List Of Field Settings For Indoor Unit - Daikin Aurora Series Service Manual

Hide thumbs Also See for Aurora Series:
Table of Contents

Advertisement

SiUS341802E
1.4

List of Field Settings for Indoor Unit

Mode
First
No.
Code
(∗2)
No.
Filter sign setting
(Setting for display time to
clean air filter)
0
(Sets display time to clean air
filter to half when there is
heavy filter contamination.)
1
Ultra long life filter sign setting
1 (∗7) Filter cleaning sign time (Light/Heavy)
10(20)
2
Selection of thermistor
2 (∗6) Remote sensor and remote controller thermistor
3
Filter cleaning sign
Remote controller thermostat control during the
6
group control
7 (∗9) Time for absence area detection
1
Auxiliary electric heater ON temperature: Ton
2
Auxiliary electric heater OFF temperature: Toff
3
Setting the airflow rate when heating
3 (∗6) Electric heater setting
5 (∗6) Electric heater capacity setting
6 (∗9) Setting the rate of human detection
11(21)
7
Airflow adjustment
8 (∗9) Compensating the temperature around people
9 (∗9) Compensating the floor temperature
Optional output switching
0
(field selection of output for adaptor for wiring)
External ON/OFF input
1
(Set when ON/OFF is to be controlled from
outside.)
Thermostat switching
2
(Set when remote sensor is to be used)
12(22)
3
Airflow setting when heating thermostat is OFF
Setting of operation mode to AUTO
4
(automatic temperature differential setting for
VRV system Heat Pump series cool/heat)
5
Auto restart after power failure reset
6
Airflow setting when cooling thermostat is OFF
Field Settings and Test Operation
Setting Contents
Ultra long life
filter
Long life filter
Standard
filter
Second Code No.
01
Approx.
10,000
hrs.
Approx.
Light
Heavy
2,500
hrs.
Approx.
200 hrs.
Long life filter
Ultra long life filter
2,500/1,250
10,000/5,000
Remote controller +
Only suction air
Suction air
thermistor
thermistor
Only remote sensor
Displayed
Not displayed
Remote controller
Remote controller
thermostat control
thermostat control
is not permitted
is permitted
30 minutes
60 minutes
Refer to page 102 for details.
Standard
Slightly increased
Refer to page 103 for details.
Refer to page 103 for details.
High sensitivity
Low sensitivity
Completion of
OFF
airflow adjustment
Priorities given on
Suction air
the suction air
temperature only
temperature
–4°C (–7.2°F)
–2°C (–3.6°F)
Refer to page 105 for details.
Refer to page 105 for details.
1°C (1.8°F)
0.5°C (0.9°F)
LL tap
Set fan speed
Refer to page 106 for details.
Not equipped
Equipped
LL tap
Set fan speed
Field Settings from Remote Controller
: Factory setting
02
03
Approx.
5,000
hrs.
Approx.
1,250
hrs.
Approx.
100 hrs.
Only remote
controller
thermistor
Only remote
controller
thermistor
Increased
Standard
sensitivity
Start of airflow
adjustment
Standard
0°C (0°F)
OFF (∗8)
OFF (∗8)
04
Infrared
presence/floor
sensor
disabled
Priorities given
on the floor
temperature
+2°C (+3.6°F)
96