EBS CPX200NWB Installation And Programming Manual page 100

Alarm control unit
Table of Contents

Advertisement

9.1.2.6. OUT
Format:
Limitations:
Description
9.1.2.7. FLUSH
Format:
Limitations:
Description
9.1.2.8. SENDSMS
Format:
Limitations:
Description
9.1.2.9. GETSTATUS
Format:
CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL
OUT=o,s,[time]
Can be executed only by ATS or administrator
Set the state 's' on the output 'o'.
o – output selection (1–3)
s – final output state (1 – on, 0 – off)
time – in case when output is switching on, duration can be described in
seconds. 0 means bistable state. If this parameter is not typed then output
will switch on for duration set during configuration.
Output can be switched off by remote command in any time regardless
from output set type and work mode.
Examples:
OUT=2,1
– switch on output 2 for time set during configuration
OUT=2,0
– switch off output 2
OUT=1,1,0 – switch on output 1 in bistable state
OUT=3,1,10 – switch on output 3 for 10 seconds
FLUSH=x
x is equal to 0 or 1, possible to execution only by ATS
For x = 0 it clears the queue of outstanding events to be sent to the OSM
server. This results in the loss of outstanding events – the device
generates then an event indicating the fact.
For x = 1 it clears the event log of the device.
SENDSMS=phone_no,text_wihout_spaces
This command does not work when sent via SMS; possible to execution
only by ATS
Allows you to send the SMS to the specified phone number (phone_no)
with the specified content. This command is a tool with which you can get
information about the phone number of the SIM card installed in the
device when connected to the OSM server using GPRS.
GETSTATUS
100 / 118

Advertisement

Table of Contents
loading