Heater Control (Fxtq-Ta Models) - Daikin Aurora Series Service Manual

Hide thumbs Also See for Aurora Series:
Table of Contents

Advertisement

Outline of Control (Indoor Unit)

9.12 Heater Control (FXTQ-TA Models)

Note:
Optional heater kit HKS... is required.
For FXTQ models, heater ON/OFF output from wiring adaptor interlocks with the operation of
heater kit HKS....(When the heater 1 turns ON/OFF, heater output of wiring adaptor turns ON/OFF.)
Fan residual operation also interlocks with the fan residual operation of heater kit HKS.... The
residual time will be 90 seconds. (Refer to Fan Control (Heater Residual) (FXTQ-TA Models) on
page 89.)
9.12.1 Auxiliary Electric Heater Control
If heating is insufficient in heat pump system alone, an electric heater is to be used as the auxiliary
heater. The following shows the ON/OFF conditions for the electric heater.
• Heating/Automatic heating
&
• Auxiliary heater enabled: 1
Heater allowed
• Condition A
&
• Time up
• Thermostat step 2: ON
H/P Heating: In operation
• Thermostat step 3: ON
• Time up
&
• Electric heater capacity
setting (∗5): Setting available
85
Heater not allowed
Thermostat OFF/Operation OFF
Thermostat ON
H/P Heating: In operation
Heater 1: OFF
Heater 2: OFF
Fan: ON
ENTRY/
5 minutes timer starts.
Heater 1: ON
Heater 2: OFF
Fan: ON
ENTRY/
5 minutes timer starts.
H/P Heating: In operation
Heater 1: ON
Heater 2: ON
(OFF for single heater)
Fan: ON
OR
Heater 1: OFF
Heater 2: OFF
Heater 1: OFF
Heater 2: OFF
Thermostat OFF
Condition B
Condition B
• Elimination of Condition A
OR
• Thermostat step 2: OFF
• Thermostat step 3: OFF
• Electric heater capacity setting:
OR
Setting not available
• Not in heating/Automatic heating
• Auxiliary heater enabled: 0 (∗3)
Thermostat OFF
Thermostat ON
Condition C
H/P In defrost/oil return
Heater 1: ON
Heater 2: OFF
Fan: ON
Elimination of
Condition B
Elimination of
Condition A
SiUS341802E
Functions and Control