Compressor Step Control - Daikin Aurora Series Service Manual

Hide thumbs Also See for Aurora Series:
Table of Contents

Advertisement

SiUS341802E
5.4

Compressor Step Control

Compressor operations vary with the following steps according to information in Compressor PI Control on page 48.
Furthermore, the operating priority of compressors is subject to information in Operating Priority and Rotation of
Compressors on page 49.
Single unit installation
RXLQ72TA
RXYQ72-120TA
Step No.
rps
1
15.0
2
15.2
3
15.4
4
15.6
5
15.9
6
16.2
7
16.5
8
16.8
9
17.1
10
17.4
11
17.7
12
18.0
13
18.3
14
18.6
15
19.0
16
19.4
17
19.8
18
20.1
19
20.5
20
20.7
21
21.0
22
21.3
23
21.6
24
21.9
25
22.2
26
22.5
27
22.9
28
23.2
29
23.5
30
23.8
31
24.2
32
24.5
33
24.9
34
25.2
35
25.5
36
25.9
37
26.3
38
26.6
39
27.0
40
27.4
41
27.8
42
28.1
43
28.5
44
29.0
45
29.4
46
29.8
47
30.2
48
30.6
49
31.0
50
31.5
51
31.9
52
32.4
53
32.8
54
33.3
55
33.8
56
34.2
57
34.7
58
35.2
59
35.7
60
36.2
Note:
1. Depending on the operating conditions of compressors, the compressors may run in patterns other
than those aforementioned.
Functions and Control
Step No.
rps
Step No.
61
36.7
121
62
37.2
122
63
37.7
123
64
38.3
124
65
38.8
125
66
39.3
126
67
39.9
127
68
40.5
128
69
41.0
129
70
41.6
130
71
42.2
131
72
42.8
132
73
43.4
133
74
44.0
134
75
44.6
135
76
45.2
136
77
45.8
137
78
46.5
138
79
47.1
139
80
47.8
140
81
48.5
141
82
49.1
142
83
49.8
143
84
50.5
144
85
51.1
145
86
52.0
146
87
52.7
147
88
53.4
148
89
54.2
149
90
54.9
150
91
55.7
151
92
56.5
152
93
57.3
153
94
58.1
154
95
58.9
155
96
59.7
156
97
60.5
157
98
61.4
158
99
62.3
100
63.4
101
64.0
102
64.9
103
65.6
104
66.6
105
67.7
106
68.6
107
69.6
108
70.6
109
71.6
110
72.6
111
73.6
112
74.6
113
75.7
114
76.7
115
77.8
116
78.9
117
80.0
118
81.1
119
82.2
120
83.4
rps
84.5
85.7
86.9
88.1
89.4
90.6
91.9
93.2
94.5
95.8
97.2
98.5
99.9
101.3
RXYQ72TA upper limit
102.7
104.2
105.6
107.1
108.4
110.1
111.7
113.2
114.8
116.4
118.0
119.7
RXYQ96TA upper limit
121.4
123.1
124.8
126.5
128.3
130.1
132.0
133.8
135.7
137.6
139.5
140.0
RXLQ72TA, RXYQ120TA
upper limit
Basic Control
50