Raypak 910500 Owner's Manual And Installation Instructions page 65

Table of Contents

Advertisement

Modbus
Off, Monitor, Temp,
Mode
Rate
Address
1 ~ 170
Data Type
RTU, ASCH
Parity
None, Odd, Even
2400, 9600, 19200,
Baud Rate
57600, 115000
(1)
Split differential for hydronic Target Setpoint e.g. 5.0°C diff = CFH at 2.5°C below Target Setpoint &
CFH end at 2.5°C above Target Setpoint (only available to be viewed/changed if PIM DIP switch 1 is
ON otherwise hydronic differential is 12°C split (6°C above/below setpoint) and parameter is not
displayed – Default DIP 1 setting is OFF).
BMS Modbus operating mode (Temp = Temp control, Rate =
Rate control)
Modbus slave address (not avail if Modbus Mode para =
OFF)
Modbus data type (not avail if Modbus Mode para = OFF)
Modbus parity (not avail if Modbus Mode para = OFF)
Modbus baud rate (not avail if Modbus Mode para = OFF)
65
Monitor
1
RTU
Even
19200