Field Setting from Outdoor Unit
Accessing modes
BS1 is used to change the mode you want to access.
• Access mode 1
Press BS1 once. Segment indication changes to:
• Access mode 2
Press BS1 for at least 5 seconds. Segment indication changes to:
INFORMATION If you get confused in the middle of the process, press BS1.
Mode 1
Mode 1 is used to set basic settings and to monitor the status of the unit.
•
Changing and access the setting in mode 1:
Once mode1 is selected (press BS1 once), you can select the wanted setting. It is done by pushing BS2.
Accessing the selected setting's value is done by pressing BS3 once.
•
To quit and return to the initial status, press BS1.
Example:
Checking the content of parameter [1-10] (to know how many indoor units are connected to the system).
Mode: 1
Setting: 10
•
Make sure the segment indication is as during normal operation (default situation when shipped from factory).
•
Press BS1 once; result segment display:
Result: mode 1 is accessed.
•
Press BS2 10 times; result segment display:
Result: mode 1 setting 10 is addressed.
•
Press BS3 1 time; the value which is returned (depending on the actual field situation), is the amount of
indoor units which are connected to the system.
Result: mode1 setting 10 is addressed and selected, return value is monitored information
•
To leave the monitoring function, press BS1 once, you will return to the default situation when shipped from
factory.
Mode 2
Mode 2 is used to set field settings of the outdoor unit and system.
•
Changing and access the setting in mode 2:
Once mode 2 is selected (press BS1 for more than 5 seconds), you can select the wanted setting. It is done
by pressing BS2.
Accessing the selected setting's value is done by pressing BS3 once.
•
To quit and return to the initial status, press BS1.
•
Changing the value of the selected setting in mode 2:
- Once mode 2 is selected (press BS1 for more than 5 seconds) you can select the wanted setting. It is done
by pressing BS2.
- Accessing the selected setting's value is done by pressing BS3 once.
- Now BS2 is used to select the required value of the selected setting.
- When the required value is selected, you can define the change of value by pressing BS3 once.
- Press BS3 again to start operation according to the chosen value.
119
Then it returns to idle situation (no indication on segment displays: blank)
SiUS341802E
Field Settings and Test Operation