General Specifications; Network Wiring Specifications - Mitsubishi MELSEC-F FX2N-64CL-M User Manual

Cc-link/lt master block
Hide thumbs Also See for MELSEC-F FX2N-64CL-M:
Table of Contents

Advertisement

FX2N-64CL-M CC-Link/LT Master Block
2.1

General specifications

Item
Operating temperature
Storage temperature
Operating humidity
Vibration resistance
Shock resistance
Noise immunity
Dielectric withstand
voltage
Isolation resistance
Operating ambience
Working altitude
Grounding
*1 Do not use the PLC under pressure higher than the atmospheric pressure. Doing so may damage the PLC.
2.2

Network wiring specifications

Item
Communication speed
Distance between stations
Maximum number of
modules connected in 1
drop line
Maximum trunk length
T-branch interval
Maximum drop length
Cumulative drop line
length
0 to 55°C (32 to 131°F)
-20 to 70°C (-4 to 158°F)
35 to 85%RH (Dew condensation should not be allowed.)
Direct mounting
Frequency
Acceleration
10 to 57Hz
57 to 150Hz
9.8m/s
DIN rail mounting
Frequency
Acceleration
10 to 57Hz
57 to 150Hz
4.9m/s
2
147 m/s
, working time: 11 ms, half sine wave, three times in each of X, Y and Z
directions
By noise simulator of noise voltage = 1,000 Vp-p, noise width = 1 µs, rising = 1 ns,
cycle = 30 to 100 Hz
500V AC for 1 min
5 MΩ or more by 500V DC
megger
Do not use in a corrosive gas, flammable gas or conductive dust environment.
*1
<2000m
Class D grounding
(Common grounding with a heavy electrical system is not allowed.)
2.5Mbps
35m (114' 9")
4m (13' 1")
15m (49' 2")
Specification
Half amplitude
--
0.075mm
2
--
Half amplitude
--
0.035mm
2
--
In conformance to JEM-1021
Between case and PLC grounding terminal
Specification
625kbps
156kbps
No restriction
8 units
100m (328' 1")
500m (1640' 5")
No restriction
16m (52' 5")
60m (196' 10")
50m (164' 0")
200m (656' 2")
Specifications 2
Number of sweep times
10 times in each of the X, Y and Z
directions (for 80 min)
Remarks
--
--
Maximum number of
remote modules
connected per branch in
a drop line
Cable length between
terminating resistors
--
Cable length per branch
Sum of all drop lines
2-2

Advertisement

Table of Contents
loading

Table of Contents