Daikin Aurora Series Service Manual page 146

Hide thumbs Also See for Aurora Series:
Table of Contents

Advertisement

Field Setting from Outdoor Unit
[2-60]: Gas furnace setting
Default value: 0.
When a gas furnace is connected, the setting [2-60] has to be changed to 1.
[2-78]: Heat pump lockout temperature
Heat pump is locked out when the outdoor air temperature is smaller than the heat pump lockout
temperature.
This is only effective when the heat pump lockout 2 setting [2-37] is Mode 3 to 6.
0 (default)
[2-79]: Heat pump lockout release differential
Heat pump is resumed when the outdoor air temperature is recovered by differential above the heat
pump lockout temperature.
1 (default)
[2-81]: Cooling comfort setting
1 (default)
This setting is used in conjunction with setting [2-8].
[2-82]: Heating comfort setting
1 (default)
This setting is used in conjunction with setting [2-9].
133
Value
Heat pump lockout temperature
[2-78]
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Value
Heat pump lockout release differential
[2-79]
0
2
Value
[2-81]
0
2
3
Value
[2-82]
0
2
3
–26.1°C (–15°F)
–23.3°C (–10°F)
–20.5°C (–5°F)
–17.7°C (0°F)
–15°C (5°F)
–12.2°C (10°F)
–9.4°C (15°F)
–6.6°C (20°F)
–3.8°C (25°F)
–1.1°C (30°F)
1.6°C (35°F)
4.4°C (40°F)
7.2°C (45°F)
10°C (50°F)
Forced heat pump lockout
2.8°C (5°F)
5.6°C (10°F)
8.3°C (15°F)
Cooling comfort setting
Eco
Mild
Quick
Powerful
Heating comfort setting
Eco
Mild
Quick
Powerful
SiUS341802E
Field Settings and Test Operation