Space Heating/Cooling Control - Daikin Altherma EHFH-D3V Installation Manual

Table of Contents

Advertisement

7.2.4

Space heating/cooling control

Leaving water temperature: Main zone
#
Code
[A.3.1.1.1]
N/A
Select the setpoint mode of the leaving
water temperature.
LWT setpoint mode:
▪ 0 (Fixed): Absolute
▪ 1
dependent
▪ 2 (Fixed/scheduled): Absolute +
scheduled (only if Unit
method=LWT control)
▪ 3
dependent + scheduled (only if Unit
control method=LWT control)
[7.7.1.1]
[1-00]
If you selected weather-dependent
curve as a setpoint mode, adjust the
[1-01]
curve to your needs.
[1-02]
Set weather-dependent heating:
[1-03]
T t
[1-02]
[1-03]
▪ T
(main)
▪ T
[7.7.1.2]
[1-06]
If you selected weather-dependent
curve as a setpoint mode, adjust the
[1-07]
curve to your needs.
[1‑08]
Set weather-dependent cooling:
[1-09]
T t
[1-08]
[1-09]
▪ T
(main)
▪ T
(a)
Also see
"7.3 Weather-dependent
EHFH03S18D
Daikin Altherma 3 R F
4P596803-1D – 2022.08
Description
(Weather
dep.):
Weather-
control
(WD/scheduled):
Weather-
(a)
[1-00]
[1-01]
: Target leaving water temperature
t
: Outdoor temperature
a
(a)
[1-06]
[1-07]
: Target leaving water temperature
t
: Outdoor temperature
a
curve" [ 4  22].
Leaving water temperature: Additional zone
#
Code
[A.3.1.2.1]
N/A
[7.7.2.1]
[0-00]
[0-01]
[0-02]
[0-03]
T a
[7.7.2.2]
[0-04]
[0-05]
[0-06]
[0-07]
T a
(a)
Also see
"7.3 Weather-dependent
Leaving water temperature: Delta T source
The Delta T is the required temperature difference between entering
and leaving water. This applies to both temperature zones. Change
the value of Delta T if another minimum temperature difference is
required for the good operation of the heat emitters in heating or
cooling mode.
#
Code
[A.3.1.3.1]
[1-0B]
[A.3.1.3.2]
[1-0D]
7 Configuration
Description
Select the setpoint mode of the leaving
water temperature.
LWT setpoint mode:
▪ 0 (Fixed): Absolute
▪ 1
(Weather
dep.):
Weather-
dependent
▪ 2 (Fixed/scheduled): Absolute +
scheduled (only if Unit
control
method=LWT control)
▪ 3
(WD/scheduled):
Weather-
dependent + scheduled (only if Unit
control method=LWT control)
If you selected weather-dependent
curve as a setpoint mode, adjust the
(a)
curve to your needs.
Set weather-dependent heating:
T t
[0-01]
[0-00]
[0-03]
[0-02]
▪ T
: Target leaving water temperature
t
(additional)
▪ T
: Outdoor temperature
a
If you selected weather-dependent
curve as a setpoint mode, adjust the
(a)
curve to your needs.
Set weather-dependent cooling:
T t
[0-05]
[0-04]
[0-07]
[0-06]
▪ T
: Target leaving water temperature
t
(additional)
▪ T
: Outdoor temperature
a
curve" [ 4  22].
Description
Delta T for heating
Range: 3°C~10°C
Delta T for cooling
Range: 3°C~10°C
Installation manual
T a
T a
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Altherma 3 r f

Table of Contents