WAGO I/O System 750
750-637 Incremental Encoder Interfaces

Table 30: Status Byte S1, All Versions, Except 750-637/000-004

Bit 7
0
MapPZD
MapPZD
StaN1
StaN2
N1
N2
0
0

Table 31: Status Byte S1, Version 750-637/000-004

Bit 7
0
MapPZD
Set Cam_Ack
N1_F2
N2_F2
N1_F1
N2_F1
0
0
Status Byte S1
Bit 6
Bit 5
Bit 4
0
N2
N1
Coding of Process Data
Coding of Process Data
Status Cam Output 1
0:
Cam output 1 is not set
1:
Cam output 1 is set
Status Cam Output 2
0:
Cam output 2 is not set
1:
Cam output 2 is set
Cam Window 1
Lower comparison value N1_LO ≤ counter value ≤ upper
Bit is set when:
comparison value N1_HI
Cam Window 2
Lower comparison value N2_LO ≤ counter value ≤ upper
Bit is set when:
comparison value N2_HI
Reserved
Reserved
Status Byte S1
Bit 6
Bit 5
Bit 4
0
N2_F1
N1_F1
Coding of Process Data
Collective and Ack Bit for All Cam Set Requests
One or more request bists 2,3,4 or 5 are set by the
Bit is set when:
control byte.
Cam 1, Window 2
Lower comparison value N1F2_LO < counter value <
Bit is set when:
upper comparison value N1F2_HI and cams enabled
(C1.6) and field voltage present (S0.6=0)
Cam 2, Window 2
Lower comparison value N2F2_LO < counter value <
Bit is set when:
upper comparison value N2F2_HI and cams enabled
(C1.6) and field voltage present (S0.6=0)
Cam 1, Window 1
Lower comparison value N1F1_LO < counter value <
Bit is set when:
upper comparison value N1F1_HI and cams enabled
(C1.6) and field voltage present (S0.6=0)
Cam 2, Window 1
Lower comparison value N2F1_LO < counter value <
Bit is set when:
upper comparison value N2F1_HI and cams enabled
(C1.6) and field voltage present (S0.6=0)
Reserved
Reserved
Public
Process Image
Bit 3
Bit 2
Bit 1
StaN2
StaN1
MapPZD
Bit 3
Bit 2
Bit 1
N2_F2
N1_F2
Set Cam_
39
Bit 0
MapPZD
Bit 0
MapPZD
Ack
Manual
Version 1.6.1

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-637750-637/000-001750-637/000-002750-637/000-003750-637/000-004