Startup Control In Heating - Daikin Aurora Series Service Manual

Hide thumbs Also See for Aurora Series:
Table of Contents

Advertisement

SiUS341802E
4.2

Startup Control in Heating

Inverter compressor
(M1C)
Electronic expansion
0 pulse
valve (main)
(Y1E)
Inverter fan
Step 4
(M1F + M2F)
DSH: Discharge pipe superheated degree
Pc : High pressure sensor detection value
Pe : Low pressure sensor detection value
Functions and Control
Frequency step up
5 sec. interval
+10 rps/10 sec.
E
D
C
B
A
0 Hz
PI control
Initial
opening
Step 8
Pc – Pe > 0.17 MPa (24.7 psi)
Frequency
(rps)
A
B
C
D
E
Pc – Pe > 0.42 MPa (60.9 psi)
OR
Pc – Pe > 0.32 MPa (46.4 psi)
&
&
20 rps or more
DSH > 12˚C (21.6˚F)
Startup Control
RXLQ72TA
RXLQ96/120TA
RXYQ72-120TA
RXYQ144/168TA
19
16.4
24
16.4
29
18
38
24
57
36
46