“The present publication is drawn up by way of information only and ISO14001 assures an effective environmental manufacturer of air conditioning does not constitute an offer binding upon Daikin Europe N.V.. Daikin management system in order to help protect equipment, compressors and Europe N.V.
• Altherma Altherma Small Capacity PAGE Indoor - Outdoor Heating only - ERHQ006-008AD Oudoor unit - 1~ Heating and Cooling EKHBH(X)008AA Indoor unit - 1~ Altherma Large Capacity Indoor - Outdoor Heating only - ERHQ011-016AA Oudoor unit - 1~ Heating and Cooling ERHQ011-016AAW1 Oudoor unit - 3~ EKHBH(X)016AB...
Page 7
EEDEN09-720 technical data Part 1/4: ERHQ006-008AD EKHBH/X008AA...
Page 9
• Outdoor units • ERHQ006-008AD TABLE OF CONTENTS ERHQ006-008AD Features ............10 Specifications .
• Outdoor units • ERHQ006-008AD Specifications 2-1 NOMINAL CAPACITY AND NOMINAL INPUT ERHQ006AD ERHQ007AD ERHQ008AD Indoor Units EKHBH008AA combination indoor units + outdoor units Condition 1 Heating Minimum 4.36 4.36 4.36 capacity Nominal 5.75 6.84 8.43 Maximum kW 7.45 8.79 9.58 Heating PI Nominal...
Page 12
• Outdoor units • ERHQ006-008AD Specifications 2-2 TECHNICAL SPECIFICATIONS ERHQ006AD ERHQ007AD ERHQ008AD Heat Dimensions Length Exchanger Nr of Rows Fin Pitch Nr of Stages Tube type Hi-Xa(8) Type WF fin Treatment Anti-corrosion treatment (PE) Type Propeller Quantity Discharge direction Horizontal Motor Quantity Output...
• Outdoor units • ERHQ006-008AD Specifications 2-2 TECHNICAL SPECIFICATIONS ERHQ006AD ERHQ007AD ERHQ008AD Standard Item Installation manual Accessories Quantity Item Drain plug Quantity Notes See operation range drawing The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment.
• Outdoor units • ERHQ006-008AD Dimensional drawing & centre of gravity 4 - 1 Dimensional drawing unit (mm) ERHQ006-008 AD Drain outlet (I.D. J 15.9 hose for connection) Wall height on air outlet side Minimum space for air passage = less than 1200 In case of removing stop valve cover 4 x holes for anchor bolts (M8 or M10) Name plate...
• Outdoor units • ERHQ006-008AD Dimensional drawing & centre of gravity 4 - 2 Centre of gravity ERHQ006-008 AD The position of foundation bolt 4D042258L • Altherma • Outdoor units...
• Outdoor units • ERHQ006-008AD Sound data 7 - 1 Sound pressure spectrum ERHQ006AA ERHQ007AA ERHQ008AA HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
Page 21
• Indoor units • EKHBH-X008AA TABLE OF CONTENTS EKHBH-X008AA Features ............22 Specifications .
• Indoor units • EKHBH-X008AA Specifications 2-1 TECHNICAL SPECIFICATIONS EKHBH008AA EKHBX0008AA Operation Ambient Heating °C -20~25 range Cooling °C 10~43 Waterside Heating °C 15~50 Cooling °C 5~22 2-2 ELECTRICAL SPECIFICATIONS EKHBH008AA EKHBX0008AA Electric heater Type Power Supply Phase Frequenc Voltage Current Running Current...
Page 25
• Indoor units • EKHBH-X008AA Specifications 2-2 ELECTRICAL SPECIFICATIONS EKHBH008AA EKHBX0008AA Wiring For power Quantity of wires connections supply backup Type of wires Select diameter and type according to national and local regulations heater Electric heater Type Power Supply Phase Frequenc Voltage Current...
Page 26
• Indoor units • EKHBH-X008AA Specifications 2-2 ELECTRICAL SPECIFICATIONS EKHBH008AA EKHBX0008AA Wiring For power Quantity of wires connections supply backup Type of wires Select diameter and type according to national and local regulations heater Connection type For power supply connection to Optional Warm Water Tank + Q2L Quantity of wires Type of wires Select diameter and type according to national and local regulations...
• Indoor units • EKHBH-X008AA Dimensional drawing & centre of gravity 4 - 1 Dimensional drawing EKHBH008AA FIXATION Service door (Closed) 361 (Open) 553 G 1 (Male) Center of gravity Pump + switch for speed setting Dimensions Remocon wallbracket Water IN connection G 1 1/2 (female) Water OUT connection G 1 1/2 (female) Power supply intake (+ domestic hot water tank) Air purge...
• Indoor units • EKHBH-X008AA Piping diagram EKHBH(X)008AA Water side R4T I n l e t water thermi s tor R3T Refri g erant l i q ui d si d e thermi s tor Field installation R2T Outl e t water backup heater thermi s tor R1T Outl e t water heat-exchanger thermi s tor Filter Inlet...
• Indoor units • EKHBH-X008AA Wiring diagram 6 - 1 Wiring diagram EKHBH(X)008AA3V3 Only for EKSOLHWAV1 Power supply Outdoor unit Option Domestic hot 230V 1N∼50Hz water tank Solar pump connection >> See note 2 << Only See note 9 for EKHW Option Only for EKHW(S/E) Option See note 7 For EKHWSU*V3...
Page 31
• Indoor units • EKHBH-X008AA Wiring diagram 6 - 1 Wiring diagram EKHBH(X)008AA6WN/9WN Domestic hot Domestic hot Power supply Only for EKSOLHWAV1 water tank water tank Outdoor unit 3(/N)∼400(/230V) 50Hz Option Solar pump connection >> See note 2 << Only See note 9 for EKHWE Option Only for EKHWS*Z2...
• Indoor units • EKHBH-X008AA Wiring diagram 6 - 2 External connection diagram EKHBH(X)008AA EKHBH(X)008AA Standard parts Power supply Outdoor unit 3 core Unit power supply: 230V + earth For more details please check unit wiring X1M:L-N-Earth diagram Backup heater power supply (3/6/9kW): 400V or 230V + earth Optional power supply X2M:1-2-3-Earth Booster heater power supply (3kW): 400V or 230V + earth...
• Indoor units • EKHBH-X008AA Operation range Outdoor temp. (°CDB) EKHBH(X)008AA ERHQ006-008AD Leaving evaporator water temperature (°C) Outdoor temp. (°CDB) : Units with optional back up heater Leaving condenser water temperature (°C) Outdoor temp. (°CDB) : Booster heater operation only : Units with optional back up heater or booster heater operation only...
• Indoor units • EKHBH-X008AA Hydraulic performance 8 - 1 Static pressure drop unit EKHBH(X)008AA Flow (l/min) III: High speed II: medium speed I: Low speed ESP: External static pressure Flow: waterflow through the unit Warning: 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit.
Page 35
EEDEN09-720 technical data Part 2/4: ERHQ011-016AA ERHQ011-016AAW1 EKHBH(X)016AB...
Page 37
• Outdoor units • ERHQ011-016AAV3 TABLE OF CONTENTS ERHQ011-016AAV3 Features ............38 Specifications .
• Outdoor units • ERHQ011-016AAV3 Specifications 2-1 NOMINAL CAPACITY AND NOMINAL INPUT ERHQ011AA ERHQ014AA ERHQ016AA Indoor Units EKHBH016AB combination indoor units + outdoor units Condition 1 Heating Nominal 11.2 14.0 16.0 capacity Heating PI Nominal 2.46 3.17 3.83 Nominal 4.55 4.42 4.18 Nominal...
Page 40
• Outdoor units • ERHQ011-016AAV3 Specifications 2-2 TECHNICAL SPECIFICATIONS ERHQ011AA ERHQ014AA ERHQ016AA Heat Dimensions Length Exchanger Nr of Rows Fin Pitch Nr of Passes Face m² 0.98 0.98 0.98 Area Nr of Stages Tube type Hi-XSS(8) Type WF fin Treatment Anti-corrosion treatment (PE) Type Propeller...
• Outdoor units • ERHQ011-016AAV3 Dimensional drawing & centre of gravity 4 - 1 Dimensional drawing ERHQ011-016 Gas pipe connection ∅15.9 flare Hole for anchor bolt 4-M12 Liquid pipe connection ∅9.5 flare Service port (in the unit) Grounding terminal M5 (in switch box) Refrigerant piping intake Power supply wiring intake (knock out hole ∅34) control wiring intake (knock out hole ∅27)
• Outdoor units • ERHQ011-016AAV3 Piping diagram ERHQ011-016AAV3 Electronic expansion valve Filter Filter Heat exchanger 4-Way-Valve High Pressure Low Pressure Switch Sensor EKHB 016 Field Piping ø9.5 C 1220T-0 Service Port Compressor 5/16’ Field Piping ø15.9 C 1220T-0 Accumulator Outdoor Unit Indoor Unit Heating Cooling...
• Outdoor units • ERHQ011-016AAV3 Sound data 7 - 1 Sound pressure spectrum ERHQ011-016 ERHQ011AAV3 ERHQ014AAV3 ERHQ016AAV3 HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) 3TW57767-2A NOTES Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level.
• Outdoor units • ERHQ011-016AAV3 Sound data 7 - 2 Sound pressure night quiet mode ERHQ011-016 ERHQ011AAV3 ERHQ014AAV3 ERHQ016AAV3 HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) 3TW57767-4 NOTES Data is valid at free field condition (measured in a semi-anachoic room). dBA = A-Weighted sound pressure level.
• Outdoor units • ERHQ011-016AAV3 Installation 8 - 1 Service space ERHQ011-016 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.
• Outdoor units • ERHQ011-016AAV3 Operation range ERHQ011-016AAV3 Outdoor temp. (°CDB) Leaving evaporator Water temperature (°C) Outdoor temp. (°CDB) No heat pump operation, back up heater only ERHQ_V18 units include special equipment (insulation heater sheet, ...) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
Page 53
• Outdoor units • ERHQ011-016AAW1 TABLE OF CONTENTS ERHQ011-016AAW1 Features ............54 Specifications .
• Outdoor units • ERHQ011-016AAW1 Specifications 2-2 TECHNICAL SPECIFICATIONS ERHQ011AAW1 ERHQ014AAW1 ERHQ016AAW1 Motor Speed (nominal) Steps Heating Cooling Motor Output Drive Direct drive Compressor Quantity Motor Model JT1G-VDYR@S Type Hermetically sealed scroll compressor Motor Output W 2,200 Starting Method Inverter driven Motor Crankcase Heater Output...
• Outdoor units • ERHQ011-016AAW1 Specifications 2-2 TECHNICAL SPECIFICATIONS ERHQ011AAW1 ERHQ014AAW1 ERHQ016AAW1 Safety Devices High pressure switch Fan motor thermal protector Fuse Standard Item Tie-wraps Accessories Quantity Item Installation manual Quantity Notes The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment.
• Outdoor units • ERHQ011-016AAW1 Capacity tables 3 - 1 Heating capacity tables ERHQ011-016AAW1 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW]...
• Outdoor units • ERHQ011-016AAW1 Capacity tables 3 - 2 Cooling capacity tables ERHQ011-016AAW1 Maximum Cooling Capacity Model Tamb LWE [°C] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] 3TW57912-1A...
• Outdoor units • ERHQ011-016AAW1 Dimensional drawing & centre of gravity 4 - 1 Dimensional drawing ERHQ011-016AAW1 1. Gas pipe connection J15.9 flare Hole for anchor bolt 4-M12 2. Liquid connection pipe "9.5 flare 3. Service port (in the unit) 4.
• Outdoor units • ERHQ011-016AAW1 Sound data 7 - 1 Sound pressure spectrum ERHQ011AAW1* ERHQ014AAW1* ERHQ016AAW1* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Outdoor units • ERHQ011-016AAW1 Sound data 7 - 2 Sound pressure night quiet mode ERHQ011AAW1* ERHQ014AAW1* ERHQ016AAW1* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Outdoor units • ERHQ011-016AAW1 Installation 8 - 1 Service space ERHQ011-016 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.
• Outdoor units • ERHQ011-016AAW1 Operation range ERHQ011-016AAW1 Outdoor temp. (°CDB) Leaving evaporator Water temperature (°C) Outdoor temp. (°CDB) Units with optional back up heater operation possible, but no guarantee of capacity (if outdoor temperature < -25°C unit will stop) ERHQ_W18 units include special equipment (insulation heater sheet, à) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
Page 69
• Indoor units • EKHBH-X016AB TABLE OF CONTENTS EKHBH-X016AB Features ............70 Specifications .
• Indoor units • EKHBH-X016AB Specifications 2-2 ELECTRICAL SPECIFICATIONS EKHBH016AB EKHBX016AB Electric heater Type Power Supply Phase Frequency Voltage Current back-up Running heater Current Current back-up Z-max Text 0.29 0.29 heater + booster Running Current 26 (13+13) heater (EKHWS* Minimum Ssc value Equipment complying with EN/IEC 61000-3-12 ** models) Electric heater...
Page 73
• Indoor units • EKHBH-X016AB Specifications 2-2 ELECTRICAL SPECIFICATIONS EKHBH016AB EKHBX016AB Electric heater Type Power Supply Phase Frequency Voltage Current back-up Running heater Current Current back-up Running Current 26 (13+13) heater + booster 20.5 (13+7.5) heater (EKHWS* Minimum Ssc value Equipment complying with EN/IEC 61000-3-12 ** models) Equipment complying with EN/IEC 61000-3-12 **...
• Indoor units • EKHBH-X016AB Dimensional drawing & centre of gravity 4 - 1 Dimensional drawing EKHBH016AB FIXATION Service door (Closed) 361 (Open) 553 1-1/4″ Male BSP View A Scale 1/5 Dimensions wallbracket Center of gravity Minimum space for service & ventilation Pump + switch for speed setting Remocon Water IN connection: 1 1/4’’...
• Indoor units • EKHBH-X016AB Piping diagram EKHBH(X)016AB Water Site Expansion Vessel Pressure Gauge Drain Safety Valve Evaporator Condensor Purge Flowswitch Blow Off Refriferant Field Installation Side Pump Refr. Out Water Outlet Refr. In Electric Shut Off Valve Heater Body With Drain/Fill Valve Plate Heat...
• Indoor units • EKHBH-X016AB Wiring diagram 6 - 1 Wiring diagram EKHBH(X)016AB3V3 Only for EKSOLHWAV1 Outdoor unit Power supply Option Domestic hot water 230V 1N∼50Hz Solar pump connection tank >> See note 2 << Only See note 9 for *EKHWE* Option Only for *EKHW(S/E) Option See note 7...
Page 78
• Indoor units • EKHBH-X016AB Wiring diagram 6 - 1 Wiring diagram EKHBH(X)016AB6T1/9T1 Only for EKSOLHWAV1 Power supply Outdoor unit Option Domestic hot water Solar pump connection tank >> See note 2 << See note 9 Only for EKHW*V3 Option See note 7 For EKHWSU*V3 Option...
• Indoor units • EKHBH-X016AB Wiring diagram 6 - 2 External connection diagram Electrical connection diagram Altherma For more details please check unit wiring Standard parts diagram Outdoor unit Power supply 5 or 3 core unit power supply: 400V or 230V + earth X1M:L1-L2-L3-N-Earth Optional power supply Power supply (alarm indication, cooling/heating...
• Indoor units • EKHBH-X016AB Installation 7 - 1 Drainage instructions EKHBDP Leaving water temperature limit to prevent condesation Relative humidity 40% Relative humidity 60% Relative humidity 80% Maximum leaving water temperature cooling mode = 22°C Example: With ambient temperature of 25°C and relative humidity of 40%.
• Indoor units • EKHBH-X016AB Operation range EKHBH(X)016AB Outdoor temp. (°CDB) Leaving evaporator Water temperature (°C) Outdoor temp. (°CDB) No heat pump operation, back up heater only ERHQ_V18 units include special equipment (insulation heater sheet, ...) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Indoor units • EKHBH-X016AB Hydraulic performance 9 - 1 Static pressure drop unit EKHBH(X)016 Flow [l/min] Warning: l high speed 1. Selecting a flow outside the curves can cause damage to or ll medium speed malfunction of the unit. See also minimum and maximum allowed ESP: external static pressure water flowrange in the technical specifications.
• Monobloc • EDHQ011-016AA6V3 Features 1 6 A 1 - 0 h e r o b l o b l Q 0 1 M o n A l t E D H M o n • Heating only monobloc • Low energy bills and low CO2 emissions •...
• Monobloc • EDHQ011-016AA6V3 Specifications 2-3 MAIN COMPONENTS EDHQ011AA6V3 EDHQ014AA6V3 EDHQ016AA6V3 Air heat exchanger Specifications Length Nr of Rows Fin pitch Nr of Passes Face area m² 1.131 1.131 1.131 Nr of Stages Tube type Hi-XSS Type WF fin Treatment Anti-corrosion treatment (PE) Type Propeller...
• Monobloc • EDHQ011-016AA6V3 Specifications 2-4 ELECTRICAL SPECIFICATIONS EDHQ011AA6V3 EDHQ014AA6V3 EDHQ016AA6V3 Power supply Main Power Name compressor Phase component Frequency Voltage Voltage range Minimum -10% Maximum +10% Current Minimum Ssc Equipment complying with EN/IEC 61000-3-12(*) value Recomended fuses Wiring connections For power supply See installation manual compressor component...
Page 90
• Monobloc • EDHQ011-016AA6V3 Specifications 2-4 ELECTRICAL SPECIFICATIONS EDHQ011AA6V3 EDHQ014AA6V3 EDHQ016AA6V3 Power supply Voltage range Minimum -10% hydraulic Maximum +10% component Wiring connections Connection type for power supply hydraulic compartment Quantity of wires Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires...
• Monobloc • EDHQ011-016AA6V3 Options EDHQ011-016AAV3 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase 3-Phase Zone 2 Zone 3 Zone 2 Zone 3 EDLQ***AA6V3 EDHQ***AA6V3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6V3 EBHQ***AA6V3 EBLQ***AA6W1 EBHQ***AA6W1 Reference Description EKRP1HB Digital I/O PCB EKBPHT16Y Bottom plate heater V (2) V (2)
Page 92
55°C and it required, install an aquastat(*) valve in the Booster heater return water flow of the E(D/B)(H/L)Q* unit. Heat exchanger coil Daikin shall not be held liable fo any damage resulting from failure to observe 10 Domestic hot water tank this rule. 11 Boiler (field supply)
• Monobloc • EDHQ011-016AA6V3 Capacity tables 4 - 1 Heating capacity tables EDHQ011-016AA6V3 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW]...
• Monobloc • EDHQ011-016AA6V3 Wiring diagram 7 - 2 External connection diagram EDHQ011-016AA6V3 Electrical connection diagram Altherma For more details please check unit wiring Standard parts diagram Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off X1M: L1-L2-L3-N-Earth indication, solar interlock)
• Monobloc • EDHQ011-016AA6V3 Sound data 8 - 1 Sound pressure spectrum EDHQ011-016AA6V3 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EDHQ011-016AA6V3 Sound data 8 - 2 Sound pressure night quiet mode EDHQ011-016AA6V3 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EDHQ011-016AA6V3 Installation 9 - 1 Service space EDHQ011-016AA6V3 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.
• Monobloc • EDHQ011-016AA6V3 Operation range EDHQ011-016AA6V3 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EDHQ011-016AA6V3 Hydraulic performance 11 - 1 Static pressure drop unit EDHQ011-016AA6V3 Flow (l/min) I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications.
Page 103
• Monobloc • EDHQ011-016AA6W1 TABLE OF CONTENTS EDHQ011-016AA6W1 Features ............104 Specifications .
• Monobloc • EDHQ011-016AA6W1 Features 1 6 A 1 - 0 h e r o b l o b l Q 0 1 M o n A l t E D H M o n • Heating only monobloc • Low energy bills and low CO2 emissions •...
• Monobloc • EDHQ011-016AA6W1 Specifications 2-3 MAIN COMPONENTS EDHQ011AA6W1 EDHQ014AA6W1 EDHQ016AA6W1 Air heat exchanger Specifications Length Nr of Rows Fin pitch Nr of Passes Face area m² 1.131 1.131 1.131 Nr of Stages Tube type Hi-XSS Type WF fin Treatment Anti-corrosion treatment (PE) Type Propeller...
• Monobloc • EDHQ011-016AA6W1 Specifications 2-4 ELECTRICAL SPECIFICATIONS EDHQ011AA6W1 EDHQ014AA6W1 EDHQ016AA6W1 Power supply Main Power Name compressor Phase component Frequency Voltage Voltage range Minimum -10% Maximum +10% Current Nominal running Heating (A) current (RLA) Maximum running Heating current Power supply Current Recomended compressor...
Page 108
• Monobloc • EDHQ011-016AA6W1 Specifications 2-4 ELECTRICAL SPECIFICATIONS EDHQ011AA6W1 EDHQ014AA6W1 EDHQ016AA6W1 Power supply Voltage range Minimum -10% hydraulic Maximum +10% component Wiring connections Connection type for power supply hydraulic compartment Quantity of wires Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires...
• Monobloc • EDHQ011-016AA6W1 Options EDHQ011-016AA6W1 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase 3-Phase Zone 2 Zone 3 Zone 2 Zone 3 EDLQ***AA6V3 EDHQ***AA6V3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6V3 EBHQ***AA6V3 EBLQ***AA6W1 EBHQ***AA6W1 Reference Description EKRP1HB Digital I/O PCB EKBPHT16Y Bottom plate heater V (2) V (2)
Page 110
55°C and it required, install an aquastat(*) valve in the Booster heater return water flow of the E(D/B)(H/L)Q* unit. Heat exchanger coil Daikin shall not be held liable fo any damage resulting from failure to observe 10 Domestic hot water tank this rule. 11 Boiler (field supply)
• Monobloc • EDHQ011-016AA6W1 Capacity tables 4 - 1 Heating capacity tables EDHQ011-016AA6W1 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW]...
• Monobloc • EDHQ011-016AA6W1 Wiring diagram 7 - 2 External connection diagram EDHQ011-016AA6W1 Electrical connection diagram Altherma For more details please check unit wiring Standard parts diagram Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off X1M: L1-L2-L3-N-Earth indication, solar interlock)
• Monobloc • EDHQ011-016AA6W1 Sound data 8 - 1 Sound pressure spectrum EDHQ011-016AA6W1 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EDHQ011-016AA6W1 Sound data 8 - 2 Sound pressure night quiet mode EDHQ011-016AA6W1 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EDHQ011-016AA6W1 Installation 9 - 1 Service space EDHQ011-016AA6W1 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.
• Monobloc • EDHQ011-016AA6W1 Operation range EDHQ011-016AA6W1 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only operation possible, but no guarantee of capacity E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EDHQ011-016AA6W1 Hydraulic performance 11 - 1 Static pressure drop unit EDHQ011-016AA6W1 Flow (l/min) I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications.
Page 121
• Monobloc • EDLQ011-016AA6V3 TABLE OF CONTENTS EDLQ011-016AA6V3 Features ............122 Specifications .
• Monobloc • EDLQ011-016AA6V3 Features 1 6 A 1 - 0 h e r o b l o b l Q 0 1 M o n A l t E D L M o n • Heating only monobloc with bottom plate heater •...
• Monobloc • EDLQ011-016AA6V3 Specifications 2-3 MAIN COMPONENTS EDLQ011AA6V3 EDLQ014AA6V3 EDLQ016AA6V3 Air heat exchanger Specifications Length Nr of Rows Fin pitch Nr of Passes Face area m² 1.131 1.131 1.131 Nr of Stages Tube type Hi-XSS Type WF fin Treatment Anti-corrosion treatment (PE) Type Propeller...
• Monobloc • EDLQ011-016AA6V3 Specifications 2-4 ELECTRICAL SPECIFICATIONS EDLQ011AA6V3 EDLQ014AA6V3 EDLQ016AA6V3 Power supply Main Power Name compressor Phase component Frequency Voltage Voltage range Minimum -10% Maximum +10% Current Minimum Equipment complying with EN/IEC 61000-3-12(*) Ssc value Recomende d fuses Wiring connections For power supply See installation manual compressor component Power supply...
Page 126
• Monobloc • EDLQ011-016AA6V3 Specifications 2-4 ELECTRICAL SPECIFICATIONS EDLQ011AA6V3 EDLQ014AA6V3 EDLQ016AA6V3 Power supply Voltage range Minimum -10% hydraulic Maximum +10% component Wiring connections Connection type for power supply hydraulic compartment Quantity of wires Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires...
• Monobloc • EDLQ011-016AA6V3 Options EDLQ011-016AAV3 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase 3-Phase Zone 2 Zone 3 Zone 2 Zone 3 EDLQ***AA6V3 EDHQ***AA6V3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6V3 EBHQ***AA6V3 EBLQ***AA6W1 EBHQ***AA6W1 Reference Description EKRP1HB Digital I/O PCB EKBPHT16Y Bottom plate heater V (2) V (2)
Page 128
55°C and it required, install an aquastat(*) valve in the Booster heater return water flow of the E(D/B)(H/L)Q* unit. Heat exchanger coil Daikin shall not be held liable fo any damage resulting from failure to observe 10 Domestic hot water tank this rule. 11 Boiler (field supply)
• Monobloc • EDLQ011-016AA6V3 Capacity tables 4 - 1 Heating capacity tables EDLQ011-016AA6V3 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW]...
• Monobloc • EDLQ011-016AA6V3 Wiring diagram 7 - 2 External connection diagram EDLQ011-016AA6V3 Electrical connection diagram Altherma For more details please check unit wiring Standard parts diagram Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off X1M: L1-L2-L3-N-Earth indication, solar interlock)
• Monobloc • EDLQ011-016AA6V3 Sound data 8 - 1 Sound pressure spectrum EDLQ011-016AA6V3 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EDLQ011-016AA6V3 Sound data 8 - 2 Sound pressure night quiet mode EDLQ011-016AA6V3 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EDLQ011-016AA6V3 Installation 9 - 1 Service space EDLQ011-016AA6V3 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.
• Monobloc • EDLQ011-016AA6V3 Operation range EDLQ011-016AA6V3 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EDLQ011-016AA6V3 Hydraulic performance 11 - 1 Static pressure drop unit EDLQ011-016AA6V3 Flow (l/min) I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications.
Page 139
• Monobloc • EDLQ011-016AA6W1 TABLE OF CONTENTS EDLQ011-016AA6W1 Features ............140 Specifications .
• Monobloc • EDLQ011-016AA6W1 Features 1 6 A 1 - 0 h e r o b l o b l Q 0 1 M o n A l t E D L M o n • Heating only monobloc with bottom plate heater •...
• Monobloc • EDLQ011-016AA6W1 Specifications 2-3 MAIN COMPONENTS EDLQ011AA6W1 EDLQ014AA6W1 EDLQ016AA6W1 Air heat exchanger Specifications Length Nr of Rows Fin pitch Nr of Passes Face area m² 1.131 1.131 1.131 Nr of Stages Tube type Hi-XSS Type WF fin Treatment Anti-corrosion treatment (PE) Type Propeller...
• Monobloc • EDLQ011-016AA6W1 Specifications 2-4 ELECTRICAL SPECIFICATIONS EDLQ011AA6W1 EDLQ014AA6W1 EDLQ016AA6W1 Power supply Main Power Name compressor Phase component Frequency Voltage Voltage range Minimum -10% Maximum +10% Current Nominal running Heating (A) current (RLA) Maximum running Heating current Power supply Current Recomended compressor...
Page 144
• Monobloc • EDLQ011-016AA6W1 Specifications 2-4 ELECTRICAL SPECIFICATIONS EDLQ011AA6W1 EDLQ014AA6W1 EDLQ016AA6W1 Power supply Voltage range Minimum -10% hydraulic Maximum +10% component Wiring connections Connection type for power supply hydraulic compartment Quantity of wires Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires...
• Monobloc • EDLQ011-016AA6W1 Options EDLQ011-016AA6W1 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase 3-Phase Zone 2 Zone 3 Zone 2 Zone 3 EDLQ***AA6V3 EDHQ***AA6V3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6V3 EBHQ***AA6V3 EBLQ***AA6W1 EBHQ***AA6W1 Reference Description EKRP1HB Digital I/O PCB EKBPHT16Y Bottom plate heater V (2) V (2)
Page 146
55°C and it required, install an aquastat(*) valve in the Booster heater return water flow of the E(D/B)(H/L)Q * unit. Heat exchanger coil Daikin shall not be held liable fo any damage resulting from failure to observe 10 Domestic hot water tank this rule. 11 Boiler (field supply)
• Monobloc • EDLQ011-016AA6W1 Capacity tables 4 - 1 Heating capacity tables EDLQ011-016AA6W1 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW]...
• Monobloc • EDLQ011-016AA6W1 Wiring diagram 7 - 2 External connection diagram EDLQ011-016AA6W1 Electrical connection diagram Altherma For more details please check unit wiring Standard parts diagram Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off X1M: L1-L2-L3-N-Earth indication, solar interlock)
• Monobloc • EDLQ011-016AA6W1 Sound data 8 - 1 Sound pressure spectrum EDLQ011-016AA6W1 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EDLQ011-016AA6W1 Sound data 8 - 2 Sound pressure night quiet mode EDLQ011-016AA6W1 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EDLQ011-016AA6W1 Installation 9 - 1 Service space EDLQ011-016AA6W1 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.
• Monobloc • EDLQ011-016AA6W1 Operation range EDLQ011-016AA6W1 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only operation possible, but no guarantee of capacity E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EDLQ011-016AA6W1 Hydraulic performance 11 - 1 Static pressure drop unit EDLQ011-016AA6W1 Flow (l/min) I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications.
• Monobloc • EBHQ011-016AA6V3 Features 1 6 A 1 - 0 h e r o b l o b l Q 0 1 M o n A l t E B H M o n • Reversible monobloc • Low energy bills and low CO2 emissions •...
• Monobloc • EBHQ011-016AA6V3 Specifications 2-3 MAIN COMPONENTS EBHQ011AA6V3 EBHQ014AA6V3 EBHQ016AA6V3 Expansion vessel Volume Maximum water pressure Pre pressure Water filter Diameter perforations Material Brass Water circuit Piping connections inch G5/4 (FEMALE) Piping inch 5/4" Safety valve Manometer Drain valve / Fill valve Shut off valve Air purge valve Total water volume (6)
Page 162
• Monobloc • EBHQ011-016AA6V3 Specifications 2-4 ELECTRICAL SPECIFICATIONS EBHQ011AA6V3 EBHQ014AA6V3 EBHQ016AA6V3 Power supply Voltage range Minimum -10% hydraulic Maximum +10% component Wiring connections Connection type for power supply hydraulic compartment Quantity of wires Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires...
• Monobloc • EBHQ011-016AA6V3 Options EBHQ011-016AAV3 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase 3-Phase Zone 2 Zone 3 Zone 2 Zone 3 EDLQ***AA6V3 EDHQ***AA6V3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6V3 EBHQ***AA6V3 EBLQ***AA6W1 EBHQ***AA6W1 Reference Description EKRP1HB Digital I/O PCB EKBPHT16Y Bottom plate heater V (2) V (2)
Page 164
55°C and it required, install an aquastat(*) valve in the Booster heater return water flow of the E(D/B)(H/L)Q* unit. Heat exchanger coil Daikin shall not be held liable fo any damage resulting from failure to observe 10 Domestic hot water tank this rule. 11 Boiler (field supply)
• Monobloc • EBHQ011-016AA6V3 Capacity tables 4 - 1 Heating capacity tables EBHQ011-016AA6V3 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW]...
• Monobloc • EBHQ011-016AA6V3 Capacity tables 4 - 2 Cooling capacity tables EBHQ011-016AA6V3 Maximum Cooling Capacity Model Tamb LWE [°C] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] 3TW58012-1A...
• Monobloc • EBHQ011-016AA6V3 Wiring diagram 7 - 2 External connection diagram EBHQ011-016AA6V3 Electrical connection diagram Altherma For more details please check unit wiring Standard parts diagram Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off X1M: L1-L2-L3-N-Earth indication, solar interlock)
• Monobloc • EBHQ011-016AA6V3 Sound data 8 - 1 Sound pressure spectrum EBHQ011-016AA6V3 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EBHQ011-016AA6V3 Sound data 8 - 2 Sound pressure night quiet mode EBHQ011-016AA6V3 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EBHQ011-016AA6V3 Installation 9 - 1 Service space EBHQ011-016AA6V3 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.
• Monobloc • EBHQ011-016AA6V3 Operation range EBHQ011-016AA6V3 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EBHQ011-016AA6V3 Hydraulic performance 11 - 1 Static pressure drop unit EBHQ011-016AA6V3 Flow (l/min) I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications.
Page 177
• Monobloc • EBHQ011-016AA6W1 TABLE OF CONTENTS EBHQ011-016AA6W1 Features ............178 Specifications .
• Monobloc • EBHQ011-016AA6W1 Features 1 6 A 1 - 0 h e r o b l o b l Q 0 1 M o n A l t E B H M o n • Reversible monobloc • Low energy bills and low CO2 emissions •...
• Monobloc • EBHQ011-016AA6W1 Specifications 2-3 MAIN COMPONENTS EBHQ011AA6W1 EBHQ014AA6W1 EBHQ016AA6W1 Expansion vessel Volume Maximum water pressure Pre pressure Water filter Diameter perforations Material Brass Water circuit Piping connections inch G5/4 (FEMALE) Piping inch 5/4" Safety valve Manometer Drain valve / Fill valve Shut off valve Air purge valve Total water volume (6)
Page 182
• Monobloc • EBHQ011-016AA6W1 Specifications 2-4 ELECTRICAL SPECIFICATIONS EBHQ011AA6W1 EBHQ014AA6W1 EBHQ016AA6W1 Power supply Voltage range Minimum -10% hydraulic Maximum +10% component Wiring connections Connection type for power supply hydraulic compartment Quantity of wires Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires...
• Monobloc • EBHQ011-016AA6W1 Options EBHQ011-016AA6W1 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase 3-Phase Zone 2 Zone 3 Zone 2 Zone 3 EDLQ***AA6V3 EDHQ***AA6V3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6V3 EBHQ***AA6V3 EBLQ***AA6W1 EBHQ***AA6W1 Reference Description EKRP1HB Digital I/O PCB EKBPHT16Y Bottom plate heater V (2) V (2)
Page 184
55°C and it required, install an aquastat(*) valve in the Booster heater return water flow of the E(D/B)(H/L)Q* unit. Heat exchanger coil Daikin shall not be held liable fo any damage resulting from failure to observe 10 Domestic hot water tank this rule. 11 Boiler (field supply)
• Monobloc • EBHQ011-016AA6W1 Capacity tables 4 - 1 Heating capacity tables EBHQ011-016AA6W1 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW]...
• Monobloc • EBHQ011-016AA6W1 Capacity tables 4 - 2 Cooling capacity tables EBHQ011-016AA6W1 Maximum Cooling Capacity Model Tamb LWE [°C] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] 3TW58012-1A...
• Monobloc • EBHQ011-016AA6W1 Wiring diagram 7 - 2 External connection diagram EBHQ011-016AA6W1 Electrical connection diagram Altherma For more details please check unit wiring Standard parts diagram Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off X1M: L1-L2-L3-N-Earth indication, solar interlock)
• Monobloc • EBHQ011-016AA6W1 Sound data 8 - 1 Sound pressure spectrum EBHQ011-016AA6W1 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EBHQ011-016AA6W1 Sound data 8 - 2 Sound pressure night quiet mode EBHQ011-016AA6W1 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EBHQ011-016AA6W1 Installation 9 - 1 Service space EBHQ011-016AA6W1 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.
• Monobloc • EBHQ011-016AA6W1 Operation range EBHQ011-016AA6W1 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only operation possible, but no guarantee of capacity E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EBHQ011-016AA6W1 Hydraulic performance 11 - 1 Static pressure drop unit EBHQ011-016AA6W1 Flow (l/min) I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications.
Page 197
• Monobloc • EBLQ011-016AA6V3 TABLE OF CONTENTS EBLQ011-016AA6V3 Features ............198 Specifications .
• Monobloc • EBLQ011-016AA6V3 Specifications 2-3 MAIN COMPONENTS EBLQ011AA6V3 EBLQ014AA6V3 EBLQ016AA6V3 Expansion vessel Volume Maximum water pressure Pre pressure Water filter Diameter perforations Material Brass Water circuit Piping connections inch G5/4 (FEMALE) Piping inch 5/4" Safety valve Manometer Drain valve / Fill valve Shut off valve Air purge valve Total water volume (6)
Page 202
• Monobloc • EBLQ011-016AA6V3 Specifications 2-4 ELECTRICAL SPECIFICATIONS EBLQ011AA6V3 EBLQ014AA6V3 EBLQ016AA6V3 Power supply Voltage range Minimum -10% hydraulic Maximum +10% component Wiring connections Connection type for power supply hydraulic compartment Quantity of wires Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires...
• Monobloc • EBLQ011-016AA6V3 Options EBLQ011-016AAV3 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase 3-Phase Zone 2 Zone 3 Zone 2 Zone 3 EDLQ***AA6V3 EDHQ***AA6V3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6V3 EBHQ***AA6V3 EBLQ***AA6W1 EBHQ***AA6W1 Reference Description EKRP1HB Digital I/O PCB EKBPHT16Y Bottom plate heater V (2) V (2)
Page 204
55°C and it required, install an aquastat(*) valve in the Booster heater return water flow of the E(D/B)(H/L)Q* unit. Heat exchanger coil Daikin shall not be held liable fo any damage resulting from failure to observe 10 Domestic hot water tank this rule. 11 Boiler (field supply)
• Monobloc • EBLQ011-016AA6V3 Capacity tables 4 - 1 Heating capacity tables EBLQ011-016AA6V3 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW]...
• Monobloc • EBLQ011-016AA6V3 Capacity tables 4 - 2 Cooling capacity tables EBLQ011-016AA6V3 Maximum Cooling Capacity Model Tamb LWE [°C] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] 3TW58012-1A...
• Monobloc • EBLQ011-016AA6V3 Wiring diagram 7 - 2 External connection diagram EBLQ011-016AA6V3 Electrical connection diagram Altherma For more details please check unit wiring Standard parts diagram Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off X1M: L1-L2-L3-N-Earth indication, solar interlock)
• Monobloc • EBLQ011-016AA6V3 Sound data 8 - 1 Sound pressure spectrum EBLQ011-016AA6V3 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EBLQ011-016AA6V3 Sound data 8 - 2 Sound pressure night quiet mode EBLQ011-016AA6V3 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EBLQ011-016AA6V3 Installation 9 - 1 Service space EBLQ011-016AA6V3 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.
• Monobloc • EBLQ011-016AA6V3 Operation range EBLQ011-016AA6V3 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EBLQ011-016AA6V3 Hydraulic performance 11 - 1 Static pressure drop unit EBLQ011-016AA6V3 Flow (l/min) I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications.
Page 217
• Monobloc • EBLQ011-016AA6W1 TABLE OF CONTENTS EBLQ011-016AA6W1 Features ............218 Specifications .
• Monobloc • EBLQ011-016AA6W1 Specifications 2-3 MAIN COMPONENTS EBLQ011AA6W1 EBLQ014AA6W1 EBLQ016AA6W1 Expansion vessel Volume Maximum water pressure Pre pressure Water filter Diameter perforations Material Brass Water circuit Piping connections inch G5/4 (FEMALE) Piping inch 5/4" Safety valve Manometer Drain valve / Fill valve Shut off valve Air purge valve Total water volume (6)
Page 222
• Monobloc • EBLQ011-016AA6W1 Specifications 2-4 ELECTRICAL SPECIFICATIONS EBLQ011AA6W1 EBLQ014AA6W1 EBLQ016AA6W1 Power supply Voltage range Minimum -10% hydraulic Maximum +10% component Wiring connections Connection type for power supply hydraulic compartment Quantity of wires Type of wires Select diameter and type according to national and local regulations Connection type for power supply connection to optional sanitary tank + Q2L Quantity of wires...
• Monobloc • EBLQ011-016AA6W1 Options EBLQ011-016AA6W1 Kit availability for E(D/B)(H/L)Q011-016AA* Altherma Monoblock / Low temperature 1-Phase 3-Phase Zone 2 Zone 3 Zone 2 Zone 3 EDLQ***AA6V3 EDHQ***AA6V3 EDLQ***AA6W1 EDHQ***AA6W1 EBLQ***AA6V3 EBHQ***AA6V3 EBLQ***AA6W1 EBHQ***AA6W1 Reference Description EKRP1HB Digital I/O PCB EKBPHT16Y Bottom plate heater V (2) V (2)
Page 224
55°C and it required, install an aquastat(*) valve in the Booster heater return water flow of the E(D/B)(H/L)Q* unit. Heat exchanger coil Daikin shall not be held liable fo any damage resulting from failure to observe 10 Domestic hot water tank this rule. 11 Boiler (field supply)
• Monobloc • EBLQ011-016AA6W1 Capacity tables 4 - 1 Heating capacity tables EBLQ011-016AA6W1 Maximum Heating Capacity (Peak values) Model LWC [°C] Tamb HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW] HC [kW] PI [kW]...
• Monobloc • EBLQ011-016AA6W1 Capacity tables 4 - 2 Cooling capacity tables EBLQ011-016AA6W1 Maximum Cooling Capacity Model Tamb LWE [°C] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] 3TW58012-1A...
• Monobloc • EBLQ011-016AA6W1 Wiring diagram 7 - 2 External connection diagram EBLQ011-016AA6W1 Electrical connection diagram Altherma For more details please check unit wiring Standard parts diagram Outdoor unit Power supply Optional power supply 5 or 3 core unit power supply: 400V or 230V + earth Power supply (alarm indication, cooling/heating on/off X1M: L1-L2-L3-N-Earth indication, solar interlock)
• Monobloc • EBLQ011-016AA6W1 Sound data 8 - 1 Sound pressure spectrum EBLQ011-016AA6W1 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EBLQ011-016AA6W1 Sound data 8 - 2 Sound pressure night quiet mode EBLQ011-016AA6W1 E(D/B)(H/L)Q011* E(D/B)(H/L)Q014* E(D/B)(H/L)Q016* HEATING HEATING HEATING Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz) Notes: Data is valid at free field condition (measured in a semi-anachoic room) dBA = A-weighted sound power level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa If sound is measured under actual installation conditions, the measured...
• Monobloc • EBLQ011-016AA6W1 Installation 9 - 1 Service space EBLQ011-016AA6W1 A. Non stacked installation Legend Unit: mm Suction side obstacle Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed.
• Monobloc • EBLQ011-016AA6W1 Operation range EBLQ011-016AA6W1 only EB(H/L)* Leaving evaporator Water temperature (°C) No heat pump operation, back up heater only operation possible, but no guarantee of capacity E(D/B)L* units include special equipment (insulation, heater sheet, . . . ) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions.
• Monobloc • EBLQ011-016AA6W1 Hydraulic performance 11 - 1 Static pressure drop unit EBLQ011-016AA6W1 Flow (l/min) I High speed II medium speed ESP: External static pressure Flow: waterflow through the unit WARNING 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications.
Page 237
EEDEN09-720 technical data Part 4/4: EKHWS-B EKHWE EKSOLHWAV1 EKRTW EKRTR...
Page 239
• Domestic hot water tank • EKHWS-B TABLE OF CONTENTS EKHWS-B Features ............240 Specifications .
• Domestic hot water tank • EKHWS-B Features h e r W S - A l t E K H • Stainless steel domestic hot water tank • Easy to install • Cost effective alternative to a fossil fuel boiler •...
(3) Efficiency of domestic hot water production: In the ALTHERMA by Daikin system both the heat pump and the electric booster heater supply the energy to produce domestic hot water. The higher the portion of energy supplied by the heat pump, the more energy efficient the system is.
• Domestic hot water tank • EKHWS-B Dimensional drawing & centre of gravity 4 - 1 Dimensional drawing EKHWS-B Water mains in G 3/4 (Female) Water mains out G 3/4 (Female) Thermistor connection Flow (from EKHB(H/X)*) G 3/4 (Female) Return (to EKHB(H/X)*) G 3/4 (Female) Switchbox Thermal protector Anode...
• Domestic hot water tank • EKHWS-B Piping diagram EKHWSU-B Overview Field installation (Delivered with EKHWSU*B*) Field installation 3-way motorized valve (delivered with indoor unit) Shut off valve Outdoor Indoor Load Shut off valve Water flow Water return Option domestic hot water tank Option domestic hot water tank Water main OUT Water main IN...
Page 245
• Domestic hot water tank • EKHWE TABLE OF CONTENTS EKHWE Features ............246 Specifications .
• Domestic hot water tank • EKHWE Features h e r A l t E K H • Enameled domestic hot water tank • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort •...
(3) Efficiency of domestic hot water production: In the ALTHERMA by Daikin system both the heat pump and the electric booster heater supply the energy to produce domestic hot water. The higher the portion of energy supplied by the heat pump, the more energy efficient the system is.
• Domestic hot water tank • EKHWE Dimensional drawing & centre of gravity 4 - 1 Dimensional drawing EKHWE Required service space around the tank Cold water inlet: G 3/4 (Male) Hot water outlet: G 3/4 (Male) Thermistor hole Flow (From EKHB(H/X)*): Rp 3/4 (Female) Return (To EKHB(H/X)*): Rp 3/4 (Female) Wall mounted Switchbox...
• Solar Kit • EKSOLHWAV1 Features W A V h e r O L H A l t E K S • Connectable to solar collectors • Easy to install • Cost effective alternative to a fossil fuel boiler • Total solution for year round comfort •...
• Solar Kit • EKSOLHWAV1 Specifications 2-1 TECHNICAL SPECIFICATIONS EKSOLHWAV1 Dimensions Packing Height Width Depth Unit Height Width Depth Weight Unit Packed Unit Packing Material Carton Weight Heat Type Brazed plate Exchanger Pressure drop Solar side kPa 21.5 Maximum inlet Solar side °C temperature Capacity...
• Solar Kit • EKSOLHWAV1 Piping diagram Solenoid valve EKSOLHWAV1 3-way motorized valve Overview Field supply Field installation (delivered with 3-way motorized indoor unit) valve Load Shut off Outdoor Indoor valve Shut off Water from valve indoor Field supply Option domestic hot water tank Field supply Solar...
• Room thermostat • EKRTW Specifications 2-1 TECHNICAL SPECIFICATIONS EKRTW Dimensions Unit Height Width Depth Packing Height Width Depth Weight Unit Gross Packing Material Carton Weight Ambient Storage °C -20~60 temperature Operation °C 0~50 Temperature Heating °C 4-37 setting range Cooling °C 4-37...
• Room thermostat • EKRTW Options Additional information: comfort function mode Use this mode for a fixed temperature on comfort level. (comfort setpoint default on 21°C in heating mode, 24°C in cooling mode) reduced function mode Use this mode for a fixed temperature on reduced level. (reduced setpoint default on 17°C in heating mode, 28°C in cooling mode) Use this mode to let your installation be controlled by the schedule timer.
• Room thermostat • EKRTR Specifications 2-1 TECHNICAL SPECIFICATIONS EKRTR thermostat Dimensions Unit Height Width Depth Packing Height Width Depth Weight Unit Gross Packing Material Carton Weight Ambient Storage °C -20~60 temperature Operation °C 0~50 Temperature Heating °C 4-37 setting range Cooling °C 4-37...
• Room thermostat • EKRTR Options Additional information: comfort function mode Use this mode for a fixed temperature on comfort level. (comfort setpoint default on 21°C in heating mode, 24°C in cooling mode) reduced function mode Use this mode for a fixed temperature on reduced level. (reduced setpoint default on 17°C in heating mode, 28°C in cooling mode) Use this mode to let your installation be controlled by the schedule timer.