Service Mode
Maintenance Menu
Indoor Unit Status
Outdoor Unit Status
Forced Defrost
Error Display
Swap Unit No.
Addressed Sensor
Value
∗1. (For FXTQ-TA models)
The actual fan speed is converted into the fan tap to be displayed. Therefore, if the fan speed is changed by
controls or external factors, the airflow rate set with the remote controller may differ from the fan tap display.
∗2. (For FXTQ-TA models)
0 rpm is displayed even if the fan is rotating.
∗3. (For FXTQ-TA models)
The ON/OFF status of the humidifier connected to HUMIDIFIER on the X1M terminal of the indoor unit PCB is
not displayed. The ON/OFF status of the humidifier connected to the wiring adaptor is displayed.
39
Item 2
FLOAT
T1/T2
Th1
Th2
Th3
Th4
Th5
Th6
Unit No.
FAN step
COMP
EV1
SV1
Th1
Th2
Th3
Th4
Th5
Th6
Forced defrost ON
Forced defrost OFF
Display Error ON
Display Error OFF
Display Warning ON
Display Warning OFF
Current Unit No.
Transfer Unit No.
Unit No.: 0 - 15
Code
00
:
01
:
02
:
03
:
04
:
05
:
06
:
07
:
08
:
09
:
10 and over:
Data
Float switch OPEN/CLOSE
T1/T2 input from outside OPEN/CLOSE
Suction air thermistor
Heat exchanger liquid pipe thermistor
Heat exchanger gas pipe thermistor
Discharge air thermistor
Select the unit number you want to check.
Fan tap
Compressor power supply frequency (Hz)
Degree that electronic expansion valve is open (pulse)
Solenoid valve ON/OFF
Enables the forced defrost operation.
Disables the forced defrost operation.
Displays the error on the screen.
Displays neither errors nor warnings.
Displays a warning on the screen if an error occurs.
No warning is displayed.
A unit number can be transferred to another.
Select the unit number you want to check.
Remote controller thermistor (°F)
Suction air thermistor (°F)
Heat exchanger liquid pipe thermistor (°F)
Heat exchanger gas pipe thermistor (°F)
Indoor unit address No.
Outdoor unit address No.
Branch selector unit address No.
Zone control address No.
Cooling/Heating batch address No.
Demand/low-noise address No.
Differs depending on the connected indoor/outdoor unit.
The corresponding data will be displayed, based on the unit
number and code selected.
SiUS341802E
Remarks
Remote Controller