for hydronic Target Setpoint e.g. 5.0°C diff = CFH at 2.5°C below Target Setpoint &
CFH end at 2.5°C above Target Setpoint (only available to be viewed/changed if PIM DIP switch 1 is
ON otherwise hydronic differential is 12°C split (6°C above/below setpoint) and parameter is not
displayed – Default DIP 1 setting is OFF).
Sets the length of system pump (P2) post purge i.e. pump
run on (only when Modbus Mode para = Temp or Rate and
if PIM DIP switch 3 is ON - Default DIP 3 setting is ON)
Not used for MVB
Select ON if an indirect DHW tank sensor S5 is used in lieu
of an indirect DHW tankstat (only avail if Mode para = 2 or
3)
Indirect DHW tank target setpoint temp when a tankstat is
used in lieu of tank sensor S5 (only avail if MODE para = 2
or 3 and Ind DHW Sensor S5 para = OFF)
Indirect DHW target setpoint temp (only avail if Mode para
= 2 or 3 and Ind DHW Sensor S5 para = ON)
Subtractive differential for Ind DHW Setpoint para i.e. 3°
diff = CFH at 3° below Ind DHW Setpoint and CFH end at
Ind DHW Setpoint (only avail if Mode para = 2 or 3 and Ind
DHW Sensor S5 para = ON)
Select ON if indirect DHW priority is required during an
indirect DHW tank CFH (only avail if Mode para = 2.
Indirect priority is always on for mode 3)
Sets length of priority override time (only avail if Mode para
= 3 or if Mode para = 2 and Ind Priority Enable para is set
to ON
Warm weather heating shut down temp (only avail if Target
Mode para = RSET) Note: Indirect DHW CFH will override
Outdoor reset start temp (only avail if Target Mode para =
RSET)
Outdoor reset design temp (only avail if Target Mode para
= RSET)
Starting heater target temp when outdoor temp is at
Outdoor Start temp (only avail if Target Mode para =
RSET)
RSET target setpoint. Calculated when outdoor temp is as
cold as Outdoor Design temp (only avail if Target Mode
para = RSET)
BMS Modbus operating mode (Temp = Temp control, Rate
= Rate control)
Modbus slave address (not avail if Modbus Mode para =
OFF)
Modbus data type (not avail if Modbus Mode para = OFF)
Modbus parity (not avail if Modbus Mode para = OFF)
Modbus baud rate (not avail if Modbus Mode para = OFF)
61
0:20 min
0%
OFF
82.0°C
60.0°C
(82ºC Max)
3°C
OFF
1:00 hr
21.0°C
21.1°C
-12.2°C
21.0°C
82.2°C
(80ºC Max)
Monitor
1
RTU
Even
19200