Inverter Compressor Overcurrent - Daikin Aurora Series Service Manual

Hide thumbs Also See for Aurora Series:
Table of Contents

Advertisement

Troubleshooting by Error Code

2.49 Inverter Compressor Overcurrent

L8
Error Code
Applicable
All outdoor unit models
Models
Method of Error
Detect current flowing through the power transistor.
Detection
Error Decision
When the secondary-side inverter current exceeds.
Conditions
Supposed
Causes
Troubleshooting
241
Compressor overloaded
Wiring disconnection in compressor coil
Disconnection of compressor wiring
Defective inverter PCB
Incorrect power supply voltage
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Is the stop valve open?
Check the compressor cable
for disconnection and flaws.
Are the
Power OFF
leads of the relevant
compressor
normal?
Are
wiring and wire
connections to the relevant
compressor
normal?
The
insulation
resistance of the
relevant compressor is
100 kΩ or less to
ground.
The coil
of the relevant
compressor has caused
wiring disconnection
in it.
A
NO
YES
NO
YES
NO
YES
YES
NO
YES
NO
Go to the next page.
SiUS341802E
Open the stop valve.
Replace the leads of the
relevant compressor.
Rectify the wiring and
wire connections.
Replace the
compressor.
Replace the
compressor.
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents