Field Settings from Remote Controller
Filter Cleaning Sign
Whether or not to display "Filter Cleaning" after operation of certain duration can be selected.
Mode No.
10 (20)
∗ Filter cleaning sign is not displayed when an Auto-clean Panel is connected.
Time for Absence Area Detection
(For units with an infrared presence/floor sensor only)
By selecting the energy-saving operation mode in the absence, the target temperature is shifted to the energy-
saving end by 1°C (maximum 2°C) after the state of absence continues for a certain period of time.
Absent time defined for detection can be selected as follows:
Mode No.
10 (20)
• The set temperature displayed on the remote controller remains same even if the target temperature is shifted.
• As soon as people is detected while the temperature is shifted, this control will be cancelled (reset).
101
First Code No.
Second Code No.
3
First Code No.
Second Code No.
7
31
30
29
28
27
Cooling (at 28˚C)
26
21
Heating (at 20˚C)
20
19
18
17
∗ The values in parentheses represent the time
when Second code No. is "02."
01
02
01
02
Human detection
State of absence
30 (60)∗
60 (120)∗
Elapsed time of absence (min.)
SiUS341802E
Contents
Displayed
Not displayed
Contents
30 minutes
60 minutes
Field Settings and Test Operation