8 Configuration
#
Code
[A.2.2.6.3]
[C-09]
Alarm output
Indicates the logic of the alarm output on
the
malfunctioning.
▪ 0 (Normally open)(default): The alarm
output will be powered when an alarm
occurs. By setting this value, a
distinction
malfunctioning and detection of a
power failure of the unit.
▪ 1 (Normally closed): The alarm output
will NOT be powered when an alarm
occurs.
[A.2.2.6.4]
[F-04]
Bottom plate heater
Only applicable for EHBH/X16 and
EHVH/X16. Indicates if an optional
bottom plate heater is installed on the
outdoor unit. The power of the bottom
plate heater is in this case supplied by
the indoor unit.
▪ 0 (No)(default): NOT installed.
▪ 1 (Yes): Installed. Remark: If this value
is set, the output on the digital I/O
PCB cannot be used for space
heating/cooling
"5 Application guidelines" on page 7.
Demand PCB
The demand PCB is used to enable the power consumption control
by digital inputs. See "5 Application guidelines" on page 7.
#
Code
[A.2.2.7]
[D-04]
Demand PCB
Only applicable for EHBH/X04+08 and
EHVH/X04+08. Indicates if the optional
demand PCB is installed.
▪ 0 (No)(default): NOT installed.
▪ 1 (Yes): Installed. Power consumption
control by digital inputs is selectable in
[A.6.2.1].
Energy metering
When energy metering is performed by the use of external power
meters, configure the settings as described below. Select the pulse
frequency output of each power meter in accordance with the power
meter specifications. It is possible to connect (up to 2) power meters
with different pulse frequencies. When only 1 or no power meter is
used, select No to indicate the corresponding pulse input is NOT
used.
#
Code
[A.2.2.8]
[D-08]
Optional external kWh meter 1:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1 pulse/kWh)
▪ 2: Installed (1 pulse/kWh)
▪ 3: Installed (10 pulse/kWh)
▪ 4: Installed (100 pulse/kWh)
▪ 5: Installed (1000 pulse/kWh)
Installer reference guide
38
Description
digital
I/O
PCB
during
is
made
between
output.
See
Description
Description
#
Code
[A.2.2.9]
[D-09]
Optional external kWh meter 2:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1 pulse/kWh)
▪ 2: Installed (1 pulse/kWh)
▪ 3: Installed (10 pulse/kWh)
▪ 4: Installed (100 pulse/kWh)
▪ 5: Installed (1000 pulse/kWh)
8.2.4
Quick wizard: Capacities (energy
metering)
The capacities of all electrical heaters must be set for the energy
metering and/or power consumption control feature to work properly.
When measuring the resistance value of each heater, you can set
the exact heater capacity and this will lead to more accurate energy
data.
#
Code
[A.2.3.1]
[6-02]
Booster heater: Only applies to domestic
hot water tanks with an internal booster
heater (EKHW*). The capacity of the
booster heater at nominal voltage.
Nominal value is 3 kW. Default: 0.
0~10 kW (in steps of 0.2 kW)
[A.2.3.2]
[6-03]
BUH: step 1: The capacity of the first
step of the backup heater at nominal
voltage. Nominal value 3 kW. Default:
3 kW.
0~10 kW (in steps of 0.2 kW)
[A.2.3.3]
[6-04]
BUH: step 2: Only applies to a two-step
backup heater (*9W). The capacity
difference between the second and first
step of the backup heater at nominal
voltage. Nominal value depends on the
backup heater configuration:
▪ 3 kW, 1N~ 230 V: 0 kW
▪ 6 kW, 1N~ 230 V: 3 kW (6 kW-3 kW)
▪ 6 kW, 3~ 230 V: 3 kW (6 kW-3 kW)
▪ 6 kW, 3N~ 400 V: 3 kW (6 kW-3 kW)
▪ 9 kW, 3N~ 400 V: 6 kW (9 kW-3 kW)
0~10 kW (in steps of 0.2 kW):
▪ *3V: default 0 kW
▪ *9W: default 6 kW
[A.2.3.6]
[6-07]
Bottom plate heater: Only applies to an
optional bottom plate heater
(EKBPHTH16A). The capacity of the
optional bottom plate heater at nominal
voltage. Default: 0 W.
0~200 W (in steps of 10 W)
8.2.5

Space heating/cooling control

The basic required settings in order to configure the space heating/
cooling of your system are described in this chapter. The weather-
dependent installer settings define the parameters for the weather-
dependent operation of the unit. When weather-dependent operation
is active, the water temperature is determined automatically
depending on the outdoor temperature. Low outdoor temperatures
will result in warmer water and vice versa. During weather-
dependent operation, the user has the possibility to shift up or down
the target water temperature by a maximum of 5°C.
See the user reference guide and/or operation manual for more
details about this function.
ERHQ011~016BA + ERLQ011~016CA + EHVH/X16S18+26CA
Description
Description
Daikin Altherma - Low Temperature Split